McQuay Templifier Installation Data Download Page 8

INSTALLATION

THERMAL INSULATION

Factory installed thermal insulation is furnished on all
parts of the Templifier unit as needed to prevent
sweating, to retain thermal efficiency, and to protect
operating personnel from hot surfaces.

Care should be taken not to tear, damage or remove
any of this factory insulation.

All field piping connections to the Templifier should be

insulated by the installer if required by good practice

and personnel safety.

ELECTRICAL

Wiring, fuse and wire size must be in accordance with

information provided in the Electrical Data. Standard
NEMA motor starters require modification to meet

McQuay specifications. Refer to Electrical Data sup-
plied with the unit for details.

IMPORTANT: The voltage of these units should be

within the limitation of plus or minus 10%, and the 

 

voltage unbalance between phases must not exceed
3%. Since a 3% % voltage unbalance will cause an
approximate 25% increase in motor temperature, it is

most important that the unbalance between phases be
at a minimum.

NOTE: Do not make final power connections to the
starter until wiring has been checked and approved by
an authorized McQuay Service Representative. Under

no circumstances should the compressor be brought
up to speed unless proper phase sequence and rotation
have been established. Serious damage may result if
the compressor starts in the wrong direction. Jog the
machine to check rotation using the sight glasses on
the rear motor cover to observe direction.

Power Wiring T**063/079/100/126

Power wiring to the compressor must be in proper
phase sequence. Motor rotation is set up for clockwise
rotation facing motor end cover with phase sequence

of l-2-3. Care should be taken that proper phase
sequence is carried through the starter to the compres-
s o r .   W i t h   t h e   p h a s e   s e q u e n c e   o f   l - 2 - 3   a n d   L1
connected to T1 and T6, L2 connected to T2 and T4,
and L3 connected to T3 and T5, rotation is proper. See

diagram in terminal box cover.

Phase sequence can be determined by using GE No.

546703265 phase sequence meter or equal. Before
connecting the starter load leads to the compressor
terminals and while checking the field connection
wiring, the transition timer in the starter should be
adjusted to make the transition in 15 seconds. This
should be reset when the compressor is put on the

line. The timer should be adjusted to actuate (discon-
nect Star winding connection and connect Delta)
when the motor has come up to speed and before any
speed reduction occurs.

CAUTION: Wiring connection to compressor terminal

studs must be made with copper lugs and copper wire.

Power Wiring T**048/050

All T**048/050 units are normally supplied with a
factory wired and mounted star delta starter equipped
with ambient compensated quick trip overloads, fac-
tory set at 1 

15% 

F.L.A. Wiring, fuse and wire size must

be in accordance with information located in the elec-
trical data supplied with the unit or the McQuay Electri-
cal Data pertaining to your unit.

The power wiring to the compressor starter must be i n

proper phase sequence. See second paragraph under

T**063/079/100/126 Power Wiring.

All units are factory equipped with open transition

starters. Closed transition starters are supplied on a
special order basis. Transition should be set to 15
seconds.

Control Wiring

The control circuit on the McQuay T**063/079/100

and 126 Templifiers is designed for 1 15 volts. Power
should be supplied from a separate circuit and fused at

10 amps. (See Table 2). The control circuit on the

TP048/050  unit is also designed for 115 volts, but

power is provided to the control panel by a .75 or 1
KVA 
1 15 volt transformer supplied and mounted in the

starter package.

T A B L E   2   M A X I M U M   C O N D U C T O R   L E N G T H *

Maximum length is distance conductor will traverse between

control power source and the unit control panel. Wire size based
on voltage drop not to exceed 3 percent.

Panel terminal connectors will accommodate wire size up to 10

AWG, larger conductors will require an intermediate junction box.

The disconnect switch should be tagged to prevent
current interruption. SWITCH IS TO REMAIN ON AT

ALL TIMES IN ORDER TO KEEP OIL HEATERS

8

Summary of Contents for Templifier

Page 1: ...SINGLE AND DUAL COMPRESSOR CENTRIFUGAL TEMPLlFlER HEAT PUMPS 13600 Industrial Park Blvd P 0 Box 1551 Minneapolis Minnesota 55440...

Page 2: ......

Page 3: ...nameplate affixed with certain data for the installer including electrical data for the compressors and oil pumps MODEL STYLE SERIAL _ S O NO FACTORY CHARGED LBS REFRIGERANT _ LEAK TEST PRESSURE 100 P...

Page 4: ...s to prevent damage to the control center and other components On units with side mounted compressors the unit can be lifted by the three corner fitting eyes and the extended eye at the compressor end...

Page 5: ...AL OR FLANGE CONNECTIONS THE SOLID STATE TEMPERATURE SENSOR AND THERMOSTAT BULBS MUST BE REMOVED FROM THE WELLS TO PREVENT DAMAGE TO THOSE COMPONENTS Small water pressure test valves or pipe plugs are...

Page 6: ...rop through the evaporator is greater or equal to the oil cooler pressure drop Under no circumstances should the oil cooler be piped in parallel with a single pass evaporator This will result in inade...

Page 7: ...n practice for all installations NOTE Remove plastic thread protectors from the inside of the valves prior to making pipe connections Whenever vent piping is installed the lines should be run in accor...

Page 8: ...an be determined by using GE No 546703265 phase sequence meter or equal Before connecting the starter load leads to the compressor terminals and while checking the field connection wiring the transiti...

Page 9: ...ol center for proper connections The purpose of the water flow interlocks is to prevent compressor operation until both the source water and condenser water pumps are running and flow is proven 9 Oper...

Page 10: ...OULD BE MAINTAINED ANY TIME REFRIGERANT IS ADDED OR REMOVED FROM THE SYSTEM CAUTION DO NOT USE OXYGEN TO BUILD UP PRESSURE AS A SERIOUS EXPLOSION CAN RESULT A pressure regulating valve should always b...

Page 11: ...able and helpful in charging with that refrigerant Important At this point the charging procedure should be inter rupted and pre start checks made before attempting to complete refrigerant charge The...

Reviews: