Installation Manual

 

 

 

 

Type

DRDN20/40 DIN rail Type Redundancy Module

 

 

DRDN20-12  

INPUT

1

9-14VDC 20A 

  OUTPUT

20A (max) 

2

9-14 VDC  20A 

DRDN20-24  

INPUT

1

19-29VDC 20A  

OUTPUT

20A (max) 

2

19-29VDC 20A 

DRDN20-48  

INPUT

1

36-60VDC 20A  

OUTPUT

20A (max) 

2

36-60VDC 20A 

DRDN40-12  

INPUT

1

9-14VDC 40A 

  OUTPUT

40A (max) 

2

9-14 VDC  40A 

DRDN40-24  

INPUT

1

19-29VDC 40A  

OUTPUT

40A (max) 

2

19-29VDC 40A 

DRDN40-48  

INPUT

1

36-60VDC 40A  

OUTPUT

40A (max) 

2

36-60VDC 40A 

 

 

Introduction 

DRDN20/40 is a DIN rail type redundancy module. 
Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating.   

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom. Mounting 

orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed. 

 
 
 
 
 
 

 

 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 18 

16 

14 

12 

10 

Rated Current of 
Equipment (Amp) 

7A  10A  15A 20A  30A  40A 50A 

Cross-section of 
Lead(mm

2

 ) 

0.8 1.3 2.1 

3.3 5.3 8.4 

13.3 

Note: 1. Current each wire carries should be de-rated to 80% of the current suggested above when 

using 5 or more wires connected to the unit. 

2. The maximum allowable wire cross-sectional area for the terminal is 6AWG/13.3 mm

2

   

 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C, such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197”). 

6

Recommended screwdriver is 4mm, slotted type. 

Summary of Contents for DRDN20

Page 1: ...the bottom Mounting orientations other than that such as upside down horizontal or table top mounting is not allowed 3 Use copper wire only and recommended wires are shown as below AWG 18 16 14 12 10...

Page 2: ...ut terminals down or else sufficient cooling will not be possible Admissible DIN rail TS35 7 5 or TS35 15 For rail fastening a Tilt the unit slightly rearwards b Fit the unit over top hat rail c Slide...

Page 3: ...anual 2 1 N Redundancy Using more PSUs as the redundant units to increase the reliability 3 Single Use Connecting only one PSU to one DRDN20 40 to reduce the stress of the MOSFET and hence increase th...

Page 4: ...ntenance or modification work Disconnect your system from supply voltage Make sure that inadvertent connection in circuit will be impossible 10 For continued protection against risk of fire replace on...

Page 5: ...oducts Appendix B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hex...

Page 6: ...to China s Standardization Administration Releases VOC Standards Standard No Name of the Standard GB 30981 2020 Limit of harmful substances of industrial protective coatings GB 33372 2020 Limits for v...

Page 7: ...eby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6 h CAS No Substance Name 1163 19 5 Decabromodiphenyl ether DecaBDE 68937 41 7...

Reviews: