108
|
BHGE
Configure Menu
When installing an SVI II ESD for the first time you have to perform configuration before
calibration because configuration can affect calibration.
If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move the
SVI II ESD to a different valve or make any change to the valve position linkage, you must run
the find STOPS calibration again.
Figure 63 CONFIGure Menu
ATO
Setup
+
+
+
*
*
*
Air to....Menu
CONFIGuration Menu
ATC
*
PSI
*
*
BAR
KPA
ENGLISH
*
*
FRENCH
+/-
Pressure Units
Menu
Language
Menu
Air to
Menu
CONFIG
CONFIG
Language
Menu
Pressure
Menu
Units
+
Select display language.
Select display
units for pressure.
Select Air To Open (ATO)
or Air To Close (ATC). Must
match the actuator exactly.
Press * to select option.
Press + or - to accept and
proceed to next menu item.
SPANISH
PORTUGUESE
JAPANESE
ITALIAN
GERMAN
*
*
*
*
*
See Figure 62 on
page 107 for full menu
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...