1-8
Fan Coil Unit
5CKWS20CR
5CKWS20CR
Water Source Heat Pump Unit
5WSS16AR
5WSS20AR
Power Supply
V/Ph/Hz
230 / 1 /50
Voltage Range
V
220 ~ 240
Nominal Power Input (Cooling)
W
1011
1414
Nominal Power Input (Heating)
W
1090
1763
Nominal Current (Cooling)
A
4.5
6.3
Nominal Current (Heating)
A
5.0
8.0
Capacitor (440 VAC)
µf
2.0 µF 440 VAC
•
All wires must be firmly connected.
•
All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
•
The connecting wires between the fan coil unit and the water source heat pump unit must be clamped on the wire clamps
as shown in the figure.
•
The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.
Water Outlet Sensor
5CKWS-CR
Terminal Block
5WSS-AR
Terminal Block
N
N
L
COMP
4WV
A
!
N
COMP
4WV
A
Power Supply Cable
L
N
E
}
220~240V / 1Ph / 50Hz
5CKWS 10 / 15 / 20CR VS 5WSS 07 / 10 / 15 / 16 / 20AR
The electrical power must be provided with
protection devices (circuit breaker or fuse) with
double pole separation system (phase + neutral)
with minimum contact gap of 3mm.
!
Model (5CKWS-CR)
10/15
20
Voltage Range
220 ~ 240V /1Ph /50Hz +
!
Power Supply Cable Size*
mm
2
1.5
2.5
Number of Wire
3
3
Interconnection Cable Size*
mm
2
1.5
2.5
Number of Wire
5
5
Recommended Fuse
A
15
20
IMPORTANT
:
*
The figures shown in the table are for information purpose only. They should be checked and selected to
comply with the local/national codes of regulations. This is also subjected to the type of installation and
conductors used.
Summary of Contents for 5CKWS 10CR
Page 2: ......
Page 66: ...6 2 i ii 2 3 3 T 6 7 7 R410 9 9 10 11 11 11 12...
Page 67: ...6 3 5CKWS CR B B 5WSS AR O 10 3 0 0 5 0 5 0 5 1 0 3 0 4 350...
Page 69: ...6 5 4 O B P B B B B B B...
Page 74: ...6 10 LED 4 1 3 4 1 3 1 1 3 1 3 2 1 a 3 4 1 3 5 1 3 opo a oc o o a a a po ep e a a...
Page 75: ...6 11 1 40 2 3 1 40 2 2 2 C C C DB 15 20 27 15 19 24 32 20 12 45 30 13 C WB STD STD...
Page 76: ...6 12 3 4 1 3 2 3 4 5 6 7...
Page 77: ......
Page 80: ......
Page 82: ...ii s U _ cN UJ s VM d d U V w WM U l u w WH K D U U U tO M...
Page 95: ......