background image

                           

Installation Manual

 

 

 

 

Type

DDRH Ultra Wide Input DIN Rail Type DC-DC Converter

 

DDRH-60-5   

INPUT: 150~1500VDC      OUTPUT: 5V 10A   

DDRH-60-12  

INPUT: 150~1500VDC    OUTPUT: 12V 5A 

DDRH-60-24  

INPUT: 150~1500VDC    OUTPUT: 24V 2.5A 

DDRH-60-48  

INPUT: 150~1500VDC    OUTPUT: 48V 1.25A 

 

 

Introduction 

DDRH series is a DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, 57mm 
slim width, 10: 1 ultra wide input voltage, -30~+80

wide range operating temperature, DC OK relay contact and 

full protective functions...etc. 
This series has ultra-high input voltage: 150~1500Vdc and various output options: 5V / 12V /24V / 48V. It is suitable 
for industrial automation, surveillance, telecommunication and can be widely deployed in the applications of new 
energy generation such as solar power, and windmill power generation, for instances, photovoltaic power systems, 
high voltage inverting and so forth. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating.   

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not 
allowed. 

 
 
 
 
 
 
 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 20 

18 

16 

14 

Rated Current of Equipment 

(Amp) 

5A 7A 10A 15A 

Cross-section of Lead(mm

2

 ) 

0.5 

0.8 

1.3 

2.1 

Note

Current each wire carries should be de-rated to 80% of the current suggested above when 

using 4-6 wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 90°C, such as UL1015. 

5

Recommended wire strapping length is 6mm (0.236”). 

6

Recommended screwdriver is 3mm, slotted type. 

7

The recommended torque setting for terminals is shown as below. 

I/P O/P 

6 kgf-cm (5.2Lb-in) 

5.1kgf-cm (4.42 Lb-in) 

 

8

External fuse wiring instruction : 

Summary of Contents for DDRH-60-5

Page 1: ...unit in use to prevent it from overheating 2 The appropriate mounting orientation for the unit is vertical the input terminals at the bottom and output on the top Mounting orientations other than tha...

Page 2: ...lfuse_fuse_solar_spxv_datash eet pdf https www littelfuse com media electrical datasheets fuse blocks and holders dead front fuse holders lit telfuse_fuse_holder_lfpxv_datasheet pdf https www littelfu...

Page 3: ...disconnection 4 Risk of fire and short circuit The openings should be protected from foreign objects or dripping liquids 5 Only install the unit in a pollution degree 2 environment Note 1 6 Please do...

Page 4: ...ZHOU ENTERPRISES Co LTD 2F A Building Yuean lndustry Park Huangcun Dongpu Yown Tianhe District Gungzhou China Post Code 510660 Tel 86 20 2887 1200 Web www meanwell com cn U S A MEAN WELL USA INC 44030...

Page 5: ...oducts Appendix B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hex...

Page 6: ...to China s Standardization Administration Releases VOC Standards Standard No Name of the Standard GB 30981 2020 Limit of harmful substances of industrial protective coatings GB 33372 2020 Limits for v...

Page 7: ...eby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6 h CAS No Substance Name 1163 19 5 Decabromodiphenyl ether DecaBDE 68937 41 7...

Reviews: