Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
156
156
LED display behaviour
At day
(value ON)
Any color
Color for the object value ON /
activated button in day mode
At day
(value OFF)
Any color
Color for the object value ON /
non-activated button in day
mode
Behavior at day
(value ON)
▪
permanent
▪
blinking
Setting the lighting behavior
when LED has the object value
ON or the key is pressed
At night
(value ON)
Any color
Color for the object value ON /
activated button in night mode
At night
(value OFF)
Any color
Color for the object value OFF /
non-activated button in night
mode
Behavior at night
(value ON)
▪
permanent
▪
blinking
Setting the lighting behavior
when LED has the object value
ON or the key is pressed
Table 151: Settings - LEDs 1-6/LED Direct buttons 1-4
Each LED can react either to any external object, such as the status of an actuator, an internal object
or the activation of a button. In addition, an LED can also react to an external or internal object and
the key operation. With this setting, the settings in menu LED 1-6/LED direct buttons 1-4 refer to the
control of the LED via the object. In this case, the behaviour of the key operation is set globally for all
LEDs and is described in menu 4.11.1 LED . The behaviour for key operation has priority.
If the setting LED reacts to "internal object" is selected, the object number with which the LED is to
be linked is selected. If the LED is to switch when the "Object 1 - Value for switchover" has the value
1, the object number 1 is to be entered. In this case the status LED would be switched on if the object
has a 1 and switched off if the object has a 0. If the LED is linked to an object which does not have a 1
bit size, the LED is switched off if the object has the value 0 and switched on if the value of the object
is not equal to 0. For an object of the DPT 5.001 - percent this would mean that the LED is switched
off at 0% and switched on at all other values.
Each LED can assume different colours and behaviour for day and night operation and switches on
depending on the object 121-Day/Night.
The following table shows the available communications objects:
Number
Name
Length
Usage
186 - 191
LED 1 -6
1 Bit
Control of the LED; object is only faded in if LED
reacts to external object
192 - 195
LED Direct button 1 - 4
1 Bit
Control of the direct button LED; object is only
faded in if LED reacts to external object
Table 152: Communication objects - LEDs 1-6/LED Direct buttons 1-4