background image

                  

                              

2” NPT

 

MULTI-PORT RELIEF                                             

 

VALVE MANIFOLD – SERIES 

  INSTRUCTION MANUAL 

The contents of this publication are for informational purposes only.  While every effort has been made to ensure accuracy, these contents are not to be construed as warranties or 
guarantees, expressed or implied, regarding the products or services described herein or for their use or applicability.  Marshall Excelsior Co. reserves the right to modify or improve 
the designs or specifications of such products at any time without notice.  The MEC™ logo is the trademark of Marshall Excelsior Co. 

 

Form #996 Multi-Port Relief Valve Manifold IOM                                                                                         Revisi on Date 11/05/15 Rev B

 

1506 George Brown Dr. 

Marshall, MI 49068 

Phone (269) 789-6700 

Fax (269) 781-8340 

www.marshallexcelsior.com 

 

 

!WARNING! 

Failure to follow these instructions or to properly install and 
maintain this equipment could result in an explosion and/or 
fire causing property damage and personal injury or death.  

 

Install, operate and maintain Marshall Excelsior Co. 
equipment in accordance with federal, state, and local codes 
and these instructions. The installation in most states must 
also comply with NFPA standards 58 and 59, and ANSI/CGA 
6.2.1. 

 

Only personnel trained in the proper procedures, codes, 
standards and regulations of the LP-Gas and NH3 industries 
should install, maintain and service this equipment. 
Be sure all instructions are read and understood before 
installation, operation and maintenance. These instructions 
must be passed along to the end user of the product. 

 

!GENERAL WARNING! 

Marshall Excelsior products are mechanical devices that are 
subject to wear, contaminants, corrosion, and aging of 
components made of materials such as rubber and metal. 
Over time these devices will eventually become inoperative. 
The safe service life of these products will reflect the 
environment and conditions of use that they are subjected to. 
Regular inspection and maintenance is essential. Marshall 
Excelsior products have a long record of quality and service, so 
LP-Gas dealers may forget hazards that can arise from using 
aging devices that have outlived their safe service life. 

 

APPLICATION

For use with LPG & NH3 stationary storage containers with 2” 
NPT connections. These Relief Manifolds have an additional 
relief valve excluded from the flow rating, which allows for 
service and/or exchange of any one relief valve without 
evacuating the tank. Our large port selection handle allows for 
each specific valve port to be closed off so that the relief valve 
may be removed while the remaining valves remain under 
pressure protecting the tank and contents. Each manifold 
model is rated based on the flow through the relief valves with 
one valve removed from service. 
 

FEATURES: 

• Ductile Iron Body 
• All Stainless Steel Internal Components 
• Durable Teflon V-Pack Stem Seals 
• Large Diameter Port Selection Handle and Port Indicator 
• Molded Rubber Weather Guard for Manifold Rotary Gear 
• Available with 250 PSIG and 265 PSIG Relief Valve Set 
   Pressures 
• Relief valves provided with weep hole for drainage. 

 
 

REQUIREMENTS FOR PRESSURE RELIEF VALVES 

Every container used for storing or hauling LP-Gas and 
anhydrous ammonia must be protected by a pressure relief 
valve. These valves are designed to protect the container 
against the development of hazardous conditions which might 
be created by any of the following: 

 

Hydrostatic pressures due to overfilling or the trapping 
of liquid between two points. 

 

High pressures resulting from exposure of the 
container to excessive external heat. 

 

High pressures due to the use of incorrect fuel. 

 

High pressures due to improper purging of the 
container. 

 

NOTE

 

Consult NFPA #58 for LP-Gas and ANSI/CGA 6.2.1 for anhydrous 
ammonia, and/or any applicable local and state regulations 
governing the application and use of pressure relief valves. 

 
 
 
 

Summary of Contents for ME904-16

Page 1: ...ect the environment and conditions of use that they are subjected to Regular inspection and maintenance is essential Marshall Excelsior products have a long record of quality and service so LP Gas dealers may forget hazards that can arise from using aging devices that have outlived their safe service life APPLICATION For use with LPG NH3 stationary storage containers with 2 NPT connections These R...

Page 2: ...ndition of the valve it must be replaced WARNING Eye protection must be worn when performing inspection on relief valves under pressure Never look directly into a relief valve under pressure or place any part of your body where the relief valve discharge could impact it In some cases a flashlight and small mirror are suggested to assist when making visual inspections In the case of a pressure reli...

Page 3: ...erly inspect and maintain pressure relief valves could result in personal injuries property damage or death Relief valves are required to function under widely varying conditions Corrosion aging of the resilient seat disc and friction all proceed at different rates depending upon the nature of the specific environment and application Gas impurities product misuse and improper installations can sho...

Page 4: ...and cover open port with weather cap attached to manifold gear boot Note Relief valve must be replaced within a short period as the manifold port valve is not intended for primary seal for extended periods of time TO INSTALL A SAFETY RELIEF VALVE 1 Remove weather cap from closed manifold port 2 Install MEC relief valve of proper size and rating according to instructions provided with the valve WAR...

Page 5: ...For ME904S 16 Ref Description Qty 1 Body 1 2 Bonnet 1 3 Handle 1 4 Weather Boot 1 5 O Ring 1 6 Screw 14 7 Nameplate 1 8 Hex Lock Collar 1 9 Machine Key 1 10 Installation Plate 1 11 Removal Plate 1 12 Washer 1 13 Handle Stem Assembly 1 14 Clapper Assembly 1 15 Gland 1 16 Gland Seat Gasket PTFE 1 17 Stem Cap Screw 3 18 Lower Stem Bearing PTFE 1 19 Gland Spring 1 20 Male Adapter V Packing 1 21 V Pack...

Page 6: ...2 NPT MULTI PORT RELIEF VALVE MANIFOLD SERIES Form 996 Multi Port Relief Valve Manifold IOM Rev B 11 05 15 ...