Electrical Installation
Status Indicators
IDX 56 User Manual
4-40
mmag | 2020-04 | rel9398
4.4.1
NET Status
The LED displays the actual status and possible errors of the IDX in respect to the NET network:
•
Green LED shows the RUN state
•
Red LED indicates errors
Table 4-33
NET status LEDs
4.4.2
Device Status
The LED displays the actual status and possible errors of the IDX:
•
Green LED shows the status
•
Red LED indicates errors
Table 4-34
Device status LEDs
LED
Description
Green
Red
OFF
—
IDX is in state INIT
Blink
—
IDX is in state PRE-OPERATIONAL
Single flash
—
IDX is in state SAFE-OPERATIONAL
ON
—
IDX is in state OPERATIONAL
Flicker
—
IDX is in state BOOTSTRAP
—
OFF
IDX is in operating condition
—
Double flash
An application watchdog timeout has occurred
Example: Timeout of Sync Manager Watchdog
—
Single flash
IDX has changed the COM state due to an internal error
Example: Change of state “Op” to “SafeOpError” due to Sync Error
—
Blink
General Configuration Error
Example: State change commanded by master is not possible due to
actual settings (register, object, hardware configuration)
Blink = continuous blinking (
≈
2.5 Hz)
Flicker = continuous flickering (
≈
10Hz)
Flash = flashing (
≈
0.2 s), followed by pause of 1 s
LED
Description
Green
Red
Slow
OFF
Power stage is disabled. The IDX is in status…
• “Switch ON Disabled”
• “Ready to Switch ON”
• “Switched ON”
ON
OFF
Power stage is enabled. The IDX is in status…
• “Operation Enable”
• “Quick Stop Active”
OFF
ON
FAULT state. The IDX is in status…
• “Fault”
ON
ON
Power stage is enabled. The IDX is in temporary status…
• “Fault Reaction Active”
Flash
ON
No valid firmware or firmware download in progress
Flash = flashing (
≈
0.9 s OFF/
≈
0.1 s ON)
Slow = slow blinking (
≈
1 Hz)