wood fires.
A
B
E
F
G
H
R§
150
350
200
345
730
607
858
A
B
E
F
G
H
R§
§
Valid only when the room walls are at 90° to each other.
See " INSTALLING THE FLUE " for recommended Australian flue systems.
PRT. NO.
DATE:
27.05.2010
595775
These instructions must be used in conjunction with the 'General Installation Instructions' for Masport
GRANDVIEW S3
‡ Note: Clearances are for fire hazard only. For durability of finishes or surfaces you should contact the
relevant manufacturer for their specification. Masport accepts no responsibility for the deterioration of surfaces
or finishes.
MODEL
INSTALLATION SPECIFICATION SHEET
POSITIONING YOUR FREE-STANDING WOODFIRE
MODEL
FLUE HEAT SHIELD
NEW ZEALAND
AUSTRALIA
MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm)
MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm)
MODEL
FLUE HEAT SHIELD
This fire has been tested to the Australian/New Zealand Standard AS/NZS 2918:2001 and all installations must
be in accordance with the minimum clearances to combustibles indicated in these instructions.
CLEARANCE REQUIREMENTS
The minimum clearances to combustables may be reduced if the combustable walls are shielded with an
approved non-combustable material. Details of suitable materials and appropriate clearance reduction factors
are present in Section 3 of AS/NZS 2918:2001.
SINGLE POLISHED S/S 900mm
GRANDVIEW
S3
O:\W-F INSTALLATION SPECIFICATIONS\Individual Installation Data Sheets\INSTALLATION
SPECIFICATIONS INDIVIDUAL MASPORT\GRANDVIEW S3 Installation Data Sheets 595775-10-05-27.xls