29
LAD to Controller/PC data sheet
R/W
byte
Data address
bytes
The data name
narrate
Numeric range
The length
of the data
unit
0x55
0x0010
LAD status
LAD status flag
Instructions for
transmitting data
4 bytes
-
0x0020
Principal
electrical voltage
Input voltage
0~65535
2 bytes
0.1V
0x0030
Load current
Load current
0~65535
2 bytes
0.01A
0x0040
Battery voltage
Total battery
series voltage
0~65536
2 bytes
0.01V
0x0050
Single cell battery
voltage
Single cell battery
voltage
0~65536
8 bytes
0.01V
0x0060
Battery
undervoltage
protection point
Battery ULP point
read
0~65536
2 bytes
0.0
5.4.1.6 Instructions for Transmitting Data:
Data is transferred in packets, reducing transfer time and avoiding
excessive data processing.
The user reads and
writes the set bit
Data address
range
Address used
Note
Controller/
PC to LAD
0x55、0xAA
0x0001~0xFFFF
0x0010~0x0060
1. 0x55 is used for reading LAD
parameters
2. 0xAA for writing to the LAD
parameter configuration
LAD to
Controller/
PC
0x55
0x0001~0xFFFF
0x0010~0x0060
1. Transmit the required packets
according to the user's sending
address
5.4.1.7 LAD _STATUS defined as follows:
The LAD_STATUS consists of two parts, LAD_STATUS_H and
LAD_STATUS_L, with a total of 4 bytes, LAD_STATUS_H at the high level
and LAD_STATUS_L at the low level.
5
30
LAD_STATUS_H:
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
High byte
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Low byte
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
BAT_SW_OFF
LAD_STATUS_L
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
High byte
Force_Status
BAT_REV
BAT_CHGI
NG
BAT_CHGFU
LL
BAT_ERROR
_4
BAT_ERROR
_3
BAT_ERROR
_2
BAT_ERROR
_1
Low byte
BAT_
NO_Balance
BAT_OVP
Link_Ctrl
LAD Power
Supply
BAT_UVP
DISCHARG
E_OLP
BAT_NC
AC_OK
High byte:
Bit 0 - Bit 7 Reserved:
0
Currently unused, reserved (default is , displayed
status is not supported as 0)
Low byte:
Bit 0 BAT_SW_OFF: Standby switch status display
0 = The standby switch is normal
= Standby switch disconnected
1
Bit 1 – Bit 7: Currently unused, reserved (default is , displayed status is
0
not supported as 0)
Low byte:
Bit 0 AC_OK AC
:
input status
0=AC input exception
1=AC input is normal
Bit 1 BAT_NC: Power-up status
0 = Standby access is normal
1 = Abnormal power backup access
Bit 2 DISCHARGE_OLP
OLP
: The
state of the main discharge
0 = The main discharge is normal
1 = Main discharge overload
Bit 3 BAT_UVP
ULP
: Power-up
protection status
0 = No backup
protection
UTP
1
UPP
= Power backup
protection has occurred
Bit 4 LAD Power Supply: System power supply status
0 = Main power supply status
1 = Standby power supply status
5