9.0 OPTIONAL FUNCTIONS
www.maxcessintl.com
MAGPOWR Spyder-Plus-S1 Tension Control
MI 850A351 1 C
Page 40 of 68
9.2.2 Taper with Open Loop Tension Control
See Section 8.4.
9.3 CALIBRATE INPUTS (Load cell and Open Loop Tension only)
Navigate to the
Recal Inputs
menu
.
Press the
key.
Inputs for Dancers are calibrated in Section 7.4.
9.3.1
Select Setpoint Tension or Manual Voltage
When using an external voltage source for either Tension setpoint or Manual
Level the inputs must be calibrated for the external voltage source minimum
and maximum. These inputs are calibrated at the factory for use with a
potentiometer connected across the appropriate terminals of the Spyder.
Select either
Tension
or
Manual
and then Press
key to begin a calibration.
9.3.2
Apply Minimum Setpoint Tension or Manual Voltage
Apply the minimum Setpoint Tension or Manual voltage. Press
.
9.3.3
Apply Maximum Setpoint Tension or Manual Voltage
Apply the maximum Setpoint Tension or Manual voltage. Press
.
9.3.4
Calibration Done
The selected input calibration is now complete. Press
. This will return to the
Recal Inputs
menu.
9.4 CALIBRATE OUTPUTS
Navigate to the
Recal Outputs
menu. Press the
key to begin calibration.
The tension meter output is calibrated at the factory and no adjustment should
be required. The main output is calibrated at the factory for the 0-10 VDC and
-10V to +10V output range. The main output will need to be recalibrated when
choosing the 4 to 20 mADC range. See Section 6.2.2.3 or 7.2.2.5 or 8.2.2.5
and Figure 4 for configuring the output range.
9.4.1
OUTPUT 0% CAL
and
Use the
and
keys to adjust the main output on Term.30 and Term.31 to 0
volts or 4 mADC. Press
when finished.
9.4.2
OUTPUT 100% CAL
Use the
and
keys to adjust the main output on Term.30 and Term.31 to
+10vdc or 20 mADC. Press
when finished.
9.4.3
METER 100% CAL
Use the
and
keys to adjust the meter output on Term.33 and Term.34 to
1 mADC or 10 VDC. Press
when finished.