Technical Manual
Motion Detector/Automatic Switch 55/63
Series .02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
41
41
4.5.1.2 Basic function
–
Dimming
Two-button function
The following picture shows the available settings:
Figure 24: Settings
–
Two-button function: Dimming
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Button assignment
(left/right)
▪
brighter/darker
▪
darker/brighter
Setting the button assignment for
the direction (brighter/darker).
Table 26: Settings
–
Two-button function: Dimming
The two-
button function “dimming” can be set either as
brighter/darker or as darker/brighter. The
relationships are shown in the following table:
Function brighter/darker
Function brighter/darker
Button
Button left
Button right
Button left
Button right
Dimming function
brighter
darker
darker
brighter
Switching function
ON
OFF
OFF
ON
Table 27: Functionality
–
Two-button Dimming
The dimming function is a start-stop dimming, i.e., as soon as the dimming function becomes active,
a bright or dark command is assigned to the input until it is released. After release, a stop telegram is
sent, which ends the dimming process.
The following table shows the available communication objects:
Number
Name/Object Function
Length
Usage
131
Buttons left/right
–
Dimming On/Off
1 Bit
Switching command for the dimming function
132
Buttons left/right
–
Dimming relative
4 Bit
Command for relative dimming
Table 28: Communication objects
–
Two-button function: Dimming