McQuay Incremental MQT Series Installation And Maintenance Data Download Page 3

IM 354 / Page 3

b. Conditioner with Subbase — Where the optional

subbase is used, the rectangular knockout in the right
front bottom of the wall sleeve is removed to allow the
subbase junction box to be mounted directly beneath
the wall sleeve (see Figure 3).

2. 265 Volt Models — Permanently wired to the subbase

junction box receptacle. A short interconnecting cord is
furnished from the chassis to reach this receptacle to
preserve the ease of quick chassis changeout. The condi-
tioner is marked with the minimum circuit ampacity and
maximum fuse size. The subbase and receptacle are
standard factory supplied equipment on these models.

Incremental air conditioners can be installed in various ways.
This instruction is based on the use of an optional subbase,
an optional louver frame and an optional condensate drain.
The following is a recommended installation procedure:

Optional Condensate Drain
If it is used, provisions should be made in the stub-up area for
the condensate connection (see Figure 4). Since the MQT
Heat Pump has a reverse cycle heating feature, it generates
condensate during the heating season which may not be
completely removed by the normal condensate disposal
system. A condensate drain opening is therefore provided at
the left bottom front of the heating/cooling chassis; it is
shipped from the factory with a rubber plug inserted. An
optional condensate drain kit is available, and it is recom-
mended that it be used to connect the chassis to condensate
drain (by others). A knockout is provided in the basepan of
the wall sleeve for this purpose.

Optional Subbase
Whenever a subbase is used, it must be installed prior to the
room/cabinet wall sleeve.

The subbase, provided in four pieces, is adjustable from

4

3

8

" to 15

5

8

" (111 to 397mm) in depth to accommodate

various projections of the conditioner into the room. The
standard subbase height is 4" (102mm) with adjustable
leveling bolts to 4

1

2

" (114mm). In all cases, the subbase

provides a 5

1

2

" (140mm) toe space inset from the front edge

of the conditioner. Thus, for applications where the minimum
9

3

4

" (248mm) conditioner projection into the room is utilized,

only the 4

3

8

" (111mm) deep front section of the subbase is

required. The adjustable side extension pieces should be
discarded. The adjustable “L” shaped extension pieces are
used when the conditioner projection into the room is greater
that 9

3

4

" (248mm). The scoring at two-inch intervals on the

extension pieces can be broken at the desired depth. The
extensions are secured with two screws on each side to the
front section on the subbase. In all cases the back of the
subbase remains open and is butted against the wall (see
Figures 4 and 5).

Optional Subbase & Codensate Drain Installation

Figure 4.

Figure 3. Conditioner — with subbase

*Note: These are actual unit dimensions. The rough
opening through the wall should be at least 

1

4

" (6mm)

larger without louver frame, or at least 

5

8

" (16mm)

larger when louver frame is used.

Unit Outside

Dimensions

Optional Subbase

Optional Subbase Front

Access Cover

Opening for

Condensate Drain

Receptacle

Leveling Bolt

Screw

Receptacle

Cover

Centerline of Wall

Opening/Subbase

Screw

16

3

8

"

(416mm)*

Equipment

Ground Wire

Wall O

pening

Electrical

Stub-up Area

44

7

8

" (1140mm)*

Summary of Contents for Incremental MQT Series

Page 1: ...uh cooling 09 Nominal 9 000 Btuh cooling 11 Nominal 11 000 Btuh cooling 14 Nominal 14 000 Btuh cooling Vintage Designation B Sizes 06 09 11 C Size 14 Unit Type A Air conditioner with electric heat B Air conditioner with hydronic heat C Heat pump with supplemental electric heat MQT 09 B C 5 B Heater Code A 2 0 kW electric heat B 3 2 kW electric heat C 4 8 kW electric heat G Steam heat W Hot water h...

Page 2: ...onal 3 8 10mm Louver Stamped Standard or 11 8 29mm Louver Extruded Optional 1 2 3 3 1 Note 4 minimum space requirement between underside of unit and floor for return air Subbase is optional on 208 and 230 volt units but standard on 265 volt A 3 4 19mm drip lip Optional condensate connection Figure 2 Conditioner wall mounted 93 4 248mm Min 4 102mm Min 2 x 4 51 x 102mm Junction Box All wiring should...

Page 3: ... provided in the basepan of the wall sleeve for this purpose Optional Subbase Whenever a subbase is used it must be installed prior to the room cabinet wall sleeve The subbase provided in four pieces is adjustable from 43 8 to 155 8 111 to 397mm in depth to accommodate various projections of the conditioner into the room The standard subbase height is 4 102mm with adjustable leveling bolts to 41 2...

Page 4: ...r building surface 3 Secure the louver frame to the wall through the sides and top of the sleeve Never secure the louver frame through the bottom Note The louver frame may also be secured from inside the room cabinet wall sleeve by screws driven through the sides and top of the louver frame sleeve Pre Installation Conditioner Preparation 1 Remove the outer carton of the room cabinet wall sleeve ch...

Page 5: ... wall opening by the depth of the louver to be installed see Figure 8 The center of gravity of the conditioner is 91 2 241mm from the rear face For wall mounted conditioners the center of gravity must be within the load bearing portion of the wall otherwise some method of support is required 3a Installations without a subbase Level or pitch the room cabinet wall sleeve a maximum of1 8 3mm down war...

Page 6: ...e assembly is 1 2 nominal copper tubing 5 8 O D actual The easiest method of connection would be with a short length of 5 8 I D flexible PVC tubing having a wall thickness of at least 1 8 3mm to prevent kinking or collapse however follow all local applicable codes Heating Cooling Chassis Installation 1 Slide the chassis into the room cabinet wall sleeve until firmly seated against the weather seal...

Page 7: ...losed exerting sufficient pressure on the top black border area to allow the latching buttons to snap into place usually with an audible click 6 Replace the two sheetmetal screws adjacent to the latch ing buttons in the front panel 7 Replace the filter assembly at the bottom of the front panel Initial start up of the Incremental conditioners by an experi enced technician is usually the responsibil...

Page 8: ...he original owner for one year Refrigerating circuits consist of the motor compressor assembly evapora tor coil condenser coil and interconnecting tubing Repairs under this warranty will be made at the Company s expense provided that the refrigerating circuit is delivered without shipping damage transportation prepaid to the factory or to a factory designated repair station at the Company s option...

Reviews: