Masport F10000 HW Installation Specification Sheet Download Page 1

wood fires.

A

B

E

F

G

H

250

300

200

445

680

607

858

200

300

200

395

680

607

858

§ 

Valid only when the room walls are at 90° to each other.

PRT. NO. 

DATE:

* Air-Group Special Insulated Flue Kit is same as AHD Special Insulated Flue Kit.

This fire has been tested and complies to the Australian/New Zealand Standard AS/NZS 2918:2001 and all 
installations must be in accordance with the minimum clearances to combustibles indicated in these instructions.

CLEARANCE REQUIREMENTS

The minimum clearances to combustables may be reduced if the combustable walls are shielded with an approved 
non-combustable material. Details of suitable materials and appropriate clearance reduction factors are present in 
Section 3  of AS/NZS 2918:2001.

F10000 HW      
F12000 HW      

FAIRHAVEN

FLOWMET UNIVERSL FLUE SYSTEM

AIR-GROUP SPECIAL INSULATED FLUE KIT *

MODEL

FLUE HEAT SHIELD

AUSTRALIA

MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm) 

02.10.2017

595772

These instructions must be used in conjunction with the 'General Installation Instructions' for Masport

F10000 HW          
F12000 HW          

FAIRHAVEN

‡ Note: Clearances are for fire hazard only. For durability of finishes or surfaces you should contact the relevant 
manufacturer for their specification. Masport accepts no responsibility for the deterioration of surfaces or finishes.

MODEL

INSTALLATION SPECIFICATION SHEET

POSITIONING YOUR FREE-STANDING WOODFIRE

Page 1 of 5

Summary of Contents for F10000 HW

Page 1: ...mbustable material Details of suitable materials and appropriate clearance reduction factors are present in Section 3 of AS NZS 2918 2001 F10000 HW F12000 HW FAIRHAVEN FLOWMET UNIVERSL FLUE SYSTEM AIR GROUP SPECIAL INSULATED FLUE KIT MODEL FLUE HEAT SHIELD AUSTRALIA MINIMUM DISTANCES TO HEAT SENSITIVE WALLS mm 02 10 2017 595772 These instructions must be used in conjunction with the General Instal...

Page 2: ...E KIT WITH 900mm S S REFLECTOR SHIELD AFP ASH FLOOR PROTECTOR AUSTRALIA ALL WITH FLUE HEATSHIELD MODEL Floor Protector Type Ø F10000 HW F12000 HW FAIRHAVEN FLOOR PROTECTOR Hearth REQUIREMENTS NOTE Where a fan is being fitted you may prefer to increase the A dimension to 100 mm to provide easier access for servicing If so the amount you add to A to bring it to 100 mm must also be added to the C and...

Page 3: ... ALLOWABLE WALL CLEARANCE FUF 300 200 607 1573 1347 715 858 AFP AGA 300 200 607 1573 1347 715 858 AFP FUF FLOWMET UNIVERSAL FLUE SYSTEM AGA AIR GROUP AHD SPECIAL INSULATED FLUE KIT WITH 900mm S S REFLECTOR SHIELD AFP ASH FLOOR PROTECTOR N R F10000 HW F12000 HW FAIRHAVEN E H M MODEL Flue Shield Floor Protector Distance above Floor C L FLOOR PROTECTOR TYPE AUSTRALIA Page 3 of 5 ...

Page 4: ...ain In New Zealand and some part of Australia it is required that the wood fire and floor protector are secured to prevent shifting in the event of an earthquake This is best done by fastening the wood fire right through the protector to the floor using two 8mm dynabolt or 8mm coach screws or toggle fasteners for wooden floors of appropriate length Seismic Restrain Holes Location Page 4 of 5 ...

Page 5: ...CIAL INSULATED FLUE KIT MUST BE MODIFIED AS PER DIAGRAM BELOW FOR F7000 HW 175MM FLUE KIT INSTALLATIONS IN AUSTRALIA FOR AUS INSTALLATION WITH FLOMET UNIVERSAL FLUE SYSTEM PLEASE REFER TO THE SPECIFIC FLUE INSTALLATION INSTRUCTIONS FROM FLUE MANUFACTURER Page 5 of 5 ...

Reviews: