McQuay SEASONCON ALP-037A Manual Download Page 40

OPTIONAL CONTROLS

SPEEDTROL - HEAD PRESSURE CONTROL

ALP-037A thru 078B

The SPEEDTROL system of head pressure control operates
in conjunction with FANTROL by modulating the motor
speed on tans 11 and 21 in response to condensing pressure.

By reducing the speed of the last fan as the condensing
pressure falls, the unit can operate at lower ambient
temperatures.

The SPEEDTROL fan motor is a single phase, 208/240

volt, thermally protected motor specially designed for
variable speed application. The solid state speed controls

SC1 1 and SC21 are mounted inside the compressor
compartment near the top of the condenser coils. Units
with 460 volt power have a transformer mounted on the
back of the control box to step the voltage down to 230
volts for the SPEEDTROL motor.

The SPEEDTROL control starts to modulate the motor

speed at approximately 230 PSIG and maintains a mini-
mum condensing pressure of 170 to 180 PSIG.

DAMPERTROL - HEAD PRESSURE CONTROL

ALP-089B  thru 159B

DAMPERTROL is an optional system for reducing con-

denser capacity. It consists of an assembly of damper
blades, linkages and blade operators installed over the first
fan turned on by FANTROL (fan no. 11) and arranged to
operate as shown. The blade operators sense condenser

pressure and extend or contract in response to the pressure

to open or close the damper blades as required to maintain
adequate condenser pressure. The operators are factory set
to begin opening the damper blades at 

 5 PSIG and to

be fully open at 250   10 PSIG.

DAMPERTROL IN OPEN POSITION DAMPERTROL 

IN CLOSED POSITION

DAMPER

  S E C T I O N

  C O I L

To check the damper blade operator pressure settings,

the unit should be started with the fuses removed from fans

11 and 13 (on 3-fan units only). At condenser pressures

below 170   5 PSIG, the damper blades should be com-
pletely closed. As pressure rises above 170   5 PSIG, the
damper blades should begin opening and be fully open at
250   10 PSIG. Leaving the fuses in on fan 12 will prevent
head pressure from becoming excessive, since this fan will
start after the fully open setting of the damper operators
has been observed.

PART WINDING START (OPTIONAL)

Part winding 

start is available on all voltage units and

consists of a solid state time delay wired in series with the
contactor that energizes the second winding of each com-

pressor  motor. Its purpose is to limit current in-rush to the
compressors upon start-up. As each compressor starts, the
contactor for the first motor winding is energized instantly

while that for the second motor winding is delayed for 1

second.

Control checkout is best accomplished by observation as

each contactor is pulled in to see that the 1 second delay
occurs before the second contactor pulls in.

L I N E

 

  N E U T R A L

PART WINDING

COMPRESSOR CONTACTOR

(2nd MOTOR WINDING)

PAGE 40

Summary of Contents for SEASONCON ALP-037A

Page 1: ...SEASONCON PACKAGED AIR COOLED CONDENSING UNIT MODELS ALP 037A THRU 057A 067B THRU 159B GROUP mcQua PEarEx Inc 13600 Industrial Park Blvd P O Box 1551 Minneapolis Mn 55440 c...

Page 2: ......

Page 3: ...hazard Avoid contact with them HANDLING Care should be taken to avoid rough handling or shock due to dropping the unit Do not push or pull the unit from anything other than the base and block the pus...

Page 4: ......

Page 5: ......

Page 6: ...nt Risers A B are sized so that their combined cross sectional internal area will allow full load unit operation without excessive pressure drop see notes Table 4 Riser B is sized to provide adequate...

Page 7: ...S McQuay has available a Liquid Line Accessory Kit for each ALP unit size Components selected for these kits were selected on the basis of a total combined pressure drop of 7 PSI includes 100 ft of tu...

Page 8: ......

Page 9: ...2 1 l 8 74 74 I I 159B 1 90 90 FIELD WIRING Wiring should be done in accordance with all applicable codes and ordinances Warranty is voided if wiring is not in accordance with specifications An open f...

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ...seal caps Making sure control stop switch Sl is open off and pumpdown switches PSI and PS2 are on manual pumpdown throw the main power and control dis connect switches to on This will energize crankc...

Page 36: ...d compressor through the oil fill hole in the crankcase and to the Sundstrand compressor through the 3 8 inch process tube on the side of the compressor To add oil isolate the crankcase and pour or pu...

Page 37: ...ning the refrigerant piping by moving pump down switches PSI and PS2 to the manual pumpdown valve assembly position The coil can then be removed from the valve body by simply removing a nut or snap ri...

Page 38: ...s prepaid APPENDIX STANDARD CONTROLS NOTE PERFORM AN OPERATIONAL CHECK OF ALL UNIT SAFETY CONTROLS ONCE PER YEAR OIL PRESSURE SAFETY CONTROL The oil pressure safety control is a manually resettable de...

Page 39: ...orator pressure will rise The highest evaporator pressure reached before compressor re start is the cut in setting of the control FANTROL HEAD PRESSURE CONTROL FANTROL is a method of head pressure con...

Page 40: ...e to open or close the damper blades as required to maintain adequate condenser pressure The operators are factory set to begin opening the damper blades at 17Ozt 5 PSIG and to be fully open at 250 10...

Page 41: ...ould pull in instantly NOTE Line is only hot when the unit thermostat calls for compressor to run COMPRESSOR LOCKOUT OPTIONAL ALP 037A THRU 078B Compressor lockout consists of a solid state time delay...

Page 42: ...the pressure setting remove the cap on the bulb and turn the adjustment screw clock wise To lower the setting turn the screw counterclockwise Do not force the adjustment beyond the range it is designe...

Page 43: ...drier 3 Replace cartrIdge Low Suction 4 Clogged suction line or compressor suction 4 Clean strainers Pressure gas strainers 5 Expansion valve malfunctioning 5 Check and reset for proper superheat 6 Co...

Reviews: