McQuay AGR 070A Product Manual Download Page 43

Product Manual AGR-3

AGR 070A through 100A

43

The vertical length can be sized smaller to accommodate the lower circuit tons at reduced load.

Minimum compressor capacity can be increased by eliminating the lowest step of compressor capacity.

Hot gas bypass can be introduced at the distributor to the evaporator, increasing the volume of gas
available in the suction line to entrain the oil.

An oil separator may be installed in the discharge line.

With reciprocating compressor units only, and only as a last resort, double suction risers can be utilized.
Since a double suction riser works by providing an oil trap to assist the return of some oil, with
refrigerant, up the smaller diameter line,

a)

 

the trap must be as small as possible,

b)

 

there must not be multiple traps, and

c)

 

whenever double risers are used in a suction line, a suction accumulator with a controlled oil
return must be installed in the line ahead of the compressor.

In horizontal refrigerant gas lines, oil return to compressors is aided by sizing lines at a velocity above
the minimum recommended and pitching the lines in the direction of refrigerant flow.

SIZING A DOUBLE RISER

At maximum circuit tons, the line size should be selected from the table based upon the recommended
maximum line loss.

With the minimum tons known, a smaller line size should be selected from ASHRAE Chapter 2, Table
13 or 14 capable of entraining oil at the reduced tons.  The smaller sized line should be the one installed
to always be active.

The net internal area of this smaller sized line (see Table 13 or 14) should be deducted from the area of
the size selected in paragraph 1) immediately above.  The remainder represents the area of the other
riser.  From Table 13 or 14, select a line size with an area equal, or close, to the calculated net area.
The combination of these two risers will provide the required performance at full circuit tons.  The line
selected for the minimum load should always be active; and both lines should enter the overhead
horizontal line in a manner to prevent spillage of oil back down the other riser.

LONG VERTICAL RISER INSTALLATION

Where job conditions require refrigerant gas lifts of more than 25 feet, McQuay recommends the
installation of a short trap half-way up the riser or at not more than 20 feet intervals.  These traps are
required to capture and hold small quantities of oil during off cycles.

Liquid Lines

Liquid lines are generally sized for 1 to 2 degrees F line losses or their equivalent in pressure drop.
Actual selection can vary based upon the pressure drop expected from refrigerant specialties such as
solenoids, refrigerant driers, valves, etc. piping lifts or risers and the amount of condenser sub-cooling
expected.

The principal concern in sizing and routing liquid lines is assurance that liquid is present in the line at
start-up of the compressor, and that liquid, not vapor, is available at the inlet to the expansion valve
during system operation.

Liquid may not be available in a liquid line at start-up if:

1.

 

The solenoid valve is located adjacent to the condenser or condensing unit; remote from the
expansion valve.

2.

 

An excessive length of liquid line is located in a heated ambient and the application permits
migration of the refrigerant to a cold air cooled condenser.

3.

 

Liquid refrigerant is permitted to gravitate from the liquid line to the condenser because of the
relative location of components.

Summary of Contents for AGR 070A

Page 1: ...Product Manual PM AGR 3 Air Cooled Reciprocating Chiller AGR 070AS 100AS Packaged Chiller AGR 070AM 100AM Remote Evaporator 70 to 100 Tons 245 to 350 kW R 22 R 134a 60 Hertz...

Page 2: ...Product Specification AGR AM 53 Our Facility is ISO Certified McQuay is a registered trademark of McQuay International 2001 McQuay International Illustrations and data cover the McQuay International p...

Page 3: ...compressor staging Copeland Discus compressors Exceeds ASHRAE Standard 90 1 for efficiency Reliability Rugged proven compressor design Factory installed operating and equipment protection controls Cod...

Page 4: ...ts statically and dynamically balanced for smooth operation Connecting rods are lightweight aluminum with integral bearing surfaces on the crankshaft and piston ends Pistons are close grain cast iron...

Page 5: ...up at ambient air temperatures to 20 F 29 C An ambient air thermostat controls the heater cable The fitted and glued in place insulation has a K factor of 0 28 at 75 F 23 C The refrigerant tube side...

Page 6: ...tem cycles condenser fans based on discharge pressure and outdoor temperature and is suited for operation to 40 F 4 4 C The optional SpeedTrol control uses both fan cycling and fan speed control on th...

Page 7: ...al Configuration MONITOR ADJUST TIME SCHEDULE PASSWORD ENTER Compressor 1 Compressor 2 Stage 3 Stage 4 Solenoid 1 Frzstat 1Alm Frzstat 2Alm MinLowPres 1 MinLowPres 2 Occupied Flow Failure OA Lockout C...

Page 8: ...alarm signal and automatically switching to the alarm menu on the display Pre alarms are self clearing when the fault condition is no longer present Critical shutdown alarms such as high condenser pr...

Page 9: ...input of 77 1 and a unit EER of 9 6 2 If any elements are unknown use the following equation water only to calculate them 24 GPM T delta tons 3 Determine the evaporator pressure drop Using Figure 9 en...

Page 10: ...kW input of 77 5 and a COP of 2 84 2 Determine the evaporator pressure drop Using Figure 9 enter at 11 L s and follow to the AGR 070AS line intersect Read horizontally to obtain an evaporator pressure...

Page 11: ...glycol adjustment factors Ratings are based on a 0 0001 0 0176 fouling factor in the evaporator at sea level operation For other fouling factors derates for different delta Ts or altitude correction f...

Page 12: ...from Table 8 is 0 984 3 The corrected capacity of the AGR is 67 5 tons x 0 986 altitude x 0 984 piping 65 5 tons This satisfies the 64 ton requirement 4 Correct the compressor power required 77 1 kW x...

Page 13: ...capacity and reduce the unit s performance For performance at elevations other than sea level refer to Table 3 Maximum allowable altitude is 6 000 feet 1830 meters Evaporator Temperature Drop Factors...

Page 14: ...986 610 m 12 6 7 0 992 1 011 0 985 1 009 0 962 1 002 0 919 0 988 14 6 8 0 997 1 014 0 990 1 012 0 967 1 005 0 924 0 991 16 8 9 1 000 1 016 0 993 1 014 0 970 1 007 0 927 0 993 6 3 3 0 966 1 016 0 959...

Page 15: ...0AM 2 1 8 2 1 8 2 5 8 2 5 8 2 5 8 2 5 8 075AM 2 1 8 2 1 8 2 5 8 2 5 8 2 5 8 2 5 8 080AM 2 1 8 2 5 8 2 1 8 2 5 8 2 5 8 2 5 8 2 5 8 2 5 8 085AM 2 5 8 2 5 8 2 5 8 2 5 8 2 5 8 3 1 8 090AM 2 5 8 2 5 8 2 5...

Page 16: ...02 6 8 8 77 4 110 0 7 7 48 0 100 6 84 5 13 1 95 5 94 7 11 6 90 5 99 3 10 1 85 3 104 3 9 0 80 2 112 0 8 3 50 0 103 8 85 8 13 3 98 6 96 0 11 8 93 3 102 0 10 3 88 1 106 1 9 2 82 9 114 0 8 1 40 0 90 3 80...

Page 17: ...9 102 3 2 62 277 8 108 9 2 35 9 0 48 2 F 351 3 86 7 3 76 335 2 95 3 3 36 319 3 99 6 2 97 302 8 104 0 2 68 286 6 110 7 2 47 10 0 50 0 F 361 4 87 8 3 81 344 9 96 6 3 41 328 1 102 0 3 02 311 7 105 7 2 73...

Page 18: ...00 77 9 97 2 9 6 75 00 58 4 59 1 11 9 50 00 38 9 34 13 7 080AS 25 00 19 4 16 1 14 5 13 0 100 00 84 7 104 9 9 7 75 00 63 5 63 5 12 50 00 42 3 35 2 14 4 085AS 25 00 21 1 15 4 16 4 13 6 100 00 86 7 106 9...

Page 19: ...ting body produces compression waves and as the waves are emitted from the vibrating body molecules are ultimately compressed These values are transmitted through gas liquid solid anything which is el...

Page 20: ...lection from the source For example a unit sitting on a flat roof or ground with no other reflective surfaces or attenuation due to grass snow etc between source and receiver Q 2 Figure 6 Q Definition...

Page 21: ...aces the direction where the lowest sound level is required The control box end provides an excellent acoustic barrier to the compressor sound as it covers one full end of the unit The sound pressure...

Page 22: ...80 17 67 4 3 105 6 62 080AS AM 11 7 187 11 80 29 6 312 19 66 5 1 117 7 37 085AS AM 13 5 203 12 81 33 3 338 21 35 5 9 127 8 00 090AS AM 10 5 208 13 12 26 3 347 21 87 4 5 130 8 20 095AS AM 12 0 226 14 2...

Page 23: ...50 150 208 384 6 3 0 2 2 00 500 230 373 3 500 1 3 00 500 380 240 3 250 1 2 50 300 460 187 3 3 0 1 2 00 250 080AS 080AM 575 151 3 2 0 1 1 50 200 208 411 6 4 0 2 2 00 500 230 408 6 4 0 2 2 00 500 380 25...

Page 24: ...460 63 82 3 6 6 13 8 315 510 195 330 080AS 080AM 575 48 68 3 0 6 11 0 245 405 152 262 208 162 162 7 8 6 30 5 N A N A 654 654 230 162 162 7 2 6 27 6 N A N A 654 654 380 103 103 4 1 6 20 0 740 740 N A...

Page 25: ...250 4 350 MCM 460 335 4 400 MCM 250 4 350 MCM 080AS 080AM 575 335 4 400 MCM 250 4 350 MCM 208 840 2 qty 1 0 600 MCM 600 2 qty 250 500 MCM 230 840 2 qty 1 0 600 MCM 600 2 qty 250 500 MCM 380 335 4 400...

Page 26: ...Handbook 8 Must be electrically grounded according to national and local electrical codes 9 MCA may vary slightly due to fan motor options such as SpeedTrol Voltage Limitations Within 10 percent of u...

Page 27: ...Product Manual AGR 3 AGR 070A through 100A 27 Figure 10 Typical Field Wiring with MicroTech Controller See Note 3 for Electrical Data Single Point Power on page 26...

Page 28: ...28 AGR 070A through 100A Product Manual AGR 3 Figure 11 Typical Field Wiring Diagram with UNT Controller See note 3 for Electrical Data Single Point Power on page 26...

Page 29: ...0 25 50 63 75 84 100 83 100 85 100 88 100 CONDENSERS HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING Coil Face Area sq ft 58 58 87 87 87 87 87 87 Coil Face Area m2 5 4 5 4 8 1 8 1 8 1 8 1 8...

Page 30: ...25 50 63 75 88 100 89 100 88 100 CONDENSERS HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING Coil Face Area sq ft 87 87 87 87 87 87 Coil Face Area m2 8 1 8 1 8 1 8 1 8 1 8 1 Finned Height x...

Page 31: ...d Length In 100x 83 5 100x 83 5 100x125 3 100x125 3 100x125 3 100x125 3 100x125 3 100x125 3 Finned Height x Finned Length mm 2032 x 2121 2032 x 2121 2540 x 3183 2540 x 3183 2540 x 3183 2540 x 3183 254...

Page 32: ...inned Length In 100x125 3 100x125 3 100x125 3 100x125 3 100x125 3 100x125 3 Finned Height x Finned Length mm 2540 x 3183 2540 x 3183 2540 x 3183 2540 x 3183 2540 x 3183 2540 x 3183 Fins Per Inch x Row...

Page 33: ...Dimensions AGR 070AS Weights Dimensions Center of Gravity inch mm Operating Shipping AGR Model Number A B C D E F X Y Z lb kg lb kg Additional Weight with Copper Fin Coils lb kg 070AS 96 2 2444 91 7 2...

Page 34: ...5 080AS 96 2 2444 99 2 2520 45 2 1148 4 4 112 17 5 444 60 4 1534 41 5 1054 36 9 937 5740 2605 5595 2540 1245 565 085AS 96 2 2444 99 2 2520 45 2 1148 4 4 112 17 5 444 60 4 1534 40 8 1036 36 2 919 5920...

Page 35: ...mm inch mm AGR MODEL NUMBER A C D E F G H 070AM 96 2 1444 49 34 1253 20 88 597 23 52 597 9 34 237 20 88 597 25 52 648 CENTER OF GRAVITY UNIT WEIGHTS ADD L FOR SUCTION LIQUID inch mm lb kgs COPPER FIN...

Page 36: ...0 1245 23 9 608 27 8 707 100AM 96 2 2444 86 0 2184 23 9 608 27 8 707 49 0 1245 23 9 608 27 8 707 CENTER OF GRAVITY UNIT WEIGHTS inch mm lb kgs AGR MODEL NUMBER X Y Z OPERATING SHIPPING ADD L FOR COPPE...

Page 37: ...0 1372 11 0 278 5 0 127 7 0 178 2 1 8 54 1 3 8 35 CDE DIMENSIONAL DATA MODEL inch mm NUMBER A B D E F G CDE 1204 1 53 5 1359 17 5 445 8 8 224 17 5 445 12 1 307 2 3 58 CDE 1255 1 71 5 1816 17 5 445 8...

Page 38: ...low debris to accumulate near the unit where it could be drawn into the condenser coil Keep condenser coils and fan discharge free of snow or other obstructions to permit adequate airflow for proper u...

Page 39: ...em before unit start up to ensure adequate flow through the evaporator Install pressure gauges in the inlet and outlet water lines to the evaporator Measure pressure drop through the evaporator and co...

Page 40: ...ures LFT For applications where the LFT is less than 35 F only full load compressor operation is allowed Motor cooling can become a problem due to reduced refrigerant flow If compressor part load oper...

Page 41: ...zes the evaporator heater cable for protection against freeze up Unless the evaporator is drained in the winter the disconnect to the evaporator heater must not be open Extended Shutdown This unit is...

Page 42: ...ding the trap at the coil determine the minimum tons for the circuit Add b and c above to obtain the total equivalent feet Use ASHRAE Table 3 for R22 or Table 4 for R134a Suction line selections are b...

Page 43: ...lected in paragraph 1 immediately above The remainder represents the area of the other riser From Table 13 or 14 select a line size with an area equal or close to the calculated net area The combinati...

Page 44: ...ss Thus a 10 foot rise represents 5 pounds per square inch loss in refrigerant pressure or the equivalent of 1 6 F subcooling with R 22 Total line losses will include values for line friction equivale...

Page 45: ...Shown Equivalents Are Acceptable Unit Model Refrigerant Circuit Nom R 22 mbh Filter Drier Solenoid Valve Sight Glass Expansion Valve AGR 070AM 1 2 460 C 487 E25S270 SA 195 Y 979 AGR 075AM 1 2 480 C 4...

Page 46: ...ed high return temperature unloader thermostat senses high return water temperatures at startup and unloads the refrigerant circuit to avoid unit shutdown due to compressor motor overload Field locati...

Page 47: ...es in normal or ice mode Alarm Bell Field installed and wired to the control panel to provide remote indication of unit alarm condition Unit Protective Base Guards Optional factory installed vinyl coa...

Page 48: ...and elevation view drawings required clearances and location of all field connections 2 Summary of all auxiliary utility requirements such as electricity water compressed air etc Summary shall indica...

Page 49: ...ckaged chillers in the quantity specified Each chiller shall consist of reciprocating semi hermetic compressors multi circuit direct expansion evaporator air cooled condenser section control system an...

Page 50: ...with 3 4 inch 19mm closed cell polymer insulation with a minimum K factor of 0 28 at 75 F 23 C and be heated with an electric heater to provide freeze protection to 20 F 29 C ambient temperature The...

Page 51: ...nclude phase voltage volts ratio and solid state compressor motor protection The controller shall be equipped with a Zone Terminal option that provides an onboard LCD display of unit operating paramet...

Page 52: ...ed by the contractor for remote failure indication Factory installed circuit breaker to provide unit short circuit protection Phase loss with under over voltage protection and with LED indication of t...

Page 53: ...and elevation view drawings required clearances and location of all field connections 2 Summary of all auxiliary utility requirements such as electricity water compressed air etc Summary shall indicat...

Page 54: ...ory run tested air cooled reciprocating compressor condensing units remote shell and tube heat exchanger interconnecting refrigerant piping control system and all components necessary for controlled u...

Page 55: ...heated with an electric heater to provide freeze protection to 20 F 29 C ambient temperature The refrigerant side working pressure shall be at least 225 psig 1552 kPa The water side working pressure s...

Page 56: ...and evaporator freeze protection Motor protection shall include phase voltage volts ratio and solid state compressor motor protection The controller shall be equipped with a Zone Terminal option that...

Page 57: ...ith thru the door handle Factory installed circuit breaker to provide unit short circuit protection Phase loss with under over voltage protection and with LED indication of the fault type 115 volt con...

Page 58: ...58 AGR 070A through 100A Product Manual AGR 3...

Page 59: ...Product Manual AGR 3 AGR 070A through 100A 59...

Page 60: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...

Reviews: