Installation Manual

 

 

 

 

Type

General Type DIN rail with Three Phase or High Input Range

 

Series

DRH-120, DRT-240, DRT-480, DRT-960

 

DRH-120-24 

INPUT: 400 -500VAC 0.65A 50/60Hz 

OUTPUT: 24V 5A 

DRH-120-48 

INPUT: 400 -500VAC 0.65A 50/60Hz 

OUTPUT: 48V 2.5A 

DRT-240-24  

INPUT: 400 -500VAC 0.95A 50/60Hz 

OUTPUT: 24V 10A 

DRT-240-48  

INPUT: 400 -500VAC 0.95A 50/60Hz 

OUTPUT: 48V 5A 

DRT-480-24  

INPUT: 400 -500VAC 1.7A 50/60Hz 

OUTPUT: 24V 20A 

DRT-480-48  

INPUT: 400 -500VAC 1.7A 50/60Hz 

OUTPUT: 48V 10A 

DRT-960-24  

INPUT: 400 -500VAC 2.4A 50/60Hz 

OUTPUT: 24V 40A 

DRT-960-48  

INPUT: 400 -500VAC 2.4A 50/60Hz 

OUTPUT: 24V 20A 

 

 

Introduction 

General  type  with  three  phase  or  high  input  range  is  a  DIN  rail  power  supply  series  with  a  high  input  range, 
340-550Vac. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source. 

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the  top  for  DRH-120,  the  input  terminals  on  the  right  and  output  on  the  left  for  DRT-240,  DRT-480  and 
DRT-960. Mounting orientations other than that,  such as upside  down,  horizontal, or table-top mounting,  is 
not allowed. 

 
 
 
 
 
 
 
 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

10 

Rated Current of 
Equipment (Amp) 

6A 

6-10A 

13-16A 

16-25A 

25-32A 

Cross-section of 
Lead(mm

2

 ) 

0.75 

1.00 

1.5 

2.5 

Note: Current each wire carries should be de-rated to 80% of the current suggested   

above when using 5 or more wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact. 

4

Use wires that can withstand temperatures of at least 80°C such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197”). 

6

Recommended screwdriver is

 

4mm, slotted type. 

7

The recommended torque setting for terminals is 10 kgf-cm (9 Lb-in). 