background image

HWA1-A

 

Air/water chillers with axial fans

 

24

 

19.3

 

E002 

 LOW PRESSURE 

If the on board pressure transducer detects a pressure lower than value set from the controller (

A16=5 

bar by default in cooling 

mode, 1.5 bar in heating mode) the alarm will be activated. In this case the compressor will stop immediately. The alarm will reset 
when the pressure goes over a hysteresis of 2.0bar. 
If the alarm occurs more than 3 times per hour, the alarm becomes a manual reset. 

19.4

 

E003 

 COMPRESSOR (C1) THERMAL PROTECTION 

These alarms are assigned with digital input. The alarm will be activated when the concerned digital input switches to the active 
state. It resets automatically when the contact returns to its rest state. 

19.5

 

E013 

 COMPRESSOR (C2) THERMAL PROTECTION 

These alarms are assigned with digital input. The alarm will be activated when the concerned digital input switches to the active 
state. It resets automatically when the contact returns to its rest state. 

19.6

 

E004 

 FAN MOTOR THERMAL PROTECTION 

These alarms are assigned with digital input. The alarm will be activated when the concerned digital input switches to the active 
state. It resets automatically when the contact returns to its rest state. 

19.7

 

E005 

 ANTIFREEZE ALARM 

The alarm will be activated when the outlet water temperature sensor is less than 4°C. It turns off when the temperature becomes 
higher than +7°C. 

19.8

 

E006 

 FLOW SWITCH ALARM 

The water side flow switch is already installed inside the unit and must NOT be tampered or bypassed in any way. The flow switch 
is bypassed for 10 seconds from the start-up of the machine. The alarm signalization occurs after 5 seconds of error persistence 
(lack of water flow, air in the circuit, etc.). The alarm is automatically reset for the first 2 times and goes off after 5 seconds. If the 
alarm occurs more than 3 times per hour, the manual reset of the alarm is required. 
The alarm is not active for 10 seconds after activating the circulator. 

19.9

 

E009 

 HIGH DISCHARGE TEMPERATURE 

In the case of a unit with the optional 

Gi

 module, there is a compressor discharge sensor with the following management of high 

discharge temperature: 
If the discharge temperature exceeds Pa 

C64

, the 

E009

 alarm appears and the compressors stop operation. 

If the discharge temperature drops below Pa 

C65

, the alarm disappears and the compressors are again ready to operate. 

19.10

 

E016 USAGE PUMP 1 THERMAL PROTECTION 

The alarm will be activated when the concerned digital input switches to the active state. It resets automatically when the contact 
returns to its rest state. 
In  case  of  alarm,  the  pump  in  matter  will  be  blocked.  If  there  is  no  other  resources  to  use  (1  serviceable  pump  only  or  both 
unserviceable pumps) obviously the whole unit will be blocked. 

19.11

 

E026 USAGE PUMP 2 THERMAL PROTECTION 

The alarm will be activated when the concerned digital input switches to the active state. It resets automatically when the contact 
returns to its rest state. 
In  case  of  alarm,  the  pump  in  matter  will  be  blocked.  If  there  is  no  other  resources  to  use  (1  serviceable  pump  only  or  both 
unserviceable pumps) obviously the whole unit will be blocked. 

19.12

 

E018 

 HIGH TEMPERATURE 

If the water outlet sensor records a value higher than 65°C for at least 50 seconds, the alarm is active. The alarm goes off when the 
temperature becomes below than 62°C. 

19.13

 

E042 

 POOR HEAT EXCHANGE 

This alarm will be activated only during sanitary hot water production and goes on during this operating mode when the outlet 
temperature  exceeds  the  parameter 

H01

. When the alarm  goes on, the compressors stop to operate. The alarm  goes off  if the 

return temperature drops below the 

H01 - b03

 threshold, and in this case the compressors are again ready to start-up. 

If the alarm goes on for 3 consecutive times during the same sanitary production cycle, it temporarily inhibits sanitary production 
and the unit returns to operate for the plant side. 
The inhibition of sanitary hot water production will be cancelled when the plant regulation achieves below the setpoint value with 

b05

 or in any case, if there is no need of thermoregulation on the plant. 

Note:

 The 

E042

 alarm remains active all along the entire cycle of sanitary hot water production. 

19.14

 

E101 - I/O MODULE COMMUNICATION TIMEOUT 

There is 10-second of timeout for communication between the main board and its I/O expansion boards. 
If the communication fails, the automatic reset alarm goes on. 
The alarm is only managed if the I/O configuration requires the presence of the module in matter. 
These alarms lock the whole unit because a priori do not know what functions are associated with the I/O ports on the module 
which does not communicate. 

Summary of Contents for HWA1-A 0140

Page 1: ...WA1 H 0285 This manual has been created for informative purpose The company declines any responsibility for the results of any projecting or any installation based on the explanations and or on the te...

Page 2: ...ONTROL 9 7 1 SET POINT ADJUSTMENT FROM 0 10V INPUT 9 7 2 CALCULATION OF THE CORRECTION WITH 0 10V INPUT 10 7 3 CALCULATION OF THE CORRECTION WITH RATIOMETRIC INPUT 10 7 3 1 Settings for standard clima...

Page 3: ...20 17 4 SETTING PARAMETERS 21 17 5 CONDENSATION PARAMETERS 21 17 6 COMPRESSOR PARAMETERS CONFIGURATION 21 18 USER AND INSTALLER ALLOWED CONFIGURATION TABLES 21 18 1 SET POINT S CONFIGURATION PARAMETE...

Page 4: ...and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectly knowledg...

Page 5: ...er voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a possi...

Page 6: ...e UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In the setting mode this button all...

Page 7: ...greater privilege Once you exit completely from the menus you lose the password privilege and need to re enter it 5 3 1 Setpoint menu You can display and change the various setpoints SETPOINT DESCRIP...

Page 8: ...ou can display the number of operating hours of the compressors and of the pumps Press the ESC button for 3 seconds to resets the actual number of operating hours Note that you can get access to the m...

Page 9: ...aged by the controller which calculates the compressor on and off events according to the setpoint based on heat within a differential If several compressors are configured the controller selects the...

Page 10: ...delay time between a compressor shutdown and shutdown of the next one 6 5 Deactivation of compressors for outdoor temperature If the outdoor temperature sensor is configured and is not in trouble so t...

Page 11: ...0 10V analogue input if enabled To enable the function you must set the H21 parameter to be 40 and change the values of the parameter b15 range 0 10 taking into account that if the input is at 0 volt...

Page 12: ...ulation of the circulator is linear type 8 1 Air purging of the system This function allows the air purging of the system to achieve this function the circulator will run at its maximum speed To enabl...

Page 13: ...draulic pump in anti freezing operation If the setting temperature is too low and the pump is off the pump will be activated automatically Pa P04 set antifreeze pump activation Pa P05 hysteresis pump...

Page 14: ...fan motor The condensation control is a function of the condensing pressure in chiller mode and the evaporation pressure in heat pump mode The fan speed can be independently controlled from the compre...

Page 15: ...nt the frost formation on the surface of the air air coil The frost formation on the evaporator which occurs more frequently at very low ambient temperatures in addition to greatly decreasing the ther...

Page 16: ...utput is active in COOLING operation The output is not active in heating operation The output is not active when the unit s OFF During the DHW production and defrosting cycle the output keeps the sett...

Page 17: ...ort Parameter Value Function H10 0 default Deactivated function 1 Active function in heating and cooling mode The remote on off function doesn t deactivate the domestic hot water production DHW 2 Acti...

Page 18: ...ction when the digital input is open Note If a temperature sensor is installed and configured this management will be ignored and the thermoregulation will be done on the basis of the detected tempera...

Page 19: ...below is reported an illustrating table regarding the operation of the system Mode of operation Active call of the heat pump Heating Temperature detected by the outlet sensor of the heat pump setpoin...

Page 20: ...ppropriately configured NC state connected on the terminals DI3E DI3E Thermostat contact normally open the secondary circulator will be activated Thermostat contact normally closed the secondary circu...

Page 21: ...SER AND INSTALLER The parameters can be activated and or edited by user or when using the installer password to get access in the CB Control menu which is located on the front panel of the unit DESCRI...

Page 22: ...6 COMPRESSOR PARAMETERS CONFIGURATION COMPRESSOR PARAMETERS CONFIGURATION Parameter Description Unit Default Range Visibility Allowed Configurations Notes n01 Output power from PC1 100 0 100 INSTALLER...

Page 23: ...output in heating sec 45 0 255 INSTALLER b08 Enabling dynamic set 0 0 1 INSTALLER b09 Max Offset in cooling dynamic set C 3 0 50 0 80 0 INSTALLER b10 Max Offset in heating dynamic set C 3 0 50 0 80 0...

Page 24: ...peration time of compressor with minimum frequency sec 60 0 255 INSTALLER 18 9 CONFIGURATION PARAMETERS OF GI Module PLANT MANAGEMENT Optional Parameter Description Unit Default Range Visibility Allow...

Page 25: ...peration If the discharge temperature drops below Pa C65 the alarm disappears and the compressors are again ready to operate 19 10E016 USAGE PUMP 1 THERMAL PROTECTION The alarm will be activated when...

Page 26: ...Antifreeze alarm Unit E006 Flow switch alarm Unit E009 High compressor s discharge temperature Unit E016 Usage pump 1 thermal overload protection Pump 1 E018 High temperature alarm in cooling operati...

Page 27: ...3 7208 7203 C 10 R W 5 0 23 0 Cooling 7204 C 10 R W 25 0 55 0 Heating 7205 C 10 R W 25 0 55 0 Sanitary 7206 C 10 R W 5 0 23 0 Second cooling 7207 C 10 R W 25 0 55 0 Second heating 7208 C 10 R W 0 0 80...

Page 28: ...C 10 R Compressors inhalation circuit 2 20433 C 10 R Compressor 1 discharge circuit 2 20434 C 10 R Compressor 2 discharge circuit 2 20435 C 10 R Compressor 3 discharge circuit 2 406 bar 100 R Pression...

Page 29: ...re fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature...

Page 30: ...lla performed correctly E060 13 Anti legionella failed or stopped E061 if enabled the cycle is activated only if the DHW 4 5 6 status is terminated by the machine if the read value is equal to 32766 t...

Page 31: ......

Page 32: ...r Supervisor Notes Catalogo Catalogue Katalog Catalogue MCO14110G7720 06 Serie Series Serie Serie S rie HWA1 A H 0140 0285 AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS Possible wasted electrical...

Reviews: