4.8.3.2 PI control switching (PWM)
If the control value is set as switching PI control (PWM), the following setting options are available
(here: controller type heating):
Figure 23: Settings - PI control switching (PWM)
The PWM control is a further development of the PI control. All settings possible for PI control can
also be made here. In addition, the PWM cycle time can be set.
The following table shows the settings for switching PI control:
ETS-Text
Dynamic range
[Default value]
Comment
Direction of controller
▪
normal
▪
inverted
Specifies the control behaviour with
rising temperature
Max value of control value
100%
; 90%; 80%; 75%; 70%; 60%;
50%; 40%; 30%; 25%; 20%; 10%; 0%
Specifies the output power of the
control value in maximum operation
Heating system
▪
Water heating (4K / 120 min)
▪
Underfloor heating (4K / 150
min)
▪
Split Unit (4K / 60min)
▪
Adjustment via control
parameter
Setting of the heating system used.
Individual parameterization possible via
setting 4
Cooling system
▪
Split Unit (4K / 60 min)
▪
Cooling ceiling (4K / 150 min)
▪
Adjustment via control
parameter
Setting of the cooling system used.
Individual parameterization possible via
setting 3
Proportional range (K)
1 K - 8 K
[4 K]
Only visible with setting "Adjustment
via control parameters
".
Here the proportional band can be set
freely
Reset time (min)
15 min
–
210 min
[150 min]
Only visible with setting "Adjustment
via control parameters
".
The integral range can be freely
adjusted here
PWM cycletime (min)
5min,
10min,
15min, 20min, 25min,
30min
Setting the PWM cycle time.
Includes the total time of a switch-on
and switch-off pulse
Table 58: Settings - PI control switching (PWM)