37
Default Transfer Point Settings (CY54-04 Model)
Range
Effect. Lower Limit
Effect. Upper Limit
Buck On
Boost On
Buck Off
Boost Off
High Limit
120-150
120
150
150
130
High Buck
120-144
120
144
130
125
High Gap
3-7
3
7
5
5
Low Gap
3-7
3
7
5
5
Low Boost
96-120
96
120
102
105
Low Limit
90-120
90
120
90
100
Rebooting the UPS (TRTC Series UPSs)
Using the SNMP-CY54-04 SNMP Card, go to Configuration/Maintenance/Battery Test
Options.
1. Start a Battery Test.
2. While the Battery Test is running. Use the Inverter On/Off control (below the Battery
Test control) to turn off the Inverter. The output of the UPS turns OFF for 30 seconds.
The same procedure above can be rebooted using the front panel controls on the UPS.