Masport grandciew s3 Installation Sheet Download Page 1

wood fires.

A

B

E

F

G

H

150

350

200

345

730

607

858

A

B

E

F

G

H

§ 

Valid only when the room walls are at 90° to each other.

See " INSTALLING THE FLUE " for recommended Australian flue systems.

PRT. NO. 
DATE:

27.05.2010

595775

These instructions must be used in conjunction with the 'General Installation Instructions' for Masport

GRANDVIEW S3

‡ Note: Clearances are for fire hazard only. For durability of finishes or surfaces you should contact the 
relevant manufacturer for their specification. Masport accepts no responsibility for the deterioration of surfaces 
or finishes.

MODEL

INSTALLATION SPECIFICATION SHEET

POSITIONING YOUR FREE-STANDING WOODFIRE

MODEL

FLUE HEAT SHIELD

NEW ZEALAND

AUSTRALIA

MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm) 

 MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm)

MODEL

FLUE HEAT SHIELD

This fire has been tested to the Australian/New Zealand Standard AS/NZS 2918:2001 and all installations must 
be in accordance with the minimum clearances to combustibles indicated in these instructions.

CLEARANCE REQUIREMENTS

The minimum clearances to combustables may be reduced if the combustable walls are shielded with an 
approved non-combustable material. Details of suitable materials and appropriate clearance reduction factors 
are present in Section 3  of AS/NZS 2918:2001.

SINGLE POLISHED S/S 900mm

GRANDVIEW 

S3

O:\W-F INSTALLATION SPECIFICATIONS\Individual Installation Data Sheets\INSTALLATION 

SPECIFICATIONS INDIVIDUAL MASPORT\GRANDVIEW S3 Installation Data Sheets 595775-10-05-27.xls