McQuay Enfinity CCH series Installation & Maintenance Data Download Page 7

IM 742 / Page 7

Start-up

1 .    Open all valves to full open position and turn on power 

to the conditioner .-

2 .    Set  thermostat  for  “Fan  Only”  operation  by  selecting 

“Off” at the system switch and “On” at the fan switch . If 

“Auto” fan operation is selected, the fan will cycle with 

the compressor . Check for proper air delivery .

3 .    For those units that have two-speed motors, reconnect 

for low speed operation if necessary .

4 .    Set thermostat to “Cool .” If the thermostat is an automat-

ic changeover type, simply set the cooling temperature 

to  the  coolest  position .  On  manual  changeover  types 

additionally select “Cool” at the system switch .

 

  Again,  many  conditioners  have  time  delays  which 

protect  the  compressor(s)  against  short  cycling . After 

a few minutes of operation, check the discharge grilles 

for  cool  air  delivery .  Measure  the  temperature  differ-

ence between entering and leaving water . It should be 

approximately 1

1

2

 times greater than the heating mode 

temperature  difference .  For  example,  if  the  cooling 

temperature difference is 15°F (8°C), the heating tem-

perature difference should have been 10°F (5°C) .

    Without automatic flow control valves, target a cooling 

temperature  difference  of  10°F  to  14°F  (5°C  to  8°C) . 

Adjust  the  combination  shutoff/balancing  valve  in  the 

return line to a water flow rate which will result in the 

10˚F to 14°F (5°C to 8°C) difference.

5 .    Set thermostat to “Heat .” If the thermostat is the auto-

matic changeover type, set system switch to the “Auto” 

position  and  depress  the  heat  setting  to  the  warmest 

selection . Some conditioners have built-in time delays 

which prevent the compressor from immediately start-

ing . With most control schemes, the fan will start imme-

diately . After  a  few  minutes  of  compressor  operation, 

check for warm air delivery at discharge grille . If this is 

a “cold building” start-up, leave unit running until return 

air to the unit is at least 65°F (18°C) .

 

  Measure the temperature difference between enter-

ing and leaving air and entering and leaving water . With 

entering water of 60°F to 80°F (16°C to 27°C), leaving 

water  should  be  6°F  to  12°F  (3 .3°C  to  6 .6°C)  cooler, 

and  the  air  temperature  rise  through  the  machine 

should  not  exceed  35°F  (19°C) .  If  the  air  tempera-

ture exceeds 35°F (19°C), then the water flow rate is  

inadequate .

6 .  Check the elevation and cleanliness of the condensate 

line . If the air is too dry for sufficient dehumidification, 

slowly pour enough water into the condensate pan to 

ensure proper drainage .

7 .    If the conditioner does not operate, check the following 

points:

 

a .  Is supply voltage to the machine compatible?

 

b .  Is thermostat type appropriate?

 

c .  Is thermostat wiring correct?

8 .    If the conditioner operates but stops after a brief period:

 

a .  Is  there  proper  airflow? Check  for  dirty  filter,  incor-

rect fan rotation (3-phase fan motors only), or incor-

rect ductwork .

 

b .  Is  there  proper  water  flow  rate  within  temperature 

limits? Check water balancing; backflush unit if dirt-

clogged .

9 .    Check for vibrating refrigerant piping, fan wheels, etc .
 10 .  Do not lubricate the fan motor during the first year of 

operation as it is prelubricated at the factory .

 11 . 

Field supplied relays installed on the input terminals W1, W2, 

Y1, Y2 or G may introduce electrical noise. Never install relay 

coils in series with the inputs.

5 .  Refill the system with clean water . Test the water using 

litmus paper for acidity, and treat as required to leave the 

water slightly alkaline (pH 7 .5 to 8 .5) . The specified per-

centage of antifreeze may also be added at this time . Use 

commercial grade antifreeze designed for HVAC systems 

only . Do not use automotive grade antifreeze .

    Once  the  system  has  been  filled  with  clean  water 

and  antifreeze  (if  used),  precautions  should  be  taken 

to  protect  the  system  from  dirty  water  conditions .  Dirty 

water  will  result  in  system  wide  degradation  of  perfor-

mance and solids may clog valves, strainers, flow regu-

lators, etc . Additionally, the heat exchanger may become 

clogged which reduces compressor service life or causes 

premature failure . 

6 .  Set the loop water controller  heat add setpoint to 70°F 

(21°C)  and  the  heat  rejection  setpoint  to  85°F  (29°C) . 

Supply  power  to  all  motors  and  start  the  circulating 

pumps . After  full  flow  has  been  established  through  all 

components  including  the  heat  rejector  (regardless  of 

season) and air vented and loop temperatures stabilized, 

each of the conditioners will be ready for check, test and 

start-up, air balancing, and water balancing .

Summary of Contents for Enfinity CCH series

Page 1: ...Electrical Data 5 Piping 5 Cleaning Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 17 Options for Mark IV AC Units 18 21 Fi...

Page 2: ...eck the available ceiling height versus the height of the unit 6 Note the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly m...

Page 3: ...res 1A and 1B 6 When attaching the hanger rods to the unit a double nut is recommended since vibration could loosen a single nut The installer is responsible for providing the hex nuts when installing...

Page 4: ...etween the conditioner discharge and the distribution diffusers Return air ducts can be brought in through a low side wall filter grille and then up through the stud pieces to a ceiling plenum or thro...

Page 5: ...rmance and minimum sound requirements Fan sound levels and performance can be affected by external static pressure changed Disconnect and cap the red lead wire and inter change it with the orange lead...

Page 6: ...ure 7 Figure 7 Supply return runouts connected together 2 Fill the system at the city water makeup connection with all air vents open After filling close all air vents The contractor should start main...

Page 7: ...erature rise through the machine should not exceed 35 F 19 C If the air tempera ture exceeds 35 F 19 C then the water flow rate is inadequate 6 Check the elevation and cleanliness of the condensate li...

Page 8: ...di tion It is assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature temperature and or humidity and equipment performance reliability and service l...

Page 9: ...ervice personnel should be observed or dam age to controller may result 5 Terminal block on Mark IV AC board provides 24 VAC at terminals R and C All other outputs are 24 VDC 6 Field supplied relays i...

Page 10: ...is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Page 11: ...ce an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally closed Notes 1 A 208 230V unit is factory wired for 208V operation If 230V power supply is...

Page 12: ...ad ShedOff Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On Page 12 IM 742 Unit Operation The Remote Reset feature provides the means to remotely reset automatic lockouts ge...

Page 13: ...ts IM 742 Page 13 MicroTech 2000 WSHP Unit Controller MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied...

Page 14: ...operation Fan operation can be customized in software to run continuously during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling...

Page 15: ...operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm auto matically resets when the attained tem...

Page 16: ...G Thermostat Terminals C R 7 Day Programmable Electronic Thermostat P N 107095901 Thermostat Connection Diagrams Mark IV AC Units Unit Sizes 007 070 Non Programmable Electronic Thermostat P N 66805420...

Page 17: ...t Grn Red Wall Sensor Locate the sensor on a wall where exposure to unrestrict ed air circulation represents the average temperature of the space A common mistake is to mount the sensor too close to t...

Page 18: ...e Mark IV AC board when using standard off the self relays The auxiliary relay can be used to provide fault signals unit operation signals or to provide a means for remote equipment to control the Mar...

Page 19: ...Control Panel O W2 G W1 Y1 F E L U A P V R C G W Y C L WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W1 Y1 F E L U A P V R C 1 2 3 Auxiliary...

Page 20: ...Override Pot1 Boilerless System Board 43 Ohm 4 pin Plug Water Temperature Sensor Signal to remote duct heater control circuit F L W1 V Mark IV Board Terminals 9 66 245 mm 007 042 14 50 368 mm 048 060...

Page 21: ...ter Controller Terminals Daisy chain to other Mark IV AC board P and C terminals 64 58 65 WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit 1 Pump Restart Relay 7 6 5 4 3 2 1 O W2 G W1 Y1 F E L...

Page 22: ...e WSHP chassis 24VAC Pilot Duty Relay by others Terminals Located on Microtech 2000 Auxiliary Board J6 24VAC Pilot Duty Relay by others Use contacts as needed for option Terminals Located on Microtech...

Page 23: ...cessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s thermostat inputs and contro...

Page 24: ...ing Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor cap...

Page 25: ...and atmosphere pressure it can become com bustible under pressure when mixed with air NOTE R 410A should not be mixed with air under pressure for leak testing Pressure mixtures of dry nitrogen and R...

Page 26: ...ng system to the air to refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refriger...

Page 27: ...een through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned and f...

Page 28: ...to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an I...

Reviews: