McQuay Enfinity CCH series Installation & Maintenance Data Download Page 4

Page 4 / IM 742

Air Discharge Conversion

Unit sizes 007 thru 070 can be shipped as straight discharge 

air or end discharge air arrangement . In the event that the 

unit needs to be converted from straight discharge to end 

discharge:
1 .  Remove top panel .
2 .  Remove the access panel to the fan motor . Remove the 

piece of insulation at the bottom on the side of the bottom 

panel .

3 .  Remove the fan discharge panel, rotate it 180 degrees, 

and move it to the other side . In other words, with straight 

air discharge the housing is bottom horizontal and with 

an end discharge the housing is top horizontal .

4 .  Remove  the  three  bolts  holding  the  fan  motor  on  and 

rotate it so that the motor oilers are in the up position .

5 .  Install  insulation  base  panel  below  new  access  panel 

location .

6 .  Reinstall the top panel .
7 .  Reinstall the piece of insulation and the access panel .

Ductwork & Attenuation

Discharge ductwork is normally used with these condition-

ers . Return air ductwork may also be required .

  All  ductwork  should  conform  to  industry  standards 

of  good  practice  as  described  in  the  ASHRAE Systems 

Guide .

  The  discharge  duct  system  will  normally  consist  of  a 

flexible  connector  at  the  unit,  a  transition  piece  to  the  full 

duct size, a short run of duct, an elbow without vanes, and 

a  trunk  duct  teeing  into  a  branch  duct  with  discharge  dif-

fusers as shown in Figure 2 . The transition piece must not 

have  angles  totaling  more  than  30°  or  severe  loss  of  air 

performance can result . Do not connect the full duct size to 

the unit without using a transition piece down to the size of 

the  discharge  collar  on  the  unit .  With  metal  duct  material, 

the sides only of the elbow and entire branch duct should 

be internally lined with acoustic fibrous insulation for sound 

attenuation . Glass fiber duct board material is more absorb-

ing and may permit omission of the canvas connector .

  The ductwork should be laid out so that there is no line of 

sight between the conditioner discharge and the distribution 

diffusers .

  Return  air  ducts  can  be  brought  in  through  a  low  side 

wall  filter-grille  and  then  up  through  the  stud  pieces  to 

a  ceiling  plenum  or  through  air  ceiling  filter-grilles .  The 

ceiling  filter-grille  must  not  be  placed  directly  under  the  

conditioner .

  Return  air  ductwork  can  be  connected  to  the  standard 

filter rack . See Figure 3 (side filter removal shown) . The filter 

rack can be installed for bottom filter removal or side filter 

removal by locating the brackets . For side filter removal the 

brackets should be located on the bottom, left side, and top . 

For bottom filter removal the brackets should be mounted on 

the left side top and right side with the spring clips support-

ing the filter .

  Do not use sheet metal screws directly into the unit cabi-

net  for  connection  of  supply  or  return  air  ductwork,  espe-

cially return air ductwork which can hit the drain pan or the 

air coil .

Figure 2. Suggested duct layout

Figure 3. Filter rack/return air duct collar

2x2 Ft .

Diffuser

(Example

Only)

Branch Duct

Internally Lined

With Acoustic

Fibrous

Insulation

Trunk Duct

Square Elbow

Canvas

Collar

Heat

Pump

Transformation

Piece

Discharge Collar

On Heat Pump

Both Sides Internally Lined With 

Acoustic Fibrous Glass Insulation

Suggested Duct Layout For

Multiple Diffuser Application

Standard 1" (25mm)

Optional  2"  (51  mm)  Rack  also 

available.

Ventilation may require outside air . The temperature of the 

ventilation air must be controlled so that mixture of outside 

air and return air entering the conditioner does not exceed 

conditioner  application  limits .  It  is  also  typical  to  close  off 

the ventilation air system during unoccupied periods (night 

setback) .

Ventilation Air

  The ventilation air system is generally a separate building 

subsystem with distribution ductwork . Simple introduction of 

the outside air into each return air plenum chamber reason-

ably close to the conditioner air inlet is recommended . Do 

not duct outside air directly to the conditioner inlet . Provide 

sufficient distance for thorough mixing of outside and return 

air . See Operating Limits on page 8 .

Summary of Contents for Enfinity CCH series

Page 1: ...Electrical Data 5 Piping 5 Cleaning Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 17 Options for Mark IV AC Units 18 21 Fi...

Page 2: ...eck the available ceiling height versus the height of the unit 6 Note the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly m...

Page 3: ...res 1A and 1B 6 When attaching the hanger rods to the unit a double nut is recommended since vibration could loosen a single nut The installer is responsible for providing the hex nuts when installing...

Page 4: ...etween the conditioner discharge and the distribution diffusers Return air ducts can be brought in through a low side wall filter grille and then up through the stud pieces to a ceiling plenum or thro...

Page 5: ...rmance and minimum sound requirements Fan sound levels and performance can be affected by external static pressure changed Disconnect and cap the red lead wire and inter change it with the orange lead...

Page 6: ...ure 7 Figure 7 Supply return runouts connected together 2 Fill the system at the city water makeup connection with all air vents open After filling close all air vents The contractor should start main...

Page 7: ...erature rise through the machine should not exceed 35 F 19 C If the air tempera ture exceeds 35 F 19 C then the water flow rate is inadequate 6 Check the elevation and cleanliness of the condensate li...

Page 8: ...di tion It is assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature temperature and or humidity and equipment performance reliability and service l...

Page 9: ...ervice personnel should be observed or dam age to controller may result 5 Terminal block on Mark IV AC board provides 24 VAC at terminals R and C All other outputs are 24 VDC 6 Field supplied relays i...

Page 10: ...is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Page 11: ...ce an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally closed Notes 1 A 208 230V unit is factory wired for 208V operation If 230V power supply is...

Page 12: ...ad ShedOff Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On Page 12 IM 742 Unit Operation The Remote Reset feature provides the means to remotely reset automatic lockouts ge...

Page 13: ...ts IM 742 Page 13 MicroTech 2000 WSHP Unit Controller MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied...

Page 14: ...operation Fan operation can be customized in software to run continuously during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling...

Page 15: ...operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm auto matically resets when the attained tem...

Page 16: ...G Thermostat Terminals C R 7 Day Programmable Electronic Thermostat P N 107095901 Thermostat Connection Diagrams Mark IV AC Units Unit Sizes 007 070 Non Programmable Electronic Thermostat P N 66805420...

Page 17: ...t Grn Red Wall Sensor Locate the sensor on a wall where exposure to unrestrict ed air circulation represents the average temperature of the space A common mistake is to mount the sensor too close to t...

Page 18: ...e Mark IV AC board when using standard off the self relays The auxiliary relay can be used to provide fault signals unit operation signals or to provide a means for remote equipment to control the Mar...

Page 19: ...Control Panel O W2 G W1 Y1 F E L U A P V R C G W Y C L WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W1 Y1 F E L U A P V R C 1 2 3 Auxiliary...

Page 20: ...Override Pot1 Boilerless System Board 43 Ohm 4 pin Plug Water Temperature Sensor Signal to remote duct heater control circuit F L W1 V Mark IV Board Terminals 9 66 245 mm 007 042 14 50 368 mm 048 060...

Page 21: ...ter Controller Terminals Daisy chain to other Mark IV AC board P and C terminals 64 58 65 WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit 1 Pump Restart Relay 7 6 5 4 3 2 1 O W2 G W1 Y1 F E L...

Page 22: ...e WSHP chassis 24VAC Pilot Duty Relay by others Terminals Located on Microtech 2000 Auxiliary Board J6 24VAC Pilot Duty Relay by others Use contacts as needed for option Terminals Located on Microtech...

Page 23: ...cessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s thermostat inputs and contro...

Page 24: ...ing Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor cap...

Page 25: ...and atmosphere pressure it can become com bustible under pressure when mixed with air NOTE R 410A should not be mixed with air under pressure for leak testing Pressure mixtures of dry nitrogen and R...

Page 26: ...ng system to the air to refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refriger...

Page 27: ...een through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned and f...

Page 28: ...to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an I...

Reviews: