McQuay MHC Series Installation & Maintenance Data Download Page 3

IM 985-1 / Page 3 of 36

Pre-Installation

1 .­ To­prevent­damage,­do­not­operate­this­equipment­

for­supplementary­heating­and­cooling­during­the­
construction­period .­Doing­so­will­void­the­warranty .

2.  Inspect the carton for any specific tagging numbers 

indicated­by­the­factory­per­a­request­from­the­
installing­contractor .­At­this­time­the­voltage,­phase­
and­capacity­should­be­checked­against­the­plans .

3 .­ Check­the­unit­size­against­the­plans­to­verify­that­

the­unit­is­being­installed­in­the­correct­location .

4 .­ Before­installation,­check­the­available­dimensions­

where­the­unit­be­installed­versus­the­dimensions­of­
the­unit .

5 .­ Note­the­location­and­routing­of­water­piping,­

condensate­drain­piping,­and­electrical­wiring .­
The­locations­of­these­items­are­clearly­marked­on­
submittal­drawings .

6.  The installing contractor will find it beneficial 

to­confer­with­piping,­sheet­metal,­and­electrical­
foremen­before­installing­any­unit .

Note: Check the unit data plate for correct voltage 
with the plans before installing the equipment. Also, 
make sure all electrical ground connections are made 
in accordance with local code.

 

7 .­ The­contractor­shall­cover­the­units­to­protect­the­

machines during finishing of the building. This is 

critical while spraying fireproofing material on bar 

joists,­sandblasting,­spray­painting­and­plastering .­
Damage­to­the­unit­due­to­a­failure­to­protect­it­

during finishing of the building is not covered by the 

warranty .­

WARNING

The installer must determine and follow all applicable 
codes and regulations. This equipment presents hazards 
of electricity, rotating parts, sharp edges, heat and weight. 
Failure to read and follow these instructions can result in 
property damage, severe personal injury or death. This 
equipment must be installed by experienced, trained 
personnel only.

Receiving and Storage

Upon­receipt­of­the­equipment,­check­carton­for­visible­
damage .­Make­a­notation­on­the­shipper’s­delivery­
ticket­before­signing .­If­there­is­any­evidence­of­rough­
handling,­immediately­open­the­cartons­to­check­for­
concealed­damage .­If­any­damage­is­found,­notify­the­
carrier­within­48­hours­to­establish­your­claim­and­
request­their­inspection­and­a­report .­The­Warranty­
Claims­Department­should­then­be­contacted .

­
Do­not­stand­or­transport­the­machines­on­end .­For­
storing,­each­carton­is­marked­with­“up”­arrows .

­
In­the­event­that­elevator­transfer­makes­up-ended­
positioning­unavoidable,­do­not­operate­the­machine­
until­it­has­been­in­the­normal­upright­position­for­at­
least­24­hours .

­
Temporary­storage­at­the­job­site­must­be­indoor,­
completely­sheltered­from­rain,­snow,­etc .­High­or­low­
temperatures­naturally­associated­with­weather­patterns­
will­not­harm­the­units .­Excessively­high­temperatures,­
140°F­(60°C)­and­higher,­may­deteriorate­certain­plastic­
materials­and­cause­permanent­damage .

IMPORTANT

This product was carefully packed and thoroughly 
inspected before leaving the factory. Responsibility for its 
safe delivery was assumed by the carrier upon acceptance 
of the shipment. Claims for loss or damage sustained in 
transit must therefore be made upon the carrier as follows:

VISIBLE LOSS OR DAMAGE

Any external evidence of loss or damage must be noted 
on the freight bill or carrier’s receipt, and signed by the 
carrier’s agent. Failure to adequately describe such 
external evidence of loss or damage may result in the 
carrier’s refusal to honor a damage claim. The form 

required to file such a claim will be supplied by the carrier.

CONCEALED LOSS OR DAMAGE

Concealed loss or damage means loss or damage which 
does not become apparent until the product has been 
unpacked. The contents may be damaged in transit due 
to rough handling even though the carton may not show 
external damages. When the damage is discovered upon 
unpacking, make a written request for inspection by the 

carrier’s agent within fifteen (15) days of the delivery date 

and  file a claim with the carrier.

   

Unit Size 

007 

009 

012 

015 

 

018

  Fan Wheel - D x W (In.)    

4.33 x 27.24 

4.33 x 27.24 

4.33 x 27.24 

4.33 x 35.43    4.33 x 35.43

  Fan Motor Horsepower    

1/30 

1/30

 

1/30

 

1/18

 

 

1/18

 

Coil Face Area (Sq. Ft.)  

 

1.67 

1.67 

1.67 

2.22 

 

2.22

  Coil Rows 

 

 

 

3

  Refrigerant Charge (Oz.)   

18.2 

19.2 

22 

29.9 

 

32

 

Filter, (Qty.) Size (In.)

   

Low Sill 

 

(1) 23.75 x 8.75

 

                                 

(1) 31.75 x 8.75

   

 

High Sill 

 

(1) 29.25 x 9.75 

                      (1) 37.25 x 9.75

 

Water Connections, Female NPT (In.) 

5/8 O.D. 

5/8 O.D.

 

5/8 O.D. 

5/8 O.D. 

 

5/8 O.D.

  Condensate Connections, Female NPT (In.) 

3/4 I.D. 

3/4 I.D. 

3/4 I.D. 

3/4 I.D. 

 

3/4 I.D.

 

Weight, Operating (Lbs.)   

138 

144 

146 

166 

 

171

  Weight, Shipping (Lbs.)  

 

158 

164 

166 

196 

 

201

Table 1. Physical Data

Summary of Contents for MHC Series

Page 1: ...ole Water Source Heat Pumps R 410A Models MHC Standard Range MHW Geothermal Range Flat Top Slope Top Unit Sizes 007 018 Group WSHP Part Number 669544301 Date January 2010 IM 985 1 2010 McQuay Internat...

Page 2: ...ltages 13 Operating Limits 13 14 MicroTech III Unit Controller 14 25 I O Expansion Module 15 MicroTech III Controller with Lon Module 16 MicroTech III Controller with BACnet Module 17 MicroTech III Un...

Page 3: ...nd a report The Warranty Claims Department should then be contacted Do not stand or transport the machines on end For storing each carton is marked with up arrows In the event that elevator transfer m...

Page 4: ...nection end of the subbase and chassis Note Make sure electrical and piping connections are in the proper location within the subbase end piping compartment Unit Installation Recommended Installation...

Page 5: ...in the subbase and secure the subbase to the floor tightening the fasteners Do not over tighten fasteners and distort or warp the subbase plate IMPORTANT 11 Use a carpenters square and level to check...

Page 6: ...It is the responsibility of the installing contractor to provide the appropriate fasteners and anchors to ensure that the unit is secured properly WARNING Left End View Right End View Provided Mounti...

Page 7: ...s supplied with a clear vinyl condensate hose Figure 4 Typical 2 Pipe Reverse Return Configuration Piping 1 Connect units to supply and return piping in a two pipe reverse return configuration Figure...

Page 8: ...ing valves installed in the field between the contractor s piping and the heat pump unit The valve installed on the return line acts as a balancing valve to adjust the proper water flow An automatic f...

Page 9: ...f piping packages Consult your local sales rep for more information Left End Piping View Right End Piping Back View Left End Piping Back View Right End Piping View When installing the hoses on valve a...

Page 10: ...lear vinyl condensate hose internally trapped within the chassis The hose extends 3 89mm out of the chassis within the piping compartment to reach the floor or the back wall Field condensate piping mu...

Page 11: ...ontractor to check for leaks upon start up of the water system could result in property damage Return Runout Supply Runout Mains Flexible Hose Runouts Initially Connected Together 3 Shut off supplemen...

Page 12: ...knockout and remove it Install a strain relief and pass the wires through the strain relief into the junction box making the connection and reinstall the junction box cover Note Check the local code c...

Page 13: ...er Electrical Data General 1 Be sure the available power is the same voltage and phase as that shown on the unit serial plate Line and voltage wiring must be done in accordance with local codes or the...

Page 14: ...t low voltage terminal strip is set up so R G energizes the fan R Y1 energizes the compressor for cooling operation R W1 energizes the compressor and reversing valve for heating operation The reversin...

Page 15: ...eat Shorted to enable reheat JP3 and JP4 open for no supplemental heat JP3 Supplemental JP3 open JP4 shorted for JP4 Heat Type boilerless electric heat JP3 and JP4 shorted is an invalid setting JP5 an...

Page 16: ...vers the installation of a McQuay Console Water Source Heat Pump For installation and operation information on LonWorks Communication Module and other ancillary control components see IM 927 MicroTech...

Page 17: ...available on a communications network using BACnet objects and properties The network cable is a shielded twisted pair cable Network communications run at 76 8 Kbps DIP switches on the controller ena...

Page 18: ...r LED Output TB1 2 2 Fan Mode Heat Cool Auto Input TB1 3 3 Setpoint Adjust Input TB1 4 4 Room Temperature Sensor Tenant Override TB1 5 5 DC Signal Common Test 1 R 24 VAC Test 2 W2 Heat Stage 2 Input T...

Page 19: ...f 36 Figure 15 MicroTech III Unit Controller Terminal Locations Location of Configuration Jumpers on the MicroTech III Unit Controller Note A random start delay time between 180 and 240 seconds is gen...

Page 20: ...Page 20 of 36 IM 985 1 Figure 16 LonWorks Communication Module Placement on MicroTech III Unit Controller...

Page 21: ...atest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan UMT Unit Mounted Therm...

Page 22: ...n Speed Relay HP High Pressure Switch R2 Relay Electric Heat IOEXP I O Expansion Board Harness LED2 LED Annunciator Harness SLTS Suction Line Temp Sensor OVL Compressor Overload Protector RV Reversing...

Page 23: ...Drain Pan Ground FSR Fan Speed Relay PTB Power Terminal Block HP High Pressure Switch SLTS Suction Line Temp Sensor OVL Compressor Overload Protector RV Reversing Valve Solenoid T1 EG2UCP Terminal Str...

Page 24: ...n LED on a wall thermostat Table 10 shows in which function the fault output is on sending a signal to the LED Units must be checked for water leaks upon initial water system start up Water leaks may...

Page 25: ...ge Heat Cool Systems Single Stage Heat Pump Systems Fan Speed Control Large Display With Backlight Selectable Fahrenheit or Celsius SimpleSet Field Programming Status Indicator Light Relay Outputs min...

Page 26: ...tions C RH RC W Y B O G1 G2 S1 S2 For detailed installation operation and application refer to Operation Application Guide LIAF015 Non Programmable Electronic Thermostat P N 668811001 Non Programmable...

Page 27: ...ew The second part of the T9000 system is called a Remote Control Node or RCN An RCN interfaces with specific desired HVAC equipment and communicates with its thermostat using unlicensed 900 MHz radio...

Page 28: ...e Sensor Terminals Fan Control Slide Switch Mode Control Slide Switch Status LED Green 0 to 10 K ohm Potentiometer Tenant Override Momentary Push Button Switch 4 59 When the optional wall mounted room...

Page 29: ...s version of the board uses VAC relays and should not be used in combination with any other accessories or equipment that require VDC connections to the G W1 or Y1 terminals i e Boilerless System Kit...

Page 30: ...Assembly Manual Outside Damper Assembly Figure 24 Manual Outside Air Damper Assembly See IM 974 for detailed installation instructions Figure 25 Motorized Outside Air Damper Assembly See IM 974 for de...

Page 31: ...tures All McQuay water source heat pumps are designed for commercial use The units are designed for the cooling mode of operation and fail safe to cooling The reversing valve is energized for the heat...

Page 32: ...low Cooling High High High High Low Low High High Pressure High Air Flow Heating Low Low Low Low High Low Low Low Temp High Air Flow Cooling Low High Normal High Low Low Normal High Pressure High Wate...

Page 33: ...refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refrigerant then flows as a low...

Page 34: ...or lock rotor amp draw Check for defective compressor internal windings with ohm meter Check for proper air flow filter could be dirty Check for low refrigerant charge Check amp draw on blower assembl...

Page 35: ...s powered by the control board s power terminals No solid state devices Triacs may be used to operate the Microtech III unit controller inputs No outside power source may be used to operate the Microt...

Page 36: ...ive go to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured i...

Reviews: