Table 7, ACZ 010A – 039A Field Wiring Data, Single Point Power
Wiring to
Standard Power Block Terminal
Wiring to
Optional Disconnect Switch
ACZ
UNIT
SIZE
Volts
HZ.
Maximum
Terminal Amps
Connector Wire Range
(Copper Wire Only)
Disconnect
Size
Connector Wire
Range
(Copper Wire Only)
208
175
14 GA – 2/0
100
8 GA – 2/0
230
175
14 GA – 2/0
100
8 GA – 2/0
460
175
14 GA – 2/0
45
14 GA – 4 GA
010A
575
60
175
14 GA – 2/0
63
14 GA – 1 GA
208
175
14 GA – 2/0
100
8 GA – 2/0
230
175
14 GA – 2/0
100
8 GA – 2/0
460
175
14 GA – 2/0
45
14 GA – 4 GA
013A
575
60
175
14 GA – 2/0
63
14 GA – 1 GA
208
175
14 GA – 2/0
100
8 GA – 2/0
230
175
14 GA – 2/0
100
8 GA – 2/0
460
175
14 GA – 2/0
45
14 GA – 4 GA
016A
575
60
175
14 GA – 2/0
63
14 GA – 1 GA
208
175
14 GA – 2/0
175
6GA – 300 kcmil
230
175
14 GA – 2/0
175
6GA – 300 kcmil
460
175
14 GA – 2/0
45
14 GA – 4 GA
020A
575
60
175
14 GA – 2/0
63
14 GA – 1 GA
208
175
14 GA – 2/0
200
6GA – 300 kcmil
230
175
14 GA – 2/0
200
6GA – 300 kcmil
460
175
14 GA – 2/0
100
8 GA – 2/0
025E
575
60
175
14 GA – 2/0
160
8 GA – 1/0
208
175
14 GA – 2/0
200
6GA – 300 kcmil
230
175
14 GA – 2/0
200
6GA – 300 kcmil
460
175
14 GA – 2/0
100
8 GA – 2/0
028A
575
60
175
14 GA – 2/0
160
8 GA – 1/0
208
175
14 GA – 2/0
200
6GA – 300 kcmil
230
175
14 GA – 2/0
200
6GA – 300 kcmil
460
175
14 GA – 2/0
100
8 GA – 2/0
033E
575
60
175
14 GA – 2/0
160
8 GA – 1/0
208
335
6 GA – 400 kcmil
200
6GA – 300 kcmil
230
335
6 GA – 400 kcmil
200
6GA – 300 kcmil
460
175
14 GA – 2/0
175
6GA – 300 kcmil
039A
575
60
175
14 GA – 2/0
175
6GA – 300 kcmil