CALIBRATION
www.maxcessintl.com
DLCA NET-IP65-ECAT
MI 850A366 1
Page 32 of 44
7.0
Calibration
The DLCA NET-IP65-ECAT has two modes of calibration:
Precision and Weightless. Precision calibration is used when
applying a known weight with a rope in the web path to the load
cells for calibration. Typically this known weight should be 10% of
the load cell rating or greater. Weightless calibration is used
when a known weight is not convenient or desired.
The
Command Interface
is used to perform the calibrations.
A command request is entered in the
Command Request
. The
Command Response
will show the progress of the command and
when the command is complete. Errors will also be shown.
Parameters for Tension Zone 1 can be accessed in the group
Configuration Tension 1
and those for Tension Zone 2 can be
accessed in the group
Configuration Tension 2
.
7.1
Precision calibration procedure
Enter values into the calibration parameters shown below. These
parameters are available for Tension Zone 1 and Tension Zone 2.
Parameter Name and description
Default
Range
0x207
0x217
Decimal Point Position
Sets the decimal point position for the tension
display.
0 = 000000
1 = 000000.
2 = 00000.0
3 = 0000.00
4 = 000.000
5 = 00.0000
6 = 0.00000
0
{0, 6}
0x20D
0x21A
Calibration Tension
Calibration tension is the force of the known weight
hanging on the rope over the load cells.
500
{0,
999000}
0x211
0x21E
Maximum Tension
Maximum tension is the maximum tension expected
for the application. Do not exceed the rating of the
load cells.
500
{0,
999000}
Set the Load Cell excitation voltage 0x201 and which sensor
inputs are used 0x203. See section 6.3.