![Marvair MAR7000 Product Data Sheet Download Page 13](http://html1.mh-extra.com/html/marvair/mar7000/mar7000_product-data-sheet_1734160013.webp)
MAR7000
13
1/2013, P/N 01757 Rev. B
The
Down
button decreases the value.
DO NOT FORGET THE ADMIN
PASSWORD!
The required password level is specified in the
prompt.
For
additional physical security and protection
from vandalism
, install the MAR7000 inside a
third-party locking thermostat guard/cover (but
proper airflow must be maintained).
Menu Items Access Levels
Menus
User Operator Administrator
Home Screen
* = Selectable, Default is User
Setpoint Adjust (Up/Down)
x*
x*
x*
System Mode (Auto/H/C/Off)
x*
x*
x*
Occupancy Override (On/Off)
x*
x*
x*
Fan Modes (Auto/On/Off)
x*
x*
x*
Main Menu* (
Default is User)
About
x
x
x
Advanced
x
x
Alarm
x
x
Date/Time
x
x
Schedule
x
x
Setpoints
x
x
System
x
x
Trend Viewer
x
x
x
Advanced Menu
Application
x
Additional Setup
x
Control Basic Programs
x
x
Communication
x
Date/Time
x
x
Device
x
Inputs
x
x
Limits
x
x
Motion Sensor
x
x
Security
x
Trend Logs
x
x
Test
x
x
This chart shows conditions in which an administrator password
is set (is not 0000) and default password levels are used.
(Advanced) Trend Logs
TRUE
TREND LOGS
TREND 1:
TREND 2: TRUE
TREND 3: FALSE
TREND 4: FALSE
TREND 5: FALSE
TREND 6: FALSE
TREND 7: FALSE
TREND #1
SPACE TEMPERATURE LOG
OBJECT REF: AI1
LOG ENABLE: TRUE
INTERVAL (MINS): 10
STOP W/FULL: FALSE
RESET COUNT: NO
COUNT: 256
TOTAL CNT: 613
VIEW LOG BUFFER
TL #1–SPACE TEMP
APR17 1:27PM, 71.4
APR17 2:27PM, 71.5
APR17 3:27PM, 71.6
APR17 4:27PM, 71.8
APR17 5:27PM, 76.3
APR17 6:27PM, 81.2
APR17 7:27PM, 82.3
NOTE: Space temperature (AI1) is the
default trend log #1. Depending on
configuration and options, other default
trend logs might exist.
The trend log buffer may be viewed by scrolling
down and selecting View Log Buffer. The buffer
may also be viewed from the Main Menu by
NOTE: The BACnet standard for log
intervals
is hundredths of seconds. The simplified
display on the MAR7000 converts the
value to minutes. However, building
automation software may display
hundredths of seconds and in different
ways.
NOTE: Other objects that can also be configured
for trend logs include:
• Humidity sensor = AI5
• Discharge air temperature = AI7
• Motion sensor = BI6
• Motion sensor occupancy override =
BV24
• See also the list of objects in