McQuay Incremental MQT Series Installation And Maintenance Data Download Page 6

Page 6 / IM 354

Louver Installation

pull it back to the wall sleeve rear face so that the louver studs
pass through the holes in the wall sleeve flanges. Securely
tighten the louver in place using the washers and nuts provided.

Install the outdoor louver from inside the room. Hold the louver
with a wire loop or other similar means. Push the louver out
through the rear opening of the room cabinet/wall sleeve and

Heating/Cooling Chassis Installation

Chassis Inspection & Installation Preparation
Check the chassis for damage. Remove and discard the
condenser fan shipping bracket (see Figure 9). Spin the fan
wheels manually to confirm free rotation. Check the refriger-
ant tubing to determine that there are no kinks, and that it
does not rub against other parts. Report any shipping dam-
age to the carrier immediately.

Check the interior of the installed room cabinet/wall box.

Clean out any dirt or debris that may have accumulated,
particularly abrasive materials that could scratch the painted
surfaces.

Optional Condensate Connection
If it has been decided to use the condensate drain, you will
need the optional kit containing one flexible drain connector
tube, one drain tube assembly and two #8 mounting screws.

1. Install the flexible tube on the chassis drain (see Figure 10).

2. Remove the front access cover of the subbase (see Figure

11).

3. Remove the knockout in the bottom left side of the wall

sleeve and mount the drain tube assembly with two
screws (see Figure 11). The assembly may be installed at
various 90 degree positions to fit job requirements.

4. Make the connection to the field supplied drain previously

installed under the subbase installation instructions. The
outlet of the drain tube assembly is 

1

2

" nominal copper

tubing (

5

8

" O.D. actual). The easiest method of connection

would be with a short length of 

5

8

" I.D. flexible PVC tubing

having a wall thickness of at least 

1

8

" (3mm) to prevent

kinking or collapse, however, follow all local applicable
codes.

Heating/Cooling Chassis Installation
1. Slide the chassis into the room cabinet/wall sleeve until

firmly seated against the weather seals. Caution: Push
only on positions marked “Hand Holds” and/or sheet-
metal flanges. Caution: Do not push on the coil surface,
control box cover, or fan scroll (see Figure 13). Caution:
Make sure that tubing does not catch when inserting
chassis.

2. Plug the electrical cord into the receptacle. Excess cord

should be coiled neatly and stored in the conditioner.

3. If the optional condensate drain kit is used, install the

flexible tube between the chassis and wall sleeve conden-
sate drain by pressing the tube into the drain assembly
(see Figure 12). Caution: When removing the chassis,
remember first to lift the tube from the drain assembly.

4. Set the manual damper operator in open or closed posi-

tion as desired (see Figure 14).

5. Check the “Standby/Normal” switch located on the face

of the control box. For normal heat pump operation,
position the switch to “Normal.” Only the electric heater
will operate when switch is in “Standby’ position.

Residential and institutional cleaning compounds can
cause permanent damage to the packaged terminal unit.
To avoid damage to unit controls and heat transfer sur-
faces, do not spray cleaning compounds onto the dis-
charge grille, the return air opening or the unit controls.
Normal cleaning can be accomplished by wiping the unit
surface with a damp cloth. When using cleaning com-
pounds on carpets, floor or walls, turn the unit off to avoid
drawing potentially damaging vapors into the package
terminal unit.

Figure 12.

Figure 9.

Figure 11.

Figure 10.

Knockout

Summary of Contents for Incremental MQT Series

Page 1: ...uh cooling 09 Nominal 9 000 Btuh cooling 11 Nominal 11 000 Btuh cooling 14 Nominal 14 000 Btuh cooling Vintage Designation B Sizes 06 09 11 C Size 14 Unit Type A Air conditioner with electric heat B Air conditioner with hydronic heat C Heat pump with supplemental electric heat MQT 09 B C 5 B Heater Code A 2 0 kW electric heat B 3 2 kW electric heat C 4 8 kW electric heat G Steam heat W Hot water h...

Page 2: ...onal 3 8 10mm Louver Stamped Standard or 11 8 29mm Louver Extruded Optional 1 2 3 3 1 Note 4 minimum space requirement between underside of unit and floor for return air Subbase is optional on 208 and 230 volt units but standard on 265 volt A 3 4 19mm drip lip Optional condensate connection Figure 2 Conditioner wall mounted 93 4 248mm Min 4 102mm Min 2 x 4 51 x 102mm Junction Box All wiring should...

Page 3: ... provided in the basepan of the wall sleeve for this purpose Optional Subbase Whenever a subbase is used it must be installed prior to the room cabinet wall sleeve The subbase provided in four pieces is adjustable from 43 8 to 155 8 111 to 397mm in depth to accommodate various projections of the conditioner into the room The standard subbase height is 4 102mm with adjustable leveling bolts to 41 2...

Page 4: ...r building surface 3 Secure the louver frame to the wall through the sides and top of the sleeve Never secure the louver frame through the bottom Note The louver frame may also be secured from inside the room cabinet wall sleeve by screws driven through the sides and top of the louver frame sleeve Pre Installation Conditioner Preparation 1 Remove the outer carton of the room cabinet wall sleeve ch...

Page 5: ... wall opening by the depth of the louver to be installed see Figure 8 The center of gravity of the conditioner is 91 2 241mm from the rear face For wall mounted conditioners the center of gravity must be within the load bearing portion of the wall otherwise some method of support is required 3a Installations without a subbase Level or pitch the room cabinet wall sleeve a maximum of1 8 3mm down war...

Page 6: ...e assembly is 1 2 nominal copper tubing 5 8 O D actual The easiest method of connection would be with a short length of 5 8 I D flexible PVC tubing having a wall thickness of at least 1 8 3mm to prevent kinking or collapse however follow all local applicable codes Heating Cooling Chassis Installation 1 Slide the chassis into the room cabinet wall sleeve until firmly seated against the weather seal...

Page 7: ...losed exerting sufficient pressure on the top black border area to allow the latching buttons to snap into place usually with an audible click 6 Replace the two sheetmetal screws adjacent to the latch ing buttons in the front panel 7 Replace the filter assembly at the bottom of the front panel Initial start up of the Incremental conditioners by an experi enced technician is usually the responsibil...

Page 8: ...he original owner for one year Refrigerating circuits consist of the motor compressor assembly evapora tor coil condenser coil and interconnecting tubing Repairs under this warranty will be made at the Company s expense provided that the refrigerating circuit is delivered without shipping damage transportation prepaid to the factory or to a factory designated repair station at the Company s option...

Reviews: