IMPORTANT

 

FILTER RECHARGING

 

INSTRUCTIONS

 

9" FREEBOARD

 

(based on 30% bed lift)

 

 

Units must be recharged with Calcite/NS

-

Mix (a mixture of 

Calcite and Mag Oxide), to increase the pH of the water 
supply            

 

(Shipped in 50 lb. boxes)

 

 

FILTER BED

 

MBA-AN-10/13 Filters 

INSTRUCTIONS

 

 

1.

 

Close inlet and outlet stop valves located on conditioner’s service piping.

 

2.

 

Press  and  hold  the  Regeneration  button  for  5  seconds  until  the  drive  motor  starts.    When  the 
drive motor stops, the display will read “C1”.  At this point, unplug valve.

 

3.

 

Remove dome plug located near the top of the tank.  

(See Drawing)

 

4.

 

Use 5/8" siphon hose (provided with unit) to remove water from dome hole.

 

5.

 

If a layer of dirt or oxidized iron is directly on top of mineral bed, try to remove with siphon 
hose or wet

-

dry vac.

 

6.

 

Insert  yard  stick  into  dome  hole  and  force  through  the  bed.    This  will  reduce  the  chance  of 
channeling.

 

7.

 

Insert funnel into dome hole and pour the neutralizing media into the tank until the filter bed is 
7" below the dome hole.

 

8.

 

Open inlet stop valve and allow water to flow into the tank until water level reaches the dome 
hole.  Close inlet stop valve.

 

9.

 

Be sure that dome hole threads are clean.  Replace dome plug into dome hole and tighten..

 

10.

 

Open inlet and outlet stop valves 

slowly

 to their  maximum position.

 

11.

 

Plug valve back in  Press the Set button and UP arrow to advance the regeneration.  The display 
will read “C2”.

 

12.

 

Press the Set button and UP arrow to advance the regeneration.  The display will read “C3”.

 

13.

 

Repeat this procedure until the timer enters the “C7” position.

 

14.

 

The filter will now rinse and automatically advance to the service position.

 

15.

 

To totally regenerate the unit, press and hold the Regeneration button for 5 seconds.  Unit will 
now regenerate.

 

 

 

Recharging Neutralizers should be done between 6 months & 1 year.

 