Technical Manual
Motion Detector/Automatic Switch 55/63
Series .02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
28
28
4.3.6 Idle time
Light channel
HVAC channel
The idle time defines the time for which the device is locked for further detection after it has been
switched off. Two settings are available for this:
Figure 15: Settings
–
Idle time
The following settings are available:
ETS-Text
Dynamic range
[Default value]
Comment
Idle time after external
button short is OFF
1 … 30 s
[5 s]
Setting of the time for which the device is
locked for further detection after it has
been switched off via "external push-
button short".
Idle time after switch-off
0 … 60 s
[1 s]
Setting the time for which the device is
locked for further detection after the
follow-up time has expired.
Table 16: Settings
–
Idle time
The parameter "
Idle time after external button short OFF
" is useful, for example, to leave the room
briefly after switching OFF via the external push-button without avoiding a renewed switching ON of
the light by detection.