309 B/C – 03/03 A – page
9/28
Heat Pump Unit
Note:
(1)
Nominal cooling capacity referred to 12/7 ° C in/out evaporator water temperature 35 °C air ambient temperature
(2)
Heating capacity referred to: 40/45°C in/out Hot water temp. & air ambient temperature. 7°C, 90% R.H.
M4AC080CR
M4AC100CR
Watt
21.700
25.800
kcal/hr
22.010
25.970
Watt
25.600
30.200
THICKNESS
mm
HEIGHT (H)
mm (in)
WIDTH (W)
mm (in)
DEPTH (D)
mm (in)
kg
350
360
dB(A)
62
64
EVAPORATOR
m
2
2,26
2,78
l/s
1.08/1.14
1.31/1.39
kPa
74/72
82/80
kPa
104
121
WATER LINE(HYDRAULIC KIT)
POWER SUPPLY
V/Ph/Hz
RUNNING CURRENT
Amp
1,1
1,1
WATER FLOW RATE ( C / H )
GPM U.S. (l/s)
17.17(1.08)/18.05(1.14)
20.70(1.31)/22.02(1.39)
INSTALLATION PIPE CONNECTION
mm (in)
42 (Rc 1-1/4)
42 (Rc 1-1/4)
HEAD (C / H)
m
26/25
23.5/22.5
CAPACITY / VOLUME
litres
8
8
CONDENSER COIL
WALL THICKNESS
mm (in)
OUTER DIAMETER
mm (in)
THICKNESS
mm (in)
2
2
14
14
m
2
(ft
2
)
2.5 (26.9)
2.5 (26.9)
CONDENSER FAN
2
2
mm (in)
600 (23.6)
600 (23.6)
V/Ph/Hz
220 / 1 / 50
220 / 1 / 50
Amp
0.9*2
0.9*2
Watt
120*2
120*2
Watt
200*2
200*2
8
8
cmm/cfm
100*2 / 3530*2
100*2 / 3530*2
COMPRESSOR
Scroll
Scroll
V/Ph/Hz
380 / 3 / 50
380 / 3 / 50
Amp
7.3*2
8.6*2
Amp
7.3*2
8.6*2
Watt
3,900*2
4,800*2
Watt
3,900*2
4,800*2
Amp
40
48
REFRIGERANT
kg
4.0*2
4.6*2
kcal/hr
18660
22180
FINISH
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
CASING
MATERIAL
TYPE
TOTAL
UNIT
DIMENSION
1260 (49.6)
1500 (59.1)
900 (35.4)
PLATE MATERIAL
HEAT EXCHANGE AREA
NOMINAL WATER FLOW (COOLING/HEATING)
Electro-galvanised Mild Steel
Polyester Power
1,0
Brazed Plate Heat Exchanger
Stainless Steel
NET WEIGHT
NOISE LEVEL
Horizontal Multistage End-Suction
Steel
BPHE PRESSURE DROP VS NOMINAL FLOW RATE (C/H)
UNIT PRESSURE DROP VS NOMINAL FLOW RATE
PUMP
TYPE
PIPING
EXPANSION
TANK
MATERIAL
380 / 3 / 50
Aluminium
0.127 (0.0005)
TYPE
TUBE
MATERIAL
Cross Finned Tubes
Seamless Copper
0.35 (0.014)
9.52 (3/8)
FIN
MATERIAL
ROWS
FINS PER INCH
FACE AREA
TYPE/DRIVE
QUANTITY
Propeller/Direct
BLADE MATERIAL
Aluminium
BLADE DIAMETER
POWER SUPPLY
RATED RUNNING CURRENT
RATED INPUT
RATED OUTPUT
MOTOR POLES
AIR VOLUME
RATED INPUT (HEATING)
MAXIMUM STARTING CURRENT
PROTECTION DEVICES
TYPE
POWER SUPPLY
RATED RUNNING CURRENT (COOLING)
RATED RUNNING CURRENT (HEATING)
TYPE
RATED INPUT (COOLING)
CONTROL
CHARGING MASS
STAGE OF CAPACITY CONTROL (%)
Overload Protection, Flow Switch & H/L Pressure Switch
0-50-100
HFC 407C
Capillary Tube