Summary of Contents for 77032600

Page 1: ...pen Interface Interface between MasterBus and CANopen MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www Mastervolt com Copyright 2016 Mastervolt 1...

Page 2: ...h can be recycled and reused When this crossed out wheeled bin symbol is attached to a product it means the product is covered by the European Directive 2012 19 EU Please be informed about the local s...

Page 3: ...l numbers base 16 This format is standard in CANopen All standard CANopen products will wait in the Pre operational state for a NMT Module Control message When a Start Remote Node Control message is r...

Page 4: ...COB ID The PDO on CANopen uses this COB ID This COB ID is independent from the configured Node ID Minimum value is 0x181 hexadecimal and the maximum value is 0x57F hexadecimal as defined by CANopen By...

Page 5: ...nfiguration parameters as in the configuration via the standard method but now combined into one string Meaning 285 This is the hexadecimal COB ID of the CANopen message Range 0x181 0x57F b0 Byte foll...

Page 6: ...can now refer to Device 1 being the MasterShunt In the Field config group select data field 1 We leave all settings as default COB ID hex 285 Byte 0 Direction MB CANopen Device 1 Page Monitoring Index...

Page 7: ...ata field button to save the configuration of data field 1 Make sure the option Auto start is still turned on The result The CANopen interface transmits out the heartbeat message every second No other...

Page 8: ...ents COB ID Select the COB ID for the Event PDO Example If you want a CANopen product to react on an empty battery event of your MasterShunt battery monitor Select the following configuration In the M...

Page 9: ...ive Event PDO option is checked the Interface will listen to a dedicated PDO with the data of 8 events COB ID The interface will listen to PDO messages with this COB ID Example To control the backligh...

Page 10: ...See figure 8 for the CANopen Interface connections 1 CAN_High 2 CAN_Low 3 CAN_Ground 4 Communication LED for MasterBus and CANopen MasterBus 4 1 2 3 MasterBus network MasterBus network Figure 8 Overvi...

Page 11: ...and CANopen Language English Current consumption 40 mA MasterBus Powering No Din rail mounting Yes Din rail 30 mm 1 2 inch Protection degree IP 21 Dimensions 66 x 78 x 32 mm 2 6 x 3 1 x 1 3 inch see F...

Page 12: ...Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 Email info mastervolt com...