McQuay FDD Series Installation & Maintenance Data Download Page 23

IM 407 / Page 23 of 24

WARNING

!

To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical
codes, and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s).
Power supply to unit must be disconnected when making field connections. To avoid electrical shock, personal injury or death, be sure
to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.

Troubleshooting Water Source Heat Pump

Low Voltage, check power
supply voltage

Fuse may be blown, circuit
breaker is open

Wires may be loose or broken.
Replace or retighten wires

Unit Control, check thermostat
for correct wiring or bad thermostat

Neither Fan, nor
Compressor Runs

Unit

Compressor runs
in short cycle

Fan operates,
Compressor does not

Compressor attempts to start
but does not

Insufficient cooling or heating

Check compressor wiring for
defective wiring or loose
connection

Check thermostat for improper
location

Check for defective compressor
internal windings with ohm meter

Check for bad compressor
capacitor

Check for lock rotor amp draw

Check for proper air flow. Filter
could be dirty

Check blower assembly for
dirt or bad fan motor capacity

Check for low refrigerant charge

Check amp draw on blower
assembly

Check capacitor

Check wiring - loose or broken
and check for bad
connection

Hi pressure lockout -
A. Cool mode, check water flow
B. Heating mode, check air flow
C. Check reversing valve for
     proper valve position

Check compressor overload
make sure it is closed

Check compressor to ground,
or for internal short to ground.

Compressor winding may be
open. Check continuity with
ohm meter

Check wiring - loose or broken
and check for bad
connection

Check relays and contacts,
also capacitor and wiring

Check high pressure switch
and low temperature switch to
see if unit is cycling on the safety

Check to see if the reversing
valve is not hung up and is
operating correctly

Check condensate overflow
switch in cool mode of operation

Summary of Contents for FDD Series

Page 1: ...iagrams 8 14 Unit operation 15 LED Status and Fault Output Status 16 Thermostat Connections Mark IV AC units 17 Options for Mark IV AC units 19 22 Troubleshooting 23 Maintenance 24 2006 McQuay Interna...

Page 2: ...e of rough handling the cartons should be opened at once to check for concealed damage If any damage is found notify the carrier within 48 hours to establish your claim and request their inspection an...

Page 3: ...ance Opt Controls Main Access Panel Condensate Water Supply Water Return Heat Pump With Right Hand Return Air Arrangement Return Air Opt Controls Elec Entrance Main Access Panel Condensate Water Suppl...

Page 4: ...duct material the return air duct should be internally lined with acoustic insulation for sound attenuation Glass fiber duct board material is more absorb ing and may permit omission of the flexible c...

Page 5: ...system may also be made to work ac ceptably but proper water flow balancing is more diffi cult to achieve and maintain 2 The piping can be steel copper or PVC 3 Supply and return runouts are usually...

Page 6: ...for initial flush and blow down making sure city water fill valves are set to make up water at the same rate Check the pressure gauge at pump suction and manually adjust the makeup to hold the same po...

Page 7: ...chine should not Operating Limits Environment This equipment is designed for indoor installation only Sheltered locations such as attics garages etc generally will not provide sufficient protection ag...

Page 8: ...upplied relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitiv...

Page 9: ...relays in series with the inputs Figure 10 Unit sizes 019 through 048 208 230 265 volts single phase 060686606 Rev C Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Pr...

Page 10: ...switches are normally closed 5 Field supplied relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Figure 12 Unit sizes 02...

Page 11: ...d relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micr...

Page 12: ...24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Proper ground...

Page 13: ...o the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Proper...

Page 14: ...for 208V operation If 230V power supply is used transformer must be wired by disconnecting the power lead from the red transformer primary wire Place an insulation cap on the red transformer primary w...

Page 15: ...itch or low pressure switch on unit sizes 048 and 060 The unit does not have to be reset on a condensate overflow detection The Mark IV AC control board has a fault output signal to an LED on a wall t...

Page 16: ...rces may be used to operate Mark IV AC board inputs Note The fault output is energized when no faults exist The fault output is de energized during faults and when unit power is off Using Drive Using...

Page 17: ...with other wires Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal o...

Page 18: ...rk IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip Multiple Unit Control Panel TB3 TB2 TB1 TB4 R C W1 Y1 W2 Y2 G Thermostat Terminals This version of the board...

Page 19: ...nal is not being used as a pump restart signal to other equipment If the P terminalmustbeusedasapumprestartsignaltootherequipment then wire the auxiliary relay s yellow wire to Y1 white wire to W1 and...

Page 20: ...r tempera ture sensor on the water supply line and then connect the duct heater control contacts to the duct heater control circuit 9 66 245 mm 007 042 14 50 368 mm 048 060 6 5 165 mm 007 042 4 12 105...

Page 21: ...C P terminal will change state causing a contact closure between terminal 58 and 64 signaling the loop water control LWC panel to restart the loop pump if Off The pump restart relay kit is typically m...

Page 22: ...signals is required on a single WSHP the MicroTech 2000 Auxiliary Module Kit 107239001 must be used and these additional output control signals will be connected to the Auxiliary board 1 circuit unit...

Page 23: ...eating Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor...

Page 24: ...differences both heating and cooling is recommended A comparison of logged data with start up and other annual data is useful as an indica tor of general equipment condition 5 Periodic lockouts alway...

Reviews: