Page 8 of 36 / IM 985-1
8 . Unitsareinternallytrapped .CopperorPVC
condensatelinescanbeused .Ameansof
disconnectionmustbefurnishedtofacilitatechassis
removal .
9 . Nopointofthedrainsystemmaybeabovethedrain
panofanyunit .
10. Automatic flow control devices must not be installed
prior to system cleaning and flushing.
11 .Ahighpointofthepipingsystemmustbevented .
12 .Checklocalcodeforanyrequirementforelectric
fittings.
Water Connections
Allpipingconnectionsshouldbemadeusinggood
plumbingpracticesandinaccordancewithanyandall
localcodesthatmayapply .
Note:
On left-hand piping units the water supply
connection is on the top. Right hand piping units the
water supply is at the bottom location.
Unit Piping Connection
Eachheatpumpissuppliedwithextendedcopper
tubing on the water-to-refrigerant coil and 5/8" (16mm)
O .D .tubing .Theconnectionsareforboththesupply
andreturnwaterconnections .SeeFigure5forleftand
righthandconnectionslocatons .
Shutoff/Balancing Valve Piping
Eachheatpumprequiresashutoffvalveonboththe
supplyandreturnlinesforeasyserviceabilityand
removalifitbecomesnecessary .
Wesuggestusingourcombinationshutoff/balancing
valves installed in the field between the contractor’s
pipingandtheheatpumpunit .Thevalveinstalledon
thereturnlineactsasabalancingvalvetoadjustthe
proper water flow. An automatic flow limiting device is
alsoavailableasafactoryinstalledoption .
Each shutoff/balancing valve has 1/2" FPT and 1/2"
FPTthreadedconnections .
Attach the field installed combination shut/off balancing
valvetothebuildingwatersupplyandreturnpiping .
Addthefemalepipeadapterconnectiontounitsupply
andreturncoilconnectionbysweatingtheminplace
usingsilversolder .
Using the specified hoses, screw the fixed end
into the shut-off/balancing valve. Remove the 1/2"
adapterfromtheotherendofthehose .Insertthe
adapter into the female fitting. Using two crescent
wrenches,onetoholdthepipeconnectionandthe
secondtotightentheadapter,inserttheswivelendof
thehoseontheadapterandtighten .Thiscompletesthe
hoseconnectiontostandardheatpumpequipment .
Figure 5. Supply and Return Connections Locations for Left- Hand and Right Hand Units (Flat Top and Slope Top)
Right-Hand Piping View
Left-Hand Piping View
On left-hand piping units the
water supply connection is on
the top. Right-hand piping units
the water supply is at the bottom
location.
IMPORTANT
Unit Size
J
K
L
M
P
Q
R
S
007-018
6⅞
"
5
1
/
5
"
6¾"
3½"
10¼"
1
3
/
5
"
5¼"
7½"
(175mm)
(132mm)
(172mm)
(90mm)
(260mm)
(41mm)
(134mm)
(192mm)
Dimensions (High Sill Units)