User Manual
36
40005E (Enhanced Bargraph Indicator)
REF NO: m42B/om/101
Issue No: 02
Table 11 Input Type Selection
Type
I/PNO Type Display
Range
Resolution
NONE
0
none
-
-
E
1
E-Tc
-200 to 1000
C
0.1°C
J
2
J-tc
-200 to 1200
C
K
3
K-tc
-200 to 1370
C
T
4
T-tc
-200 to 400
C
B
5
B-tc
450 to 1800
C
1 °C
R
6
R-tc
0 to 1750
°
C
S
7
S-tc
0 to 1750
C
N
8
n-tc
-200 to 1300
°
C
RTD
9
RTD
-199.9 to 850.0
C
0.1°C
CU53
10
Cu53
-210.0 to 210.0
°
C
NI120
11
N.120
-70.0 to 210.0
°
C
-10 to 20mV
12
-10.20
-1999 to 9999 Counts
1 Count
0 to 100 mV
13
0-100
4 to 20mAmp
14
4-20
0 to 20mAmp
15
0-20
0 to 5V
16
0-5V
1 to 5V
17
1-5V
0 to 10V
18
0.10V
10 Point Linearization:
This instrument has feature of Ten-point linearization for each channel . User can define up-to
ten different segments of the full-scale input (in percentage) with Full-scale engineering value for each
segment. This linearization is only applicable to linear input types.
Here we are defining 10 Linearization percentage steps for the current inpu
t 4 mA to 20mA. Let‟s
have one example to understand this concept.
For Example:
10 point Linearization:
Zero = 00000 and Span = 9999, Let us assume the Unit is 4-20 mA.
Table 12 10
– point Linearization
Step No.
Linearization
Percent
Value
Linearization
Range
Display Value
Input Current
mA
1
LP01
10%
LR01
1000
5.6
2
LP02
20%
LR02
2000
7.2
3
LP03
30%
LR03
3000
8.8
4
LP04
40%
LR04
4000
10.4
5
LP05
50%
LR05
5000
12
6
LP06
60%
LR06
6000
13.6
7
LP07
70%
LR07
7000
15.2