McQuay M4AC080C Installation And Operation Manual Download Page 25

309 B/C – 03/03 A – page

 

25/28

 

McQuay designers have given full consideration to make servicing convenient during unit development. After opening 
service panel, both servicing and maintenance can be easily carried out. 
   
Under normal environment, the only work needed is checking the return air way and cleaning the heat exchange surface 
regularly at month or season interval decided on operating condition. 
 
If the surrounding is very dirty or oily, for maintaining superior performance and sufficient capacity, please ask 
specialized personnel to do regular cleaning of heat exchanger. 

 
Maintenance 

 

For keeping consistent performance and durability with safe, effective and long-life operation, always conduct proper and 
regular maintenance to the unit. 
 
For long period of operation time, the heat exchanger will become dirty impairing its effectiveness and reducing the 
performance of the air conditioner. Consult your local dealer on the cleaning of the heat exchanger. 
 
No main maintenance or servicing needed for the internal water circuit except the water pump failure. It is advised that 
regular check on the strainer should be conducted and replace the water strainer if the strainer is dirty or clogged. 
 
Always check the water level in the system, for the target of protecting the moving components in the hydraulic kit from 
overheating, excessive wearing and water freeze. 

 

All the chilled water in the hydraulic system must be drained out completely during unit shutdown in winter, to avoid water 
piping damage due to freeze. 

 

Troubleshooting 

 

Symptoms 

Possible Causes 

Remedial Action 

No power supply.

 

Check power supply.

 

Fuses blown or automatic

 

Look for short circuit or

 

circuit breakdown open. 

grounded wires in motor 

  

windings. Replace fuses 

  

and reset circuit breakers 

  

when the fault has been 

  

corrected. Check tightness 

  

and soundness of all 

  

electrical connections. 

Unit is stopped because a

 

Determine the type of

 

safety has tripped. 

safety shut down and 

  

correct the default before 

  

the unit is restarted. 

Loose wires.

 

Check wire connections and

 

  

tighten terminal screws. 

1. Compressor does no t start 

·

 Compressor faulty.

 

Contact local dealer.

 

2. Fan does not work  

No power supply.

 

Check power supply.

 

  

Fan motor faulty.

 

Contact local dealer.

 

3. Air conditioner does work,  

Thermostat setting too high.

 

Reset thermostat

 

but 

insufficient cooling.

 

Condenser coil dirty.

 

Contact local dealer.

 

  

Obstacle blocking air inlet or

 

Remove the obstacle.

 

  

outlet of the unit. 

  

  

Insufficient refrigerant in the

 

Contact local dealer.

 

  

system. 

  

  

·

mproper water flow rate.

 

Contact local dealer.

 

  

Water in the system is

 

Contact local dealer.

 

  

contaminated. 

  

 

Summary of Contents for M4AC080C

Page 1: ...C Cooling capacity from 22 4 to 40 0 kW M4AC 080 150 CR Cooling capacity from 21 7 to 38 7 kW Heating capacity from 25 6 to 41 5 kW 50 Hz HFC 407 C refrigerant Product Installation and Operation Manu...

Page 2: ...t notice Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations and experienced with this type of equipment McQuay is not respon...

Page 3: ...of high efficiency comfort safety intelligence to maximum extent The unit can be flexibly coupled with multi fan coil units easily operated with artificial intelligence Additionally combined with indo...

Page 4: ...site Water inlet and outlet are provided on both sides of the machine such that piping can be connected on either side of the machine Rust resistant PP R composite water pipe with good insulation prop...

Page 5: ...and evacuated before accurately charged with HFC 407C to ensure optimum operating requirement To ensure flawless continuous operation each refrigerant circuit is equipped with a carefully sized capil...

Page 6: ...ed personnel Indoor LCD controller After switching on power the indoor controller will display system time indoor temperature and unit status During normal operation it will display the unit return wa...

Page 7: ...380 3 50 Amp 7 3 2 8 6 2 Watt 3 900 2 4 800 2 Amp 40 48 REFRIGERANT kg 3 5 2 3 3 2 19 260 22 960 PLATE MATERIAL FINISH MODEL NOMINAL COOLING CAPACITY CASING MATERIAL kcal hr Electro galvanised Mild S...

Page 8: ...5 2 Watt 5 300 2 6 240 2 Amp 55 62 REFRIGERANT kg 6 3 2 5 7 2 34 390 Electro galvanised Mild Steel FINISH Polyester Power MODEL NOMINAL COOLING CAPACITY CASING MATERIAL 1 kcal hr 28 720 TOTAL UNIT DI...

Page 9: ...Hz 380 3 50 380 3 50 Amp 7 3 2 8 6 2 Amp 7 3 2 8 6 2 Watt 3 900 2 4 800 2 Watt 3 900 2 4 800 2 Amp 40 48 REFRIGERANT kg 4 0 2 4 6 2 kcal hr 18660 22180 FINISH MODEL NOMINAL COOLING CAPACITY NOMINAL H...

Page 10: ...COMPRESSOR Scroll Scroll V Ph Hz 380 3 50 380 3 50 Amp 10 3 2 11 5 2 Amp 10 3 2 11 5 2 Watt 5 300 2 6 240 2 Watt 5 300 2 6 240 2 Amp 55 62 REFRIGERANT kg 7 5 2 6 8 2 Electro galvanised Mild Steel Poly...

Page 11: ...27 7 9 3 26 7 9 6 25 3 10 1 23 6 10 8 8 29 8 9 0 28 2 9 7 27 2 10 1 25 8 10 6 24 0 11 2 9 30 4 9 7 28 8 10 5 27 8 10 8 26 4 11 3 24 8 12 0 M4AC100C 10 31 2 10 5 29 7 11 3 28 8 12 1 27 2 12 1 25 6 12...

Page 12: ...8 7 26 8 9 5 25 8 9 8 24 5 10 3 22 8 11 0 8 28 8 9 2 27 2 9 9 26 3 10 3 24 9 10 8 23 2 11 5 9 29 4 9 9 27 9 10 7 26 9 11 1 25 5 11 6 23 9 12 2 M4AC100CR 10 30 2 10 7 28 7 11 5 27 8 12 3 26 3 12 4 24 8...

Page 13: ...5 7 7 28 0 8 5 29 9 9 0 30 8 9 6 31 9 9 9 45 25 9 7 8 27 4 8 7 29 2 9 6 30 2 10 1 31 3 10 6 50 25 3 8 6 26 8 9 4 28 7 10 0 29 6 10 5 30 7 11 0 M4AC100CR 55 24 1 9 1 25 6 9 9 27 9 10 5 28 5 11 0 29 9 1...

Page 14: ...Drop And Flow Rate Water Flow Rate Water Pressure Drop MODEL L s m h kPa Bar M4AC080C 1 08 3 9 74 0 74 M4AC100C 1 31 4 7 82 0 82 M4AC120C 1 67 6 0 76 0 76 M4AC150C 2 0 7 2 74 0 74 Cooling 1 08 3 9 74...

Page 15: ...Chilled Water Out Cable Port IN F B 100 Rc 1 1 4 Chilled Water In Rc 1 1 4 UNIT mm Model Dimension M4AC080C R M4AC100C R M4AC120C R M4AC150C R A 1500 1500 1800 1800 B 900 900 1150 1150 C 1260 1260 126...

Page 16: ...HERMAL OVERLOAD RELAY AMPS MAC80C MODEL 10 5A 11 2A 11 2A 10 5A OPEN JP SETTINGS LEAVI N G W A T E R T E M P S E N S O R R E T U R N W A T E R T E M P S E N S O R ALARM INDICATOR AC DC SUPPLY NOTES Fi...

Page 17: ...TES Field Wiring Factory Wired CAUTION The setting shown in the diagram is factory set Don t change the JP settings and the value of parameters including thermal overload relays D E F R O S T S E N S...

Page 18: ...OMPRESSOR DESCRIPTION PHASE PROTECTOR DESCRIPTION FUSE WATER PUMP FAN MOTOR CONTACTOR COMP LP SWITCH COMP HP SWITCH WATER FLOW SWITCH JP SETTINGS OPEN Don t change the JP settings and the value of If...

Page 19: ...ODEL 14 4A JP SETTINGS 14 4A 3 4A OPEN is the auxiliary electric heater contactor field supply part If want to activate two way valve interlock function let JP6 open Don t change the JP settings and t...

Page 20: ...so that air can be drawn in and discharge out efficiently Ai r I ntake Air Intake A i r I n t a k e Ai r D i schar ge Ai r di schar ge b Install the unit in such a way that the hot air discharge canno...

Page 21: ...ble foundation with level surface must be sufficiently durable against the unit weight U ni t U ni t S uppor t er D r ai n Di t ch f The location must not be susceptible to dust or oil to avoid conden...

Page 22: ...Backing Angle After deciding the mounting location remove the skid base by unfastening the bolts Mounting When mounting please use foundation bolts or expansion bolts to fasten the unit with foundati...

Page 23: ...n and choking of the system Don t use the water pump equipped in unit to clean piping If using the pump to clean is required you can fill clean water in system at water in side meanwhile make the pump...

Page 24: ...le Q ty 5 Electrical Connection Of Auxiliary Electric Heater If auxiliary electric heater or auxiliary gas heater installation is required please do installation after thoroughly reading corresponding...

Page 25: ...d Always check the water level in the system for the target of protecting the moving components in the hydraulic kit from overheating excessive wearing and water freeze All the chilled water in the hy...

Page 26: ...mp overload Contact with the dealer EA Compressor 1 overload Contact with the dealer EC Compressor 1 high pressure cutout Contact with the dealer ED Compressor 1 low pressure cutout Contact with the d...

Page 27: ...g 7 H eat i ng C ap Tube 11 W at er Pum p 3 Accum ul at or R ef r i ger ant Fl ow D i r ect i on W hen C ool i ng 1 C om pr essor 9 R ecei ver LEG E N D 2 Four W ay Val ve 6 C ool i ng C ap Tube 10 BP...

Page 28: ...il mcquay mcquayitalia com Q T Y ITEM NAME FAN FAN GUARD TOP PANEL FRONT PANEL SUPPORT LEFT RIGHT COIL GUARD LEFT COIL ASSY SEPERATE PANEL ASSY FRONT PANEL ASSY WATER IN PIPE ASSY ELECTRICAL BOX SUPPO...