Model: CDU-LCD
Doc. Ref. no.:- mMP/om/601
Issue no. 00.06
User’s Manual
Page 27 of 32
9.3 Analog Output
Sr.
No
Parameter Description
DNP
3
Point no.
Parameter
Type
Access
1.
Set point 2 of Differential Pressure H
0
Integer
R/W
2.
Set point 2 of Temperature H
1
Integer
R/W
3.
Set point 2 of Humidity H
2
Integer
R/W
4.
Set point 1 of Differential Pressure L
3
Integer
R/W
5.
Set point 1 of Temperature L
4
Integer
R/W
6.
Set point 1 of Humidity L
5
Integer
R/W
7.
Acknowledge Write
6
Integer
R/W
8.
Buzzer Delay
7
Integer
R/W
9.
Band Differential Pressure
8
Integer
R/W
10.
Band Temperature
9
Integer
R/W
11.
Band Humidity
10
Integer
R/W
12.
Buzzer Enable/Disable**
11
Integer
R/W
13.
AHU Status
##
12
Integer
R/W
14.
Memory Erase
$$
13
Integer
R/W
Table 15
** Buzzer Enable/Disable:
0
– Disable, 1 - Enable
##
AHU Status:
1
– OFF, 2 – ON, 3 - TRIP
$$
Memory Erase:
1 - Clear Log