background image

PAGE 1

I - Ship ping And Pack ing List

Package 1 of 2 contains:

1 - Energy Recovery Ventilator Assembly
1 - Outdoor Fresh Air Hood w/ Filter
1 - Outdoor Exhaust Hood w/ Barometric Dampers

Package 2 of 2 contains:

1 - Balancing Damper Assembly
1 - Platform Support Rail
2 - Door Panels
1 - Bag Assembly

  1 - Roll of ¾" x 1 ¼" gasket 
  1 - 272" of 

1

8

" x ½"  gasket 

  1 - Field Wiring Harness 
  1 - Adapter Wiring Harness
10 - #14 Screws 
30 - #10 x ½" Gold Screws 
  1 - Installation Instructions 

II - Ship ping Dam age

Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is
found.

III - Gen eral

These instructions are intended as a general guide and do
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.

IV - Re quire ments

When installed, the unit must be electrically wired and
grounded in accordance with local codes or, in absence of
local codes, with the current National Electric Code,
ANSI/NFPA No. 70.

V  -  Ap pli ca tion

Unitary Energy Recovery Ventilator (UERV) are used with
3 to 6 ton rooftop units 

equipped with a balancing

damper assembly.

 These wheels conserve energy by

mixing warmer air with cooler air in the following manner:

Recovery Wheel Mode

The Recovery Wheel mode is accomplished by two
blowers providing continuous exhaust of stale indoor air
and replacement by equal amount of outdoor air. Energy
recovery is achieved by slowly rotating the energy
recovery wheel within the cassette frame work. In winter,
the UERV adsorbs heat and moisture from the exhaust air
stream during one half of a complete rotation and gives
them back to the cold,drier intake air supply during the
other half rotation. In summer, the process is automatically
reversed. Heat and moisture are absorbed from incoming
fresh air supply and transferred to the exhaust air stream.
This process allows outdoor air ventilation rates to be
increased by factors of three or more without additional
energy penalty or increase in size of heating or air
conditioning systems.

VI - Rig ging Unit For Lift ing

1.

Maximum weight of unit is —- 750 Lbs. (Crated)

2.

Remove crating. Then remove access panel to

retrieve bag assembly. Replace access panel.

3.

All panels must be in place for rigging.

4.

Lifting lugs are supplied with the unit. Loosen machine
bolts and rotate lifting lug.

CAUTION

Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.

WARNING

Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
e l e c t r i c a l   p o w e r   t o   u n i t   O F F   a t
disconnect switch(es). Unit may have
multiple power supplies.

MAXA-MI$ER

Ô

UNITARY ENERGY RECOVERY VENTILATOR

MODEL VR028A15M/H & VR028A25H  (STATIONARY) 

 INSTALLATION

INSTRUCTIONS

035-19268-002-A-0709 / R28A-18YDW

VII  -  In stal la tion

1.

Disconnect all power to rooftop unit.

2.

Remove the rooftop unit horizontal and return air
access panels. Also remove any hoods and/or power
exhaust equipment. Discard hoods, power exhaust
equipment horizontal supply and return air access
panels. 

See Figure 1.

3.

Remove return duct cover in the floor of rooftop unit.

ETL Certified per UL 1995
and CSA 22.2

E n e r g y   r e c o ve r y   C O M P O N E N T
certified to the AHRI Air-to-Air Energy 
Recovery Ventilation Equipment
Certification Program in accordance
w ith AHRI Standard 1060-2000.
Actual performance in packaged
equipment may vary.

Summary of Contents for VR028A15M/H

Page 1: ...m back to the cold drier intake air supply during the other half rotation In summer the process is automatically reversed Heat and moisture are absorbed from incoming fresh air supply and transferred...

Page 2: ...Position standoff legs so that flat foot is on bottom of stand and reinstall nut and bolt assembly Do not fasten tightly adjustment will need to be made when unit is put into position 12 Apply the pro...

Page 3: ...oftop unit This is accomplished by removing door panel at the return air opening loosing screw in center of damper then slide damper rod up or down in the return airstream and re tighten screw Replace...

Page 4: ...otating when in the air stream the UERV is always being cleared by air first in one direction then the other Because it is always dry dust or other particles impinging on the surface during one half c...

Page 5: ...icated sealed bearings no further lubrication is necessary Mechanical Inspection Make visual inspection of dampers linkage assemblies and UERV rotating bearings during routine maintenance Filters shou...

Page 6: ...two outer corners press the segment towards the center of the wheel and inwards against the spoke flanges If hand pressure does not fully seat the segment insert the flat tip of a screw driver betwee...

Page 7: ...04 1 09 1 09 1 09 1 08 1 05 0 99 0 90 0 82 0 75 0 89 0 88 0 87 0 85 0 81 0 75 0 66 0 59 0 5 0 69 0 68 0 65 0 62 0 57 0 5 0 42 0 35 0 25 0 00 0 20 0 40 0 60 0 80 1 00 1 20 1 40 1500 1600 1700 1800 200...

Page 8: ...PAGE 8...

Page 9: ...x Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152 Jack Transformer High Volt...

Page 10: ...w ambient switch 2 Step down transformer assembly for 460 volt units 3 Selective voltage terminal for proper unit voltage 4 Optional low ambient switch 5 Optional motorized intake damper 6 Optional st...

Page 11: ...PAGE 11 EQUIPMENT LAYOUT...

Page 12: ...g Contractor Start Up Mechanic q Inspect the unit for transit damage and report any damage on the carrier s freight bill q Check model number to insure it matches the job requirements q Install field...

Reviews: