Modem and Computer Use in Intrinsically Safe Circuits
Many HART
®
modems in use today are not approved for connecting to Intrinsically Safe
control circuits. Most portable computers are NOT approved for use in hazardous areas.
Modems can be safely connected to the safe area side of barriers, and isolators. Observe
HART
®
filter requirements.
MACTek
®
Intrinsically Safe modem, Model 010005
The VIATOR RS232 HART
®
Interface [Eex ia] IIC complies with the Essential Health and Safety
Requirements relating to the design and construction of equipment and protective systems
intended for use in potentially explosive atmospheres. Requirements given in Annex II of the
Directive 94/9/EC (ATEX Directive) of the European Parliament and EU Council of 23rd March
1994. Consult MACTek Corporation, http://www.MACTekcorp.com/company.html for detailed
requirements for safe use.
MACTek
®
Warning
"This product has not been tested by any certification agency such as Factory Mutual with
jurisdiction outside the European Union for intrinsic safety. The product can be used outside
the European Union (e.g. in the USA) on the sole authority of the buyer. MACTek
®
makes no
claims of suitability and offers no warranties regarding the use of this product for connection
of PCs to circuits extending into hazardous areas in countries outside the European Union."
Do not connect a PC or HART
®
modem to an intrinsically safe circuit except on the safe area
side of a barrier. Do not operate a PC in a hazardous area without compliance with local and
plant regulations.
Use of Hand-held Communicators In Intrinsically Safe Circuits
WARNING
The DPI 620 is not approved for use in hazardous areas that use
explosion proof safety practices. Do not use the DPI 620 unless
the area has been declared safe (Hot Work Permit).
The HART
®
Communicator DPI 620 is approved to communicate with intrinsically safe control
circuits in hazardous areas. Read the product Manual for the HART
®
Communicator. Observe
all warnings. The intrinsic safety entity parameters must be added to the SVI II ESD entity
parameters to determine suitability for use in any intrinsically safe circuit. Observe the labels
on the DPI 620 or consult the manufacturer.
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...