Technical Manual
Motion Detector/Automatic Switch 55/63
Series .02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
30
30
4.3.8 Process diagrams
Fully automatic without orientation light:
Figure 17: Process diagram
–
Fully automatic without orientation light
In the operating mode "Fully automatic" the Presence Detector switches on automatically when
motion is detected. The object "External push button short" can be used to override the automatic
mode of the motion detector and forces the presence detector into manual mode. From this mode,
the detector automatically returns to auto mode according to the settings in the menu "General
settings" - "Fallback for external push button ".
If the output of the light channel is switched on (automatic mode - ON or manual mode - ON) and the
light channel is switched off via the object "External push button short", then the light channel is
blocked for 10 seconds for motion detection in order to leave the room and prevent brief restart.
The detector can be switched to manual mode via the "external push-button - long" object. From this
mode, the detector automatically returns to auto mode accordin
g to the settings in the “General
settings” menu –
“Fallback for external push button”.