background image

7

MATelec Australia reserves the right to alter technical data without notice

5.10 - 4 VSD

The VSD setup for proportional or PID speed control if the output type is set to VSD. 

RUNNING

MENU

VSD full speed level
VSD speed at stop level
Manual speed

Setup: 4 VSD

2.50m
31.0Hz
30.0Hz

RUNNING

MENU

PID proportional
PID integral
VSD no demand speed
Manual speed

Pipe fill

Sleep assist
Sleep boost pressure increase

Setup: 4 VSD

1.0
10.0
31Hz
30.0Hz

Boost
50kPa

RUNNING

MENU

VSD full speed temperature
VSD speed at setpoint
Manual speed

Setup: 4 VSD

62.5C
31.0Hz
30.0Hz

Level Control

Pressure Control

Temperature Control

Level

VSD full speed level

This is the analog level at which all the pumps will be running at full speed. Ensure that it is set lower than 

the 

setpoint

 if the 

control direction

 = ‘Fill’ and higher than the setpoint if the 

control direction

 = ‘Empty’.

VSD speed at stop 

level

This is the speed the pumps will be running at when at the 

setpoint

 stop level.

Manual speed

This is the speed a VSD controlled pump will run in manual. If the system is in auto and a duty or standby 

pump is running then the auto speed will override the 

manual speed

.

Pressure

PID Proportional

Proportional is the controlled speed response based on the analog feedback distance from 

setpoint

 

when configured for pressure VSD. ‘Increase’ = More responsive, ‘Decrease’ = Less responsive. 

See Step 

5.11 on the next page for more information on setting the PID.

PID Integral

Integral is the controlled speed response based on the analog feedback time from 

setpoint

 when 

configured for pressure VSD. ‘Increase’ = Slower response, ‘Decrease’ = Faster response. 

See Step 5.11 on 

the next page for more information on setting the PID.

VSD No demand 

speed

Once the pump speed has dropped below the 

No demand speed

 for the 

Sleep delay

 the system will go 

to sleep. 

See Step 5.12 on the next page for more information on setting the 

No demand speed

.

Manual speed

This is the speed a VSD controlled pump will run in manual. If the system is in auto and a duty or standby 

pump is running then the auto speed will override the 

manual speed

.

Pipe fill

If enabled, when the system wakes up from sleep and the analog pressure is more than 20% of the 

transducer range below 

setpoint

 the system will run a single duty pump at 45Hz to increase the pressure 

slowly. If the pump fails to increase pressure to less than 20% of the transducer range from 

setpoint

 in 10 

minutes a pipe fill fault will lockout the pumps.

Sleep assist

When the pump speed is not varying more than 0.1Hz for 20 seconds the system will initiate one of the 

following sleep assist modes if selected. ‘Speed minimise’ will slowly drop the pump speed to try and 

reach the 

No demand speed

. If the pressure drops from 

setpoint

 the system will resume normal running. 

‘Boost’ will temporarily adjust the 

setpoint

 to 

setpoint

 + 

sleep boost pressure

 increase to increase the 

system pressure, before returning to the normal running and 

setpoint

. This should slow the pump speed to 

below the 

No demand speed

 if there is no system demand.

Sleep boost pressure 

increase

This is the target pressure above the 

setpoint

 which the sleep boost will try and reach before returning to 

normal operation.

Temperature

VSD full speed 

temperature

This is the analog temperature at which all the pumps will be running at full speed. Ensure that it is set 

lower than the 

setpoint

 if the 

control direction

 = ‘Heat’ and higher than the 

setpoint

 if the 

control direction 

= ‘Cool’.

VSD speed at setpoint

This is the speed the pumps will be running at when at the 

setpoint

.

Manual speed

This is the speed a VSD controlled pump will run in manual. If the system is in auto and a duty or standby 

pump is running then the auto speed will override the 

manual speed

.

Step 5 - Setup (Continued)

 

 

Summary of Contents for Hydrowhiz FPC-63X20

Page 1: ...the control panel is to be used in Domestic Residential applications where specific Wiring Rules in respect of electrical supply protection may apply it is the responsibility of the installing electri...

Page 2: ...have internal filters to reduce the amount of distortion however in some applications additional filtering may be required If additional harmonic filtering is required to meet site specifications this...

Page 3: ...een RUNNING Enter PIN LOGIN REQUIRED 10 06 2020 17 50 58 OK 3 2 1 6 5 4 9 8 7 0 CANCEL 2020 5 6 Warning If the system mode is in auto tapping on a setting will bring up a Warning screen Press OK to tu...

Page 4: ...ype Number of pumps Pump limit Duty change period Setup 1 System Setup Level VSD 4 6 60 Mins RUNNING Current MENU 3 2 1 6 5 4 9 8 7 0 CANCEL OK 60 Mins Duty change period RUNNING MENU System type Pres...

Page 5: ...w level threshold When the analog goes below this threshold for 3 seconds the Low level protection will be activated High level threshold When the analog goes above this threshold for 3 seconds the Hi...

Page 6: ...uest Temperature control Sets the control direction for the corresponding System type Temperature cool heat Low temperature protection Alarm Triggers alarm only Lockout Triggers an alarm and shuts dow...

Page 7: ...e Sleep delay the system will go to sleep See Step 5 12 on the next page for more information on setting the No demand speed Manual speed This is the speed a VSD controlled pump will run in manual If...

Page 8: ...and destaging functions The no demand is to be set at the speed Hz at which one pump achieves the setpoint against a dead head shut discharge valve If the system is operating as a mains boosting syste...

Page 9: ...pump has not run for 7 days the pump run for 5 seconds to prevent seizing as long as the system mode is in sleep disabled or inhibit Max run fault protection Alarm Alarm only if a pump runs at the max...

Page 10: ...Main screen icon where the System Mode will need to be changed after completing Step 6 VSD commissioning Main Screen Alarms Logged Data Trend Plot Setup All Parameters Date Time Diagnostics RUNNING 10...

Page 11: ...50 50000 rpm Device for 60 Hz mains 50 1750 50000 rpm General motor data Carry out settings as specified by motor nameplate data Note When you enter the motor nameplate data take into account the phas...

Page 12: ...nominal motor voltage Hz 9908 MOTOR NOM SPEED Defines the nominal motor speed Must be equal to the value on the motor rating plate rpm 9909 MOTOR NOM POWER Defines the nominal motor power Must equal...

Page 13: ...level step DOL Standby start pressure step Standby start temp step Low level threshold Low pressure threshold Low temperature threshold High level threshold High pressure threshold High temperature t...

Page 14: ...ns bypass valve enable Sleep delay Top up valve open level Top up valve closed level 4 VSD Level Pressure Temperature VSD full speed level PID Proportional VSD full speed temperature VSD speed at stop...

Reviews: