5

2

MODEL

DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER

OUTPUT

VOLTAGE ADJ. RANGE

LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)

VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)

INPUT

INRUSH CURRENT (Typ.)
LEAKAGE CURRENT

SAFETY STANDARDS

WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION

MTBF
DIMENSION

OTHERS

PACKING

OVERLOAD

OVER VOLTAGE

BATTERY CUTOFF

AC CURRENT (Typ.)

UL6

-1

2368 , BS EN/EN62368-1, AS/NZS62368.1, EAC TP TC 004 approved; Design refer to GB 17945-2010, GB4717

-20 ~ +60

(Refer to "Derating Curve")

20 ~ 95% RH non-condensing

-30 ~ +85

, 10 ~ 95% RH non-condensing

±

0.03%/

(0 ~ 50

)

10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes

0.75Kg; 15pcs/12.25Kg/0.7CUFT

RIPPLE & NOISE (max.)

Note.2

VOLTAGE TOLERANCE

Note.3

ENVIRONMENT

SAFETY &
EMC

(Note 4 & 5)

PROTECTION

WITHSTAND VOLTAGE
ISOLATION RESISTANCE

I/P-O/P:3KVAC

I/P-FG:2KVAC

O/P-FG:0.5KVAC

I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25

/ 70% RH

OUTPUT NUMBER

215*115*30mm (L*W*H)

EMC IMMUNITY

EMC EMISSION

Parameter

Parameter

ESD

Radiated

EFT / Burst

Surge

Conducted

Magnetic Field

Conducted

Radiated

Harmonic Current

Voltage Flicker

Standard

Standard

BS EN/EN55032 (CISPR32),
EAC TP TC 020

BS EN/EN55032 (CISPR32),
EAC TP TC 020

BS EN/EN61000-4-2

BS EN/EN61000-4-3

BS EN/EN61000-4-4

BS EN/EN61000-4-5

BS EN/EN61000-4-6

BS EN/EN61000-4-8

Test Level / Note

Test Level / Note

Class A

Class A

-----

-----

-----

-----

1394.9K hrs min.

Telcordia SR-332 (Bellcore);

153.3K hrs min.

MIL-HDBK-217F (25

)

?

FUNCTION

CHARGER CIRCUIT FAIL

AC OK

Battery

, battery reverse polarity signal failure

,

disconnected

2000ms, 50ms/230VAC

2000ms, 50ms/115VAC at full load

47 ~ 63Hz

86%

86.5%

8A/115VAC

4A/230VAC

COLD START 60A/115VAC

60A/230VAC

<0.5mA / 240VAC

CH1:105 ~ 135%

CH2:90 ~ 110%

21.5V 0.5V

±

32V 0.5V

±

CH1:31 ~ 36V

CH1:47 ~ 55V

LAD-360BU

LAD-360CU

27.6V

CH2

41.5V

CH2

27.6V

CH1

41.5V

CH1

11.5A

7.14A

0 ~ 13A

0 ~ 8.64A

358.8W

358.56W

--------

--------

150mVp-p

240mVp-p

CH1: 21.6 ~ 29V

CH1: 32.4 ~ 43.5V

--------

--------

--------

--------

--------

--------

±

1.0%

±

1.0%

±

0.5%

±

0.5%

±

0.5%

±

0.5%

90 ~ 132VAC / 180 ~ 264VAC by switch

240 ~ 370VDC

(Default switch at 230VAC)

16ms/230VAC

12ms/115VAC at full load

86.5%

43V 0.5V

±

CH1:59 ~ 69V

LAD-360DU

55 2V

.

CH2

55 2V

.

CH1

5.03A

0 ~ 6.53A
360.46W

--------

240mVp-p

CH1: 43 5 ~ 58V

.

--------

--------

--------

±

0 5%

.

±

0.5%

±

0.5%

BATTERY STATIC DISCHARGE
CURRENT

<100μA

BUZZER ALARM

Battery low( fire alarm system selectable by UART)

OVER TEMPERATURE
BATTERY REVERSE POLARITY

Protected when reverse polarity , no damage, recovers automatically after fault condition is removed

Level 3, 8KV air ; Level 2, 6KV contact; criteria A

Level 3, 10V/m ; criteria A

Level 3, 2KV ; criteria A

Level 3, 1KV/Line-Line ;2KV/Line-FG ;criteria A

Level 3, 10V ; criteria A

Level 4, 30A/m ; criteria A

115VAC Input :

when input voltage <75VAC

Signals AC failure and activates

Recover the main power supply when input voltage >85VAC

230VAC Input :

when input voltage <165VAC

Signals AC failure and activates

Recover the main power supply when input voltage >175VAC

AC fail, Battery low,

disconnected

selectable by

battery

, battery reverse connect, overload status (evacuation system

UART)

Protection type : Shut down o/p voltage, re-power on to removed

Protection type : Shut down o/p voltage, re-power on to removed

Protection type : CH1 OLP, CH2 with battery: he unit will enter to UPS mode when CH1 is around 105%~120%,

T

when total output of CH1 + CH2 reach around 125%~135% output shuts down

CH1 OLP, CH2 without battery:Shut down o/p voltage,re-power on to removed
CH2 : Constant current limiting; fault condition does not affect CH1 working,recovers automatically after fault

condition is removed (External fuse is mandatory in series connection with battery for protection)

1.5A(Battery Charger)
--------

1.5A(Battery Charger)
--------

1.5A(Battery Charger)
--------

LAD-360xU Series UART Communication Function Model(U Version)

6

2

DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER

VOLTAGE ADJ. RANGE

LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)

VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)

INRUSH CURRENT (Typ.)
LEAKAGE CURRENT

SAFETY STANDARDS

WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION

MTBF
DIMENSION
PACKING

OVERLOAD

OVER VOLTAGE

BATTERY CUTOFF

AC CURRENT (Typ.)

UL62368-1,

approved;

BS EN/EN62368-1 AS/NZS62368.1,

,

Design refer to GB 17945-2010

EAC TP TC 004

-20 ~ +60

(Refer to "Derating Curve")

20 ~ 95% RH non-condensing

-30 ~ +85

, 10 ~ 95% RH non-condensing

±

0.03%/

(0 ~ 50

)

10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes

RIPPLE & NOISE (max.)

Note.2

VOLTAGE TOLERANCE

Note.3

WITHSTAND VOLTAGE
ISOLATION RESISTANCE

I/P-O/P:3KVAC

I/P-FG:2KVAC

O/P-FG:0.5KVAC

I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25

/ 70% RH

OUTPUT NUMBER

215*115*30mm (L*W*H)

EMC IMMUNITY

EMC EMISSION

Parameter

Parameter

ESD

Radiated

EFT / Burst

Surge

Conducted

Magnetic Field

Conducted

Radiated

Harmonic Current

Voltage Flicker

1160.5K hrs min.

Telcordia SR-332 (Bellcore);

126.5K hrs min.

MIL-HDBK-217F (25

)

?

DISCHARGE

TTL signal, High / Open :

; Low : Charge ; Ice : max. 30mA@ 50VDC

Discharge

BATTERY FULL

AC OK

TTL signal, High / Open : AC OK ; Low : AC Fail ; Ice : max. 30mA@ 50VDC

TTL signal, High / Open : Battery full ; Low : Battery charging ; Ice : max. 30mA@ 50VDC

2000ms, 50ms/230VAC

2000ms, 50ms/115VAC at full load

47 ~ 63Hz

86%

86.5%

8A/115VAC

4A/230VAC

COLD START 60A/115VAC

60A/230VAC

<0.5mA / 240VAC

CH1:105 ~ 135%

CH2:90 ~ 110%

21.5V 0.5V

±

32V 0.5V

±

CH1:31 ~ 36V

CH1:47 ~ 55V

LAD-360B

LAD-360C

27.6V

CH2

41.5V

CH2

27.6V

CH1

41.5V

CH1

1.5A(Battery Charger)

11.5A

7.14A

0 ~ 13A

0 ~ 8.64A

358.8W

358.56W

--------

--------

150mVp-p

240mVp-p

CH1: 21.6 ~ 29V

CH1: 32.4 ~ 43.5V

--------

--------

--------

--------

--------

--------

±

1.0%

±

1.0%

±

0.5%

±

0.5%

±

0.5%

±

0.5%

90 ~ 132VAC / 180 ~ 264VAC by switch

240 ~ 370VDC

(Default switch at 230VAC)

16ms/230VAC

12ms/115VAC at full load

86.5%

43V 0.5V

±

CH1:59 ~ 69V

LAD-360D

55 2V

.

CH2

55 2V

.

CH1

5.03A

0 ~ 6.53A
360.46W

--------

240mVp-p

CH1: 43 5 ~ 58V

.

--------

--------

--------

±

0 5%

.

±

0.5%

±

0.5%

<100μA

BATTERY STATIC DISCHARGE
CURRENT

OVER TEMPERATURE

Standard

Standard

BS EN/EN55032 (CISPR32),
EAC TP TC 020

BS EN/EN55032 (CISPR32),
EAC TP TC 020

BS EN/EN61000-4-2

BS EN/EN61000-4-3

BS EN/EN61000-4-4

BS EN/EN61000-4-5

BS EN/EN61000-4-6

BS EN/EN61000-4-8

-----

-----

Test Level / Note

Test Level / Note

Level 3, 8KV air ; Level 2, 6KV contact; criteria A

Level 3, 10V/m ; criteria A

Level 3, 2KV ; criteria A

Level 3, 1KV/Line-Line ;2KV/Line-FG ;criteria A

Level 3, 10V ; criteria A

Level 4, 30A/m ; criteria A

Class A

Class A

-----

-----

BATTERY DISCONNECT/
REVERSE POLARITY
BATTERY LOW

TTL signal, High / Open : Battery disconnect/reverse polarity ; Low : Battery connect/normal; Ice : max. 30mA@ 50VDC

TTL signal, High / Open : Battery low ; Low : Battery normal; Ice : max. 30mA@ 50VDC

Protection type : Shut down o/p voltage, re-power on to removed

Protection type : Shut down o/p voltage, re-power on to removed

0.75Kg; 15pcs/12.25Kg/0.7CUFT

Protection type : CH1 OLP, CH2 with battery: he unit will enter to UPS mode when CH1 is around 105%~120%,

T

when total output of CH1 + CH2 reach around 125%~135% output shuts down

CH1 OLP, CH2 without battery:Shut down o/p voltage,re-power on to removed
CH2 : Constant current limiting; fault condition does not affect CH1 working,recovers automatically after fault

condition is removed (External fuse is mandatory in series connection with battery for protection)

BATTERY REVERSE POLARITY

Protected when reverse polarity , no damage, recovers automatically after fault condition is removed

--------

1.5A(Battery Charger)
--------

1.5A(Battery Charger)
--------

OTHERS

ENVIRONMENT

SAFETY &
EMC

(Note 4 & 5)

PROTECTION

FUNCTION

OUTPUT

INPUT

MODEL

LAD-360x Series TTL Communication Function Model(Blank Version)

Summary of Contents for LAD Series

Page 1: ...LAD Series Economical Security Fire Alarm PSU with Battery Charger UPS User Manual Back up Charger Power Supply LAD 120 240 360 600 Series AC Grid Load Battery Pack UART RTU DATA PROTOCOL AC DC...

Page 2: ...dc and 55 2Vdc With high efficiency up to 86 5 and built in AC battery switch for easy maintenance In addition LAD 600 series not only provide TTL signals for AC OK battery disconnect battery reverse...

Page 3: ...case 3 3 Wiring use 3 4 Installation steps 3 5 Instructions for battery serial and parallel use 4 User Interface Panel 4 1 Panel description 4 2 Pin assignment 5 Function Description 5 1 DC UPS funct...

Page 4: ...en power supply and battery should be kept as short as possible to prevent excessive voltage drop suggested cable length 50cm 1000cm Too much voltage drop will lead to longer charging period d The pow...

Page 5: ...elcordia SR 332 Bellcore 209 4K hrs min MIL HDBK 217F 25 1A Battery Charger 1A Battery Charger 1A Battery Charger 4 2 MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER OUTPUT VOLTAGE ADJ RANGE...

Page 6: ...ery for protection 1 5A Battery Charger 1 5A Battery Charger 1 5A Battery Charger LAD 360xU Series UART Communication Function Model U Version 6 2 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER VO...

Page 7: ...62368 1 AS NZS62368 1 EAC TP TC 004 approved Design refer to GB 17945 2010 GB4717 LAD 600xU Series UART Communication Function Model U Version 8 2 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER VO...

Page 8: ...264 90 100 80 70 60 50 40 180 264VAC 90 132VAC 90 100 115 110 160 140 200 180 240 220 264 90 100 80 70 120 LAD 120 Series LOAD LAD 0 Series 24 360 LOAD INPUT VOLTAGE VAC 60Hz 2 10 LAD 600 Series TB1 7...

Page 9: ...ws and internal components of power supplies Please refer to case drawing on specifications to receive the maximum length of mounting screw Mounting orientations other than standard orientation or ope...

Page 10: ...nected Disconnected S W AC ON OFF S W 3 4 2 Make sure all cables are well connected then feeds the AC to power the supply and turn the main power and backup power switches to the ON position 5 11 gf c...

Page 11: ...rminal contacts It is used control and status monitoring etc For details to please refer to Chapter 4 2 1 It is used control and status monitoring etc For details to please refer to Chapter 4 2 2 4 2...

Page 12: ...l AC OK battery unconnected reverse connection battery undervoltage full linkage control battery selection buzzer alarm battery detection forced start of battery power supply etc 5 1 DC UPS function L...

Page 13: ...no AC input power supply when the backup power switch is OFF PIN 1 and 2 need to be short circuited all the time to force the UPS function to start and keep the battery powered when PIN 1 2 is open t...

Page 14: ...y is reversely connected and the output is overloaded the buzzer will alarm Pin 7 8 Short Open Fire alarm system Evacuation system Open Short BU CU DU Evacuation system Fire alarm system Status 5 2 Ba...

Page 15: ...oltage 50V max Low High or open Description R V 4 5 24 5 3 Battery disconnected reverse TTL signal battery detection status 2 When the battery is not connected or reversely connected the state is high...

Page 16: ...LAD 360 600U can be set and read through communication and multiple parallel connections cannot be used in the configuration 5 4 1 1 UART specification Protocol adopts UART interface This device adop...

Page 17: ...ition of data types The data transmission patterns of this agreement are defined as follows 5 4 1 5 Scratchpad Address Data Description Controller PC to LAD datasheet Data type Narrate Bytes Range U1...

Page 18: ...a total of 4 bytes LAD_STATUS_H at the high level and LAD_STATUS_L at the low level 5 30 LAD_STATUS_H Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 High byte Reserved Reserved Reserved Reserved Reserved Re...

Page 19: ...es of Communications The following provides an example of reading and writing to t UART he communication protocol Note 5 4 2 1 5 4 2 6 provides an example for reading instructions 5 4 2 7 5 4 2 9 is a...

Page 20: ...1 battery is normal 0 Battery balanced state Standby OVP protection status Linkage control status display System power supply status Standby UTP protection status Main discharge OLP status Standby sta...

Page 21: ...ion is 0x9F CRC 8 5 4 1 3 the 5 Response R W byte Data Length Data address bytes Data bytes CRC 8 0x55 0x05 0x00 30 0x02 91 0xBD 36 5 4 2 4 Battery voltage Brief description Battery voltage read instr...

Page 22: ...refer to the description of in CRC 8 5 4 1 3 The error detection code for the response is calculated by the CRC 8 LAD LAD s own MCU 5 4 2 6 Battery undervoltage protection points Brief description Bat...

Page 23: ...his command is 0 01V transmitted that is the decimal number of the data to be is 43 2 0 01 4320 and the corresponding hexadecimal number is 0x0E E8 0x0D CRC 8 Transmit data error detection code refer...

Page 24: ...t the power supply turns off the output Recycle AC power to recover the output Once the LAD 600 triggers the protection the output recovers after recycling AC power and 3 minutes of cold standby 6 42...

Page 25: ...al Please refer to the latest version of our manual on our website www meanwell com https MEAN WELL WEB User s Manual This product provides three years warranty under normal usage Do not replace parts...

Page 26: ......

Reviews: