Technical Manual Switch Actuator 3-fold, FanCoil
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.m
dt.de
18
3.2.2 Default settings of the communication objects
The following table shows the default settings of the communication objects:
Default settings
No.
Name
Object Function
Length Priority
C R W T
U
0
Additional
ventilation
Enable additional
ventilation
1 Bit
Low
X
X
1
Switching
Auto/Manual
1 = Automatic/ 0 =
Manual
1 Bit
Low
X
X X X
X
2
Automatic mode
Control value heating
1 Byte
Low
X
X
2
Automatic mode
Control value
heating/cooling
1 Byte
Low
X
X
3
Automatic mode
Control value cooling
1 Byte
Low
X
X
4
Automatic mode
Control value failure
1 Bit
Low
X
X
X
5
Automatic mode
Heating/Cooling
switchover
1 Bit
Low
X
X X X
X
6
Automatic mode
Switch heating valve
1 Bit
Low
X
X
X
7
Automatic mode
Switch cooling valve
1 Bit
Low
X
X
X
8
Automatic mode
Manual setpoint offset
1 Bit
Low
X
X
9
Direktbetrieb
Step 0
1 Bit
Low
X
X
9
Direktbetrieb
Bit 0
1 Bit
Low
X
X
9
Direktbetrieb
Up/Down
1 Bit
Low
X
X
10
Direktbetrieb
Step 1
1 Bit
Low
X
X
10
Direktbetrieb
Bit 1
1 Bit
Low
X
X
11
Direktbetrieb
Step 2
1 Bit
Low
X
X
12
Direktbetrieb
Step 3
1 Bit
Low
X
X
13
Status Input
(Cascading)
External heating
request
1 Bit
Low
X
X
14
Status Output
External heating
request
1 Bit
Low
X
X
X
15
Status Input
(Cascading)
External cooling request 1 Bit
Low
X
X
16
Status Output
External cooling request 1 Bit
Low
X
X
X
17
Status Input
(Cascading)
Maximum control value
for heating
1 Byte
Low
X
X
18
Status Output
Maximum control value
for heating
1 Byte
Low
X
X
X
19
Status Input
(Cascading)
Maximum control value
for cooling
1 Byte
Low
X
X
20
Status Output
Maximum control value
for cooling
1 Byte
Low
X
X
X
21
Status Input
(Cascading)
Maximum fan level
heating
1 Byte
Low
X
X
22
Status Output
Maximum fan level
heating
1 Byte
Low
X
X
X
23
Status Input
(Cascading)
Maximum fan level
cooling
1 Byte
Low
X
X
Summary of Contents for AKK-03UP.02