4.4.5.5 Presentation (Symblols)
Single-button function
Two-button function
The display of the function "Send values" depends on the selected data point type. Depending on the
selected data point type, 1-4 different symbols and their color can be selected.
The following table provides an overview of the settings for the various datapoint types:
Datapoint type
Adjustable symbols
Comment
2 Bit Switch control, DPT 2.001
4 symbols can be set: 1 symbol
for each possible state
1 Byte Percent, DPT 5.001
Three icons can be set for the
ranges 0%, 1% - 90% and > 90%.
Therefore the button evaluates
the information of the "Status
for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Decimal factor, DPT
5.005
3 symbols can be set for the
ranges 0, 1-229 and 230-255.
Therefore, the button evaluates
the information of the "Status
for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Scene Number, DPT
17.001
1 fixed symbol can be set
2 Byte Color temperature
(Kelvin), DPT 7.600
1 fixed symbol can be set
2 Byte Temperature, DPT 9.001
1 fixed symbol can be set
Special presentation possible!
2 Byte Bgightness, DPT 9.004
1 fixed symbol can be set
3 Byte RGB Wert, DPT 232.600
1 fixed symbol can be set
Table 40: Presentation (Symbols) – Send values
Special presentation:
For certain data point types, a special presentation (see table above) is possible. In this presentation,
the status is shown on a larger scale on the display.
The following presentations are possible:
ETS-Text
Dynamic range
[Default value]
Comment
Special display
(DPT 5.001, DPT 5.005)
bar symbol
bar symbol with fan
value as text (0-100%)
value as text (0-255)
At the settings “bar symbol”
and “bar symbol with fan”, the
corresponding symbol is
displayed and the bar is filled
according to the current status.
With the settings "value as
text" the text is displayed large
on the display.
Special display (DPT 9.001)
value as “°C”
value as symbol without
unit
value as “K”
With the settings "value as
symbol" the text is displayed
large on the display.
Table 41: Special display – Send values