Masoneilan SVI II ESD Installation and Maintenance Manual
=
|
105
© 2017 Baker Hughes, a GE company, LLC. All rights reserved.
Accessing Pushbuttons
The local pushbuttons are located behind a hinged cover, directly below the display window.
To open the cover loosen the screw and swing the cover down. Always re-fasten the cover
after use to protect pushbuttons from environmental contamination.
NOTE
When an exclamation mark (!) appears in the SVI II ESD display
window, it indicates that there is instrument status available.
The three pushbuttons perform the following functions:
Left Button
- Marked with
*
,
selects
or
accepts
the value or parameter option currently
displayed.
Middle Button
- Marked
–
,
moves back through the menu structure to the previous
item in the menu or decrements the currently shown value in the digital display.
Holding down the button causes the value to decrease at a faster rate.
Right Button
- Marked
+
,
moves forward through the menu structure to the next menu
item, or increments the currently shown value in the digital display. Holding down this
button causes the value to increase at a faster rate.
Pushbutton Locks and Configuration-Lock Jumper
Before performing any configuration or calibration functions using the local display you must
first ensure that the pushbuttons are placed in unlocked mode using ValVue ESD. The
positioner is factory set in unlocked mode. See ValVue ESD On Line Help for more details.
The SVI II ESD offers several security levels. It may be desirable, after initial setup, to lock the
pushbuttons so that the SVI II ESD parameters cannot be inadvertently changed by buttons.
Several levels of software modifiable pushbutton locks are provided.
Table 12 Pushbutton Lock Security Level
Level
Access
Security Level 3
Allow Local Buttons: Buttons on SVI II ESD are fully enabled.
Security Level 2
Lock Out Local Calibration and Configuration: Use the buttons to perform operations in normal
operating mode and manual mode. Do not go to configure or calibrate mode.
Security Level 1
Lock Out Local Manual: Examine variables in normal operating mode but do not put valve in
manual operating mode. Access to calibrate or configure modes is not available.
Security Level 0
Lock Out All Buttons: Buttons are disabled (level 0).
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...