background image

12

PUMP ON
FAULT

PUMP ON
FAULT

DISTRIBUTED BY:

INSTALLATION DATE:

SERIAL NUMBER:

POWER ON

LEVEL ALARM

PUMP ON

FAULT

AUTO

MAN

OFF

MUTE/

RESET

AT A GLANCE

A quick reference to the

controller’s Keypad and

Indicator functions and

meanings.

INDICATORS

PUSH BUTTONS

POWER ON

Power is turned on.

LEVEL ALARM ON

A high level alarm has been 

present for the preset time.

FLASHING

A low level alarm is present.

ON STEADY

Pump switched on to run.

ON STEADY

A pump fault/overload has

occurred.

FLASHING 

A prime loss 

fault has occurred.

Silences  the  siren  and  if  held

down  for  3  seconds,  clears  all 

faults

If  selected  (the  LED  indicator 

will  confirm if  on)  the  particular

pump  is  set  to  Automatic

Pumping Mode

Turns pump off

If selected (the LED indicator 

will confirm if on) the pump is 

set to Manual Pumping Mode

KEYPAD

MANUFACTURED BY MATelec AUSTRALIA  

 

 

EMAIL: [email protected]

MATelec reserves the right to alter technical specifications without notice.

Summary of Contents for FPC-30040-CON

Page 1: ...PUMP ON FAULT PUMP ON FAULT MAIN ISOLATOR P U M P C O N T R O L OWNER S OPERATION MANUAL Dual Pump Controller Installation and Operating Instructions MODEL FPC 30040 CON DOC FPC 30040 CON VER 1 0...

Page 2: ...st be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 A...

Page 3: ...r enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to main isolator is not restricted 4 Ensure cables condui...

Page 4: ...minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed conta...

Page 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Page 6: ...Mode Timeout With DIP Switch 5 set to On the pump will only remain in Manual Mode for 5 minutes after which time it automatically reverts to Auto High Level Alarm Reset The controller will also use th...

Page 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100k Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separa...

Page 8: ...tance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts C...

Page 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case...

Page 10: ...hermal Overload TOL2 415VAC Pump P2 95 96 NC Contact TOL2 A1 A2 Contactor 18A 240Vac C2 Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 Inline Relay 12Vdc R1 Common Fault R1 1 BMS Volt Fr...

Page 11: ...11 NOTES...

Page 12: ...level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears...