4
ACZ 010A through 039A
IOMM ACZ1
Figure 1, Suggested Pushing Arrangement
Figure 2, Suggested Lifting Arrangement
Location
Unit Placement
ACZ units are for outdoor applications and can be mounted on a roof or at ground level. Set units on
a solid and level foundation. For roof-mounted applications, install the unit on a steel channel or I-
beam frame to support the unit above the roof. For ground level applications, install the unit on a
substantial base that will not settle. A one-piece concrete slab with footings extended below the frost
line is recommended. Be sure the foundation is level (within 1/2” [13 mm] over its length and width).
The foundation must support the operating weights listed in the Physical Data Tables on pages 15 and
16.
Since its operation is affected by wind, the unit should be located so that its length is parallel with the
prevailing wind. If this is not practical, field fabricated wind deflectors may be required.
Service Access
Each end of the unit must be accessible after installation for periodic service. Compressors, filter-
driers, and liquid line solenoid valve are accessible from the end of the unit. Motor protector controls
are on the compressor. Most operational, equipment protection, and starting controls are located in
the unit control box.
The fan deck with the condenser fans and motors can be removed from the top of the unit.
Blocking required
across full width