Maple Armor NOU FW337 Installation Manual Download Page 1

DOC-FW337-UM-R1.1

INSTALLATION MANUAL

© 2016. MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.

8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2

All rights reserved. www.maplearmor.com

Page

1

of

2

FW337 NOU, NOTIFICATION OUTPUT UNIT

DESCRIPTION

The FW337 is a subassembly for the FW106 FACP

(Fire Alarm Control Panel). One NOU can support

two independent notification appliance circuits. The

circuit topology supports Class A or Class B wiring.

The maximum current is 2A per NAC, for a

maximum of 4A total per NOU. The address is set by

the rotary switch on the board. Valid address range is

1~4. It meets the UL864 10th Edition Listed standard

and the ULC-S527 3rd Edition Listed standard. Refer

to the installation and operation manual, DOC-

FW106-UM R1.1 for more details.

ATTENTION

The products must be installed in accordance with

NFPA 70, NFPA 72, CAN/ULC-S524,

and/or Canadian Electrical Code

depending on country of installation.

Check information of equipment used in

the system by other manufacturers for

any guidelines or restrictions.

NOTE

Any material extrapolated from this document or

from Maple Armor’s instructions or other documents

describing the product for use in promotional or

advertising claims, or for any other use, including

description of the product’s application, operation,

installation, and testing is the sole responsibility of

the user. Maple Armor will not assume any liability

for such use. In no case will Maple Armor’s liability

exceed the purchase price paid for a product.

SPECIFICATION

Nominal Voltage

24VDC

Voltage Range

20.4 to 26.4VDC

Standby Current

36mA

Alarm Current

54mA

Operating

Temperature

32°F to 120°F (0°C to 49°C)

Operating Humidity

0% to 93% RH

Dimension

215mm (L) × 55mm (W) ×

50.3mm (H)

Weight

11 oz (311.8 g)

SPECIFICATIONS

INSTALLATION

1. Remove all system power before installation,

first battery then AC. (To power up, connect the

AC first, then the battery.)

2. Mount the FW337 NOU onto the back box of the

FW106 FACP using two #4-40 screws provided,

see Figure 1. There are 8 identical slots for the

installation in the back box. They are shared by

the FW327 ALU, the FW337 NOU, the FW347

ROU, and the FW357 XNU, see Figure 2.