background image

25

A P P E N D I X  A

Guidelines for Locating Smoke Detectors

Experience has shown that all hostile fires in family living units generate smoke to a
greater or lesser extent. Experiments using typical fires in family living units indicate
that detectable quantities of smoke precede detectable levels of heat in most cases. In
existing homes, NFPA Standard 72 requires that a smoke detector be installed outside
each sleeping area and on each additional story of the family unit.
The following information is for general guidance only and it is recommended that
NFPA Standard 72 (National Fire Protection Association, One Batterymarch Park,
Quincy MA 02269

) be consulted and that the smoke detector manufacturer’s literature

be used for detailed installation instructions.
It is recommended that additional smoke detectors beyond those required be installed
for increased protection. The added areas include: basement, bedrooms, dining rooms,
furnace room, utility room and hallways not protected by the required detectors.

Figure 1: A smoke detector should be located
between the sleeping area and the rest of the
family unit.

Figure 3:  A smoke detector should be located on
each story of the living unit.

Figure 2:  In the family living units with more than
one sleeping area, a smoke detector should be
located to protect each sleeping area.

NOTE

: The Smoke Detector is designed

to use Eveready Energizer E91 Alkaline
Batteries. Do not use other brands of
batteries with the Smoke Detector. Using
brands other than the Eveready Energizer
will void UL approval, and may affect the
system’s operation.

Figure 4:  Smoke Detector mounting - “Dead” Air
Space. The smoke from a fire generally rises to
the ceiling, spreads out across the ceiling sur-
face and begins to bank down from the ceiling.
The corner where the ceiling and wall meet is an
air space into which the smoke may have diffi-
culty penetrating. In most fires, this “dead” air
space measures about 4 in. (0.1m) along the
ceiling from the corner and about 4 in. (0.1m)
down the wall as shown in Figure 4. Detectors
should not be placed in the dead” air space.

Family Room

Bedroom

Living
Room

Dining

Room

Kitchen

Bedroom

Bedroom

NEVER

HERE

Acceptable

here

Top of detector

acceptable here

12"

(0.3m)

Max.

4"

(0.1m)

Max.

4"

(0.1m)

Ceiling

Wall

NOTE: Measurements shown are to

the closest edge of the detector.

Bedroom

Bedroom

Basement

Living
Room

Dining

Room

Bedroom

Bedroom

Bedroom

Living Room

Kitchen

Summary of Contents for PC4164-RS

Page 1: ...onic Serial Numbers ESN for more information on enrolling older 5 digit and newer 6 digit devices 1 1 Before You Begin This manual describes how to install program and maintain the PC4164 RS on a PC40...

Page 2: ...e Sections 7 and 8 For help with troubleshooting see Section 9 Record the zone or slot and serial numbers of all wireless devices and other programming in the Programming Worksheets section at the end...

Page 3: ...wire runs thicker gauge wire must be used 1 4 Wireless Devices Please refer to the Installation Instruction sheets of the following devices for more information The PC4164 RS v2 0 can receive signals...

Page 4: ...you have done placement tests with all the wireless devices see sections 4 1 and 4 2 Find a place that is Dry Central to the proposed placement of all wireless devices As high as possible Far from sou...

Page 5: ...ed Combus to the PC4010 PC4020 Main Control Panel PC4164 RS 2 4 Connecting the PC4164 RS The PC4164 RS is connected to the control panel via the Combus CAUTION Remove all power from the panel while co...

Page 6: ...t Follow these steps to enroll your PC4164 RS module 1 At a PC4010 4020 system LCD keypad enter 8 Installer s code to go to the Installer s Programming section 2 Enter Ref 0200 to go to the Enroll Mod...

Page 7: ...ices test each one in its intended mounting location to make sure that it can communicate properly with the PC4164 RS Test the device 2 3 times See Section 4 1 for more information 1 At a system LCD k...

Page 8: ...it only has a 5 digit number enter a 0 and then the 5 digit number 4 The display will show Enroll Device WKEY XX where XX the Wkey slot to which the WLS909 is assigned 01 to 16 5 Record the serial nu...

Page 9: ...ou want to assign to that button and press The following functions may be programmed 00 Null Key 07 Arm Interior 01 Stay Arm 08 15 7 Command Outputs 1 8 02 Away Arm 16 Fire Alarm 03 No Entry Arm 17 Au...

Page 10: ...enter it now If it only has a 5 digit number enter a 0 and then the 5 digit number 4 The display will show Select 01 Partition 1 Scroll to the partition the keypad will be enrolled on Press to select...

Page 11: ...r of the function you want to select or scroll to the function you want to assign to that button and press The following functions may be programmed 00 Null Key 05 System Test 01 Stay Arm 06 Quick Exi...

Page 12: ...nded mounting location 2 At a system LCD keypad enter 8 Installer s code 3 Enter Ref 001303 to go to the Device Test section 4 Enter 00 to have test results sounded on the keypad buzzers only Enter 01...

Page 13: ...above To ensure that the PC4164 RS is receiving transmissions from these devices conduct the following tests WLS908 Activate the Panic alarm at several different points in the installation WLS909 Use...

Page 14: ...using the module placement test or the walk test You must assign panic pendant zones to one or more partitions before you can test the Panic Pendants Follow these steps to test Panic Pendants 1 Begin...

Page 15: ...ter Ref 001302 to go to the Replace Device section The LCD keypad will display Serial and either Zone XXX Wkey XX or HHK XX 3 Use the keys to scroll to the device to be deleted then press The LCD keyp...

Page 16: ...0 is empty the next device enrolled will be placed in zone number 020 If you enroll a device of the same class as the one deleted See Replacing Devices above it will be placed in the old device s slot...

Page 17: ...zone will restore communication with that zone and restore the Zone Supervisory Fault The Device Fail timer will also be reset WLS908 Panic Pendant The panic pendant does not transmit a supervisory si...

Page 18: ...des will only be reported once per armed period The Low Battery Restore transmission is not delayed The default transmission delay is 7 days To change the transmission delay 1 At a LCD keypad enter 8...

Page 19: ...ess device transmissions The panel will transmit the General System Trouble reporting code The default setting for this option is OFF To enable warning of this trouble condition 1 At a LCD keypad ente...

Page 20: ...led Verify that the device is in range of the PC4164 RS Try testing the device in the same room as the receiver Confirm that the PC4164 RS is properly connected to the Combus see section 2 for PC4164...

Page 21: ...l_____l_____l_____l l_____l_____l_____l 30 l_____l_____l_____l_____l_____l_____l l_____l_____l_____l 31 l_____l_____l_____l_____l_____l_____l l_____l_____l_____l 32 l_____l_____l_____l_____l_____l____...

Page 22: ...____l_____l l_________l 05 l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l 06 l_____l_____l l_________l l_____l_____l l_________l l_____l_____l...

Page 23: ...____l 02 l_____l_____l_____l_____l_____l_____l l_________l l_____l_____l l_____l_____l l_____l_____l l_____l_____l 03 l_____l_____l_____l_____l_____l_____l l_________l l_____l_____l l_____l_____l l___...

Page 24: ...____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l_...

Page 25: ...mily unit Figure 3 A smoke detector should be located on each story of the living unit Figure 2 In the family living units with more than one sleeping area a smoke detector should be located to protec...

Page 26: ...s 18 panic pendant 14 M Motion detector test 12 Mount devices 14 PC4164 RS 14 N Number serial 7 slot 8 zone 7 Numbers reference 2 P Panic pendant battery test 14 supervision 17 Partition programming f...

Page 27: ...attempts will be limited to a re placement of the product as the exclusive remedy for breach of warranty Under no circumstances shall Digital Security Controls Ltd be liable for any spe cial incident...

Page 28: ...Security Products TM 1998 Digital Security Controls Ltd 1645 Flint Road Downsview Ontario Canada M3J 2J6 416 665 8460 1 800 387 3630 Printed in Canada 29002890 R0...

Page 29: ...contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC4164 RS v2 0...

Page 30: ...ion It has been type tested and found to comply with the limits for Class B device in accordance with the specifications in Subpart B of Part 15 of FCC Rules which are designed to provide reasonable p...

Page 31: ...am Wireless Keys WLS909 8 3 4 Enroll and Program Handheld Keypads WLS910 10 Section 4 Testing Mounting Devices 12 4 1 Test the Placement of WLS904 WLS905 WLS906 and WLS907 Devices 12 4 2 Test WLS908 W...

Page 32: ...tors that are a part of this system may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke m...

Reviews: