McQuay FDD Series Installation & Maintenance Data Download Page 15

IM 407 / Page 15 of 24

Unit Operation

Figure 28.

INDICATION

LEDS

FAULT

YELLOW

GREEN

RED

OUTPUT

Normal mode

Off

On

Off

Off

High pressure fault

Off

Off

Flash

On

    * Low temperature fault

Flash

Off

Off

On

Condensate overflow

On

Dim

Off

On

Brownout

Off

Flash

Off

On

Load shed

Off

Off

On

Off

Unoccupied mode

On

On

Off

Off

Unit shutdown

Off

Flash

Off

On

General

Each unit has a printed circuit board control system. The low
voltage output from the low voltage terminal strip on the
control board is always 24 volts DC (direct current). Termi-
nals R and C on the low voltage terminal strip supply 24 volts
AC power. The unit has been designed for operation with a
24 volt mercury bulb type wall thermostat or a microelec-
tronic wall thermostat selected by the manufacturer. Do not
operate the unit with any other type of wall thermostat.

Two types of units are available: electromechanical con-

trol units or Mark IV/AC control units. Both have 24 volt DC
circuits on the output of the low voltage terminal strip. Each
requires its own unique automatic changeover thermostat.

Mark IV/AC control units

The Mark IV/AC circuit board is an optional control system
with built-in features such as random start, compressor time
delay, night setback, load shed, shutdown, condensate
overflow protection, defrost cycle, brownout, and LED/fault
outputs. Figure 28 shows the LED and fault output se-
quences.

The 24 volt low voltage terminal strip is set up so R-G

energizes the fan, R-Y1 energizes the compressor for cool-
ing operation, R-W1 energizes the compressor and reversing
valve for heating operation. The reversing valve is set up to
be energized in the heating mode. The circuit board has a fan
interlock circuit to energize the fan whenever the compressor
is on if the thermostat logic fails to do so.

The Mark IV/AC control board has a lockout circuit to stop

compressor operation if any one of its safety switches opens
(high pressure switch and low pressure switch on unit sizes
048 and 060). If the low temperature switch opens, the unit
will go into the cooling mode for 60 seconds to defrost any
slush in the water-to-refrigerant heat exchanger. After 60
seconds the compressor is locked out. If the condensate
sensor detects a filled drain pan, the compressor operation
will be suspended only in the cooling mode. The unit is reset
by opening and closing the disconnect switch on the main
power supply to the unit in the event the unit compressor
operation has been suspended due to low temperature
(freezestat) switch, high pressure switch, or low pressure
switch on unit sizes 048 and 060. The unit does not have to
be reset on a condensate overflow detection.

The Mark IV/AC control board has a fault output signal to

an LED on a wall thermostat. Figure 28 shows for which
functions the fault output is “on” (sending a signal to the
LED).

The Mark IV/AC control board has built-in night setback

operation. A “grounded” signal to the “U” terminal on the low
voltage terminal strip puts the unit into the unoccupied mode
for night setback operation. The fan shuts off and the unit is
put under control from the night setback terminal on the
thermostat, W2; day heating and cooling operation is locked
out. R-W2 energizes the compressor and reversing valve for

heating operation. Night setback operation can be overrid-
den for two hours by toggling the fan switch (intermittently
closing the R to O terminals) on the Deluxe Auto Changeover
thermostat. Day thermostat setpoints the control the heating
and cooling operation. The Mark IV/AC control system is also
set up for load shed and shutdown operation on receipt of a
“grounded” signal to the “L” and “E” terminals, respectively,
on the low voltage terminal strip. See Figure 29.

The P and C terminals of the Mark IV/AC board are used

for pump restart. These terminals pass a voltage signal
whenever the unit compressor is turned on. This signal is
detected by a pump restart relay board providing an N.O. or
N.C. set of contacts for heat pump loop circulation pump
control. When used with the Loop Water Controller, the relay
operation accommodates turning off circulation pump con-
trol. When used with the Loop Water Controller, the relay
operation accommodates turning off circulation pumps dur-
ing unoccupied periods with a safety override dependent on,
at minimum, one WSHP's need. The P and C terminals may
be “daisy-chained” between 200 units. See page 19.

To activate the unoccupied mode for units on the same  clock schedule, a single wire can be
“daisy-chained” between units and simply grounded through the time clock contacts. The
same system can also be done to activate the load shed and emergency shutdown modes
by running additional wires between units to ground.

Unit #1

Unit #2

Time Clock

Ground

Figure 29.

To
Additional
Units

Unit #3

* In heating mode only.

14-Position Terminal Strip

Pin

Designation

Description

1

C

Transformer ground (Ovac)

2

R

Transformer supply (24vac)

3

V

-DC power connection

4

P

Pump request output

5

A

 Alarm fault output

6

U

Unoccupied input

7

L

Load shed input

8

E

Remote shutdown input

9

F

+DC power connection

10

Y1

Occupied cooling mode input

11

W1

Occupied heating mode input

12

G

Fan only input

13

W2

Unoccupied heating mode input

14

O

Tenant override input

Mark IV/AC Sequence of
Operation

Summary of Contents for FDD Series

Page 1: ...iagrams 8 14 Unit operation 15 LED Status and Fault Output Status 16 Thermostat Connections Mark IV AC units 17 Options for Mark IV AC units 19 22 Troubleshooting 23 Maintenance 24 2006 McQuay Interna...

Page 2: ...e of rough handling the cartons should be opened at once to check for concealed damage If any damage is found notify the carrier within 48 hours to establish your claim and request their inspection an...

Page 3: ...ance Opt Controls Main Access Panel Condensate Water Supply Water Return Heat Pump With Right Hand Return Air Arrangement Return Air Opt Controls Elec Entrance Main Access Panel Condensate Water Suppl...

Page 4: ...duct material the return air duct should be internally lined with acoustic insulation for sound attenuation Glass fiber duct board material is more absorb ing and may permit omission of the flexible c...

Page 5: ...system may also be made to work ac ceptably but proper water flow balancing is more diffi cult to achieve and maintain 2 The piping can be steel copper or PVC 3 Supply and return runouts are usually...

Page 6: ...for initial flush and blow down making sure city water fill valves are set to make up water at the same rate Check the pressure gauge at pump suction and manually adjust the makeup to hold the same po...

Page 7: ...chine should not Operating Limits Environment This equipment is designed for indoor installation only Sheltered locations such as attics garages etc generally will not provide sufficient protection ag...

Page 8: ...upplied relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitiv...

Page 9: ...relays in series with the inputs Figure 10 Unit sizes 019 through 048 208 230 265 volts single phase 060686606 Rev C Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Pr...

Page 10: ...switches are normally closed 5 Field supplied relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Figure 12 Unit sizes 02...

Page 11: ...d relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micr...

Page 12: ...24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Proper ground...

Page 13: ...o the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Proper...

Page 14: ...for 208V operation If 230V power supply is used transformer must be wired by disconnecting the power lead from the red transformer primary wire Place an insulation cap on the red transformer primary w...

Page 15: ...itch or low pressure switch on unit sizes 048 and 060 The unit does not have to be reset on a condensate overflow detection The Mark IV AC control board has a fault output signal to an LED on a wall t...

Page 16: ...rces may be used to operate Mark IV AC board inputs Note The fault output is energized when no faults exist The fault output is de energized during faults and when unit power is off Using Drive Using...

Page 17: ...with other wires Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal o...

Page 18: ...rk IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip Multiple Unit Control Panel TB3 TB2 TB1 TB4 R C W1 Y1 W2 Y2 G Thermostat Terminals This version of the board...

Page 19: ...nal is not being used as a pump restart signal to other equipment If the P terminalmustbeusedasapumprestartsignaltootherequipment then wire the auxiliary relay s yellow wire to Y1 white wire to W1 and...

Page 20: ...r tempera ture sensor on the water supply line and then connect the duct heater control contacts to the duct heater control circuit 9 66 245 mm 007 042 14 50 368 mm 048 060 6 5 165 mm 007 042 4 12 105...

Page 21: ...C P terminal will change state causing a contact closure between terminal 58 and 64 signaling the loop water control LWC panel to restart the loop pump if Off The pump restart relay kit is typically m...

Page 22: ...signals is required on a single WSHP the MicroTech 2000 Auxiliary Module Kit 107239001 must be used and these additional output control signals will be connected to the Auxiliary board 1 circuit unit...

Page 23: ...eating Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor...

Page 24: ...differences both heating and cooling is recommended A comparison of logged data with start up and other annual data is useful as an indica tor of general equipment condition 5 Periodic lockouts alway...

Reviews: