McQuay Templifier Installation Data Download Page 7

INSTALLATION

1. CEO63 Compressors

2. Lube Boxes
3. Suction Shutoff Valve
4. Condenser Relief Valves
5. Expansion Valves
6. Oil Pumps

7. Oil Level Sight Glass
8. Hot Gas Bypass
9. Oil Coolers

10. Discharge Check Valve
11. Motor Cooling Liquid Line
12. Motor Cooling Liquid Filter-Drier

13. Condenser Inlet
14. Condenser Outlet
15. Evaporator Inlet
16. Evaporator Outlet
17. Motor Terminal Cover
18. Liquid Line Shutoff Valve

FIGURE 6

TFH063 

(Rear View)

VENT PIPING

As a safety precaution, each system is equipped with

pressure relief valves located on the condenser and on

the evaporator for the purpose of relieving excessive

refrigerant pressure to the atmosphere. Many local
codes require that relief valves be vented to the
outside, and this is desirable installation practice for all
installations. NOTE: Remove plastic thread protectors

from the inside of the valves prior to making pipe

connections. Whenever vent piping is installed, the
lines should be run in accordance with local code
requirements; or where local codes do not apply, ANSI

B9-1  -Sec. 12 code recommendations should be

followed.

Current condenser design incorporates two relief
valves (1 set) with a 3-way shut-off valve separating
the two valves. (See Figure 7). When piping the vent
line to a dual valve set, it may be sized for one relief
valve and piped to both valves. If one relief valve of the

two valve set fails, the shut-off valve may be used to
isolate the faulty relief valve, easing replacement. On

Condenser Relief Valve Set

1. 

#l Relief 

Valve

2.

#2 Relief 

Valve

3.

Relief Valve 3-Way  Shutoff

4.

3-Way  Access Valve

FIGURE 7

larger capacity condenser designs, two sets of dual
relief valves are used. These vents must be sized for
the total of two valves.

Summary of Contents for Templifier

Page 1: ...SINGLE AND DUAL COMPRESSOR CENTRIFUGAL TEMPLlFlER HEAT PUMPS 13600 Industrial Park Blvd P 0 Box 1551 Minneapolis Minnesota 55440...

Page 2: ......

Page 3: ...nameplate affixed with certain data for the installer including electrical data for the compressors and oil pumps MODEL STYLE SERIAL _ S O NO FACTORY CHARGED LBS REFRIGERANT _ LEAK TEST PRESSURE 100 P...

Page 4: ...s to prevent damage to the control center and other components On units with side mounted compressors the unit can be lifted by the three corner fitting eyes and the extended eye at the compressor end...

Page 5: ...AL OR FLANGE CONNECTIONS THE SOLID STATE TEMPERATURE SENSOR AND THERMOSTAT BULBS MUST BE REMOVED FROM THE WELLS TO PREVENT DAMAGE TO THOSE COMPONENTS Small water pressure test valves or pipe plugs are...

Page 6: ...rop through the evaporator is greater or equal to the oil cooler pressure drop Under no circumstances should the oil cooler be piped in parallel with a single pass evaporator This will result in inade...

Page 7: ...n practice for all installations NOTE Remove plastic thread protectors from the inside of the valves prior to making pipe connections Whenever vent piping is installed the lines should be run in accor...

Page 8: ...an be determined by using GE No 546703265 phase sequence meter or equal Before connecting the starter load leads to the compressor terminals and while checking the field connection wiring the transiti...

Page 9: ...ol center for proper connections The purpose of the water flow interlocks is to prevent compressor operation until both the source water and condenser water pumps are running and flow is proven 9 Oper...

Page 10: ...OULD BE MAINTAINED ANY TIME REFRIGERANT IS ADDED OR REMOVED FROM THE SYSTEM CAUTION DO NOT USE OXYGEN TO BUILD UP PRESSURE AS A SERIOUS EXPLOSION CAN RESULT A pressure regulating valve should always b...

Page 11: ...able and helpful in charging with that refrigerant Important At this point the charging procedure should be inter rupted and pre start checks made before attempting to complete refrigerant charge The...

Reviews: